International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection)

SMPR multifunction microprocessor terminals protect MV feeders, combining overcurrent, voltage, power and frequency protection with energy metering. SMPR-2 has a thermal model and directional earth fault protection 67N. SMPR ETH works on a Modbus TCP/IP network.

SMPR / SMPR ETH
27, 32, 37, 46, 47, 50, 50N/G, 51, 51N/G, 55, 59, 68, 81, 86
SMPR-2
49, 50, 50N/G, 51, 51N/G, 67N (directional earth fault), 68, 86
Measurements (SMPR)
currents, voltages, P, Q, S, energy MWh / Mvarh, cos φ, frequency, maximum demand
CT primary current
5–6000 A, step 5 A; inputs 1 A or 5 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

SMPR combines in one terminal the current protection of a medium-voltage feeder, voltage, power and frequency protection, and measurement of electrical quantities. The terminals are installed as main and backup protection of feeders in distribution networks, power plants and industrial networks, as well as transformers, overhead and cable lines and generators. The family consists of three models, SMPR, SMPR ETH and SMPR-2, which differ in functions and ports.

SMPR and SMPR ETH measure the RMS values of line currents and earth current, line or phase voltages, active, reactive and apparent power in both directions, active energy in MWh and reactive energy in Mvarh, power factor and frequency. Present and maximum demand are recorded for phase current and power. The protections cover undervoltage (27), directional power (32), undercurrent (37), negative-sequence current (46), voltage phase sequence (47), instantaneous and time-delayed overcurrent for phases and earth (50, 50N/50G, 51, 51N/51G), power factor (55), overvoltage (59) and frequency (81). Function 68 issues a blocking signal and 86 provides lockout with manual reset. There is an overload alarm and a count of interrupted kA per phase.

SMPR-2 focuses on current protection with a thermal model. It provides overload protection (49), phase and earth overcurrent, directional earth fault protection (67N) and functions 68 and 86. Inverse curves in all models follow ANSI, IAC or IEC/BS142, from moderately to extremely inverse, and a definite time characteristic is also available.

The CT primary current is set from 5 to 6000 A in steps of 5 A, with secondary inputs of 1 A or 5 A. The terminal has a trip relay, three assignable auxiliary relays, a relay for loss of supply or internal fault, three programmable digital inputs and a breaker position input. Breaker failure on tripping is monitored, and the panel shows the position open, closed or earthed.

LEDs and an LCD show measured values, the cause of the last trip and stored fault values. The terminal is programmed from the touch keypad or remotely. SMPR ETH has an Ethernet port with Modbus TCP/IP and two RS-485 ports with Modbus RTU, SMPR-2 is fitted with RS-232 and RS-485, and Ethernet is available to order. The manufacturer's dry-type and cast-resin current transformers are used together with the terminals.

Technical specifications

SMPR / SMPR ETH27, 32, 37, 46, 47, 50, 50N/G, 51, 51N/G, 55, 59, 68, 81, 86
SMPR-249, 50, 50N/G, 51, 51N/G, 67N (directional earth fault), 68, 86
Measurements (SMPR)currents, voltages, P, Q, S, energy MWh / Mvarh, cos φ, frequency, maximum demand
CT primary current5–6000 A, step 5 A; inputs 1 A or 5 A
Outputs1 trip + 3 programmable + 1 fault
Digital inputs3 programmable + 1 breaker position
CommunicationSMPR ETH: 1 Ethernet (Modbus TCP/IP) + 2 RS-485 (Modbus RTU); SMPR-2: RS-232 + RS-485, Ethernet to order
CharacteristicsANSI, IAC, IEC/BS142

Request a price and lead time

SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 10 98 00
HS, 6 digits8537 10
CN (EU)8537 10 98
HTSUS (USA)8537 10 91 70
China customs tariff8537 10 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which protection functions does SMPR have?

SMPR and SMPR ETH provide functions 27, 32, 37, 46, 47, 50, 50N/G, 51, 51N/G, 55, 59, 68, 81 and 86. The terminal also measures power, energy, cos φ and frequency.

When should SMPR-2 be chosen?

When current protection with a thermal model (49) and directional earth fault protection (67N) are needed. SMPR-2 also provides phase and earth overcurrent and functions 68 and 86.

Which communication protocols do the terminals support?

SMPR ETH has Ethernet with Modbus TCP/IP and two RS-485 ports with Modbus RTU. SMPR-2 is fitted with RS-232 and RS-485, and Ethernet is available to order.