РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions
The РЗЛ-05.ФХ provides protection, automation, signalling and breaker control for 6-154 kV connections. It has 5 analogue inputs, 12 discrete inputs and 13 relays, in six versions with CT-circuit backup supply, de-shunting and fibre-optic inputs.
- Application
- protection, automation and breaker control of 6-154 kV connections
- Auxiliary supply voltage
- 220 V (110 V)
- Analogue inputs
- 5 (IA, IB, IC, 3I0, 3U0)
- Temperature sensor input
- 1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.ФХ series are microprocessor protection and automation units for the connections of 6-154 kV switchgear. They cover protection, automation, signalling, fault recording, diagnostics and breaker control. Uses include overhead and cable lines, section breakers, substations and distribution points rated 6-154 kV. The units work with several breaker types.
Measuring inputs are 5 analogue channels (IA, IB, IC, 3I0, 3U0) and 1 temperature sensor input. There are 12 discrete inputs, 3 of them dry-contact, and 13 output relays. Other functions are a digital oscillograph, an event log, freely programmable logic (СПЛ) and SCADA integration. Interfaces are RS-485 and USB, the protocol is MODBUS RTU and the display is OLED.
The six versions РЗЛ-05.Ф1…Ф6 all use a 220 V (110 V) auxiliary supply and differ in three features. Backup supply from CT circuits is in Ф2, Ф4, Ф5 and Ф6. De-shunting of breaker current solenoids is in Ф5 and Ф6. Three inputs for fibre-optic sensors of the integrated arc protection are in Ф3, Ф4 and Ф6. Version Ф1 has none of these features.
The РЗЛ-05.Ф5 measures 205 × 240 × 195 mm and the РЗЛ-05.Ф6 measures 220 × 260 × 195 mm. Mounting is in a panel or cabinet. Operating temperature is −40 to +60 °C.
Free programmable logic is written with external circuits disconnected. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.
Technical specifications
| Application | protection, automation and breaker control of 6-154 kV connections |
|---|---|
| Auxiliary supply voltage | 220 V (110 V) |
| Analogue inputs | 5 (IA, IB, IC, 3I0, 3U0) |
| Temperature sensor input | 1 |
| Discrete inputs | 12 (3 dry-contact) |
| Output relays | 13 |
| Backup supply from CT circuits | Ф2, Ф4, Ф5, Ф6 |
| De-shunting of current solenoids | Ф5, Ф6 |
| Fibre-optic sensor inputs | 3 (Ф3, Ф4, Ф6) |
| Interfaces | RS-485, USB |
| Protocol | MODBUS RTU |
| Display | OLED |
| РЗЛ-05.Ф5 dimensions | 205 × 240 × 195 mm |
| РЗЛ-05.Ф6 dimensions | 220 × 260 × 195 mm |
| Operating temperature | −40…+60 °C |
Part numbers
Show all part numbers (6)
РЗЛ-05.Ф1, РЗЛ-05.Ф2, РЗЛ-05.Ф3, РЗЛ-05.Ф4, РЗЛ-05.Ф5, РЗЛ-05.Ф6
How it compares with similar models
| Parameter | РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions | РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions | РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers | РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions |
|---|---|---|---|---|
| Application | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections | protection and automation of a 110-35-10(6) kV voltage transformer | protection, automation and breaker control of 6-154 kV connections |
| Analogue inputs | 5 (IA, IB, IC, 3I0, 3U0) | 8 | 7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) | 8 |
| Discrete inputs | 12 (3 dry-contact) | 12 (3 dry-contact) | 12 (3 dry-contact) | 20 |
| Output relays | 13 | 13 | 13 (4 with changeover group, 1 bistable К7, 1 KWD) | 17 |
| Backup supply from CT circuits | Ф2, Ф4, Ф5, Ф6 | В2, В4, В5, В6, В12, В14, В15, В16 | — | А2, А4, А5, А6, А12, А14 |
| De-shunting of current solenoids | Ф5, Ф6 | В5, В6, В15, В16 | — | А5, А6 |
European equivalents
BELplus OZE, PROTECTA DTIVA, IDF / IDV / IDX transformer differential protection terminal, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection)
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do versions РЗЛ-05.Ф1…Ф6 differ?
They differ in CT-circuit backup supply (Ф2, Ф4, Ф5, Ф6), de-shunting (Ф5, Ф6) and three fibre-optic inputs (Ф3, Ф4, Ф6). Ф1 has none of them.
What inputs and outputs does the unit have?
It has 5 analogue inputs (IA, IB, IC, 3I0, 3U0), a temperature sensor input, 12 discrete inputs (3 dry-contact) and 13 relays.
What supply voltage and temperature range apply?
The auxiliary supply is 220 V (110 V). Operating temperature is −40 to +60 °C.
Similar equipment from other manufacturers