RZL-600 protection, automation and control terminal for 6-154 kV substations and feeders

The RZL-600 provides relay protection, automation, signalling and breaker control on 6-154 kV substations and feeders. It has 8 analog inputs, 21 discrete inputs and 17 relays, with free programmable logic available to order.

Type
Protection, automation and control device for substations and feeders
Voltage class
6-154 kV
Analog inputs
8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0)
Discrete inputs
21 (including 3 dry contact)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The RZL-600 series has an extended hardware and logic configuration. It is used for relay protection, automation, signalling, recording of fault parameters, diagnostics and breaker control on 6-154 kV substations and feeders. Logic can be programmed to order.

Typical duties are protection of overhead and cable lines, incoming and section breakers, backup protection of transformers, protection of high-voltage motors and automatic voltage regulation. Arc protection uses fibre optic sensors. A digital oscillograph and an event log are built in, and SCADA integration runs over the Modbus and IEC protocols.

The device can run from AC, DC or rectified operating current, including from current transformer circuits. Some versions desolenoid the breaker trip coils. Operating temperature is -40°C...+60°C.

Hardware: 8 analog inputs (IA, IB, IC, 3I0, UA, UB, UC, 3U0), 21 discrete inputs (3 of them dry contact), 3 fibre optic inputs with a 5 m cable, 17 relays (8 changeover, 6 make, 1 signalling, 2 double changeover) and 20 LEDs, 16 of them bi-colour. Interfaces are RS-485, Ethernet RJ-45 and USB. The dimensions are 270х220х110.5.

Versions: the RZL-600.1-В is the basic version, with no CT power, no desolenoiding and no fibre optic inputs. The RZL-600.2-В is extended, with CT power and desolenoiding but no fibre optic inputs. The RZL-600.3-В is the full version: CT power, desolenoiding and 3 fibre optic inputs, with 3 sensors included.

Protection, automation and control logic can be run as free programmable logic (FPL). In the version designation the letter У stands for flush mounting and the letter В for surface mounting. Events go to a log, fault waveforms are captured by a digital oscillograph, and data reach SCADA systems through the RS-485 and Ethernet RJ-45 ports.

Technical specifications

TypeProtection, automation and control device for substations and feeders
Voltage class6-154 kV
Analog inputs8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0)
Discrete inputs21 (including 3 dry contact)
Fibre optic inputs3 (cable length 5 m)
Relays17 (8 changeover, 6 make, 1 signalling, 2 double changeover)
LEDs20 (16 bi-colour)
InterfacesRS-485, Ethernet RJ-45, USB
ProtocolsModbus, IEC
Operating temperature-40°C...+60°C
Dimensions270х220х110.5

Part numbers

Show all part numbers (3)

RZL-600.1-V, RZL-600.2-V, RZL-600.3-V

How it compares with similar models

ParameterRZL-600 protection, automation and control terminal for 6-154 kV substations and feedersRZL-400 protection, automation and control terminal for 6-35 kV substations and feedersRZL-100 protection, automation and control device for 6-20 kV substations and feedersРЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions
Voltage class6-154 kV6-35 kV6-20 kV—
Discrete inputs21 (including 3 dry contact)9 (3 dry contact)8 (4 dry contact)12 (3 dry-contact)
Fibre optic inputs3 (cable length 5 m)3, in versions .3 and .63 (for arc protection sensors)—
Relays17 (8 changeover, 6 make, 1 signalling, 2 double changeover)8 (5 changeover, 3 make)8 (switching group, including 1 bistable K3 and 1 device integrity relay KWD)—
InterfacesRS-485, Ethernet RJ-45, USBRS-485, Ethernet RJ-45, USB—RS-485, Ethernet, USB
ProtocolsModbus, IECModbus RTU/TCP, IEC 60870-5-101/103/104Modbus RTU, Modbus TCPMODBUS RTU, MODBUS TCP

European equivalents

BELplus OZE, PROTECTA DTIVA, IDF / IDV / IDX transformer differential protection terminal, FPC 680

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

RZL-600 protection, automation and control terminal for 6-154 kV substations and feeders. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the RZL-600.1-В, .2-В and .3-В versions differ?

The RZL-600.1-В is the basic version: no CT power, no desolenoiding, no fibre optic inputs. The RZL-600.2-В adds CT power and desolenoiding, and the RZL-600.3-В also has 3 fibre optic inputs with 3 sensors included.

How many inputs and relays does the RZL-600 have?

8 analog inputs, 21 discrete inputs (3 dry contact), 3 fibre optic inputs, 17 relays and 20 LEDs.

How is the RZL-600 connected to SCADA?

Through RS-485 or Ethernet RJ-45, and a USB port is also fitted. Integration with SCADA systems uses the Modbus and IEC protocols.