International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

CIF / MCI / HPCI — current injection units for arc suppression coil tuning and pulse earth fault location

CIF, MCI and HPCI are modular systems for injecting current into the neutral, with which arc suppression coils are tuned precisely in highly symmetrical networks. They work at neutral displacement voltage < 0.5 %, and HPCI also serves as a pulse cabinet for earth fault location.

CIF
standard version for 20 kV networks up to 1000 A capacitive current, manual reduction of power
MCI
multi-frequency injection, 20 kV networks up to 1300 A, no chokes or additional voltage transformers
HPCI
current injection + pulse cabinet function for earth fault location
Application
neutral displacement voltage < 0.5 %

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

CIF is the standard version for 20 kV networks with capacitive current up to 1000 A; injection power is reduced manually. MCI uses multi-frequency injection in 20 kV networks up to 1300 A and needs no chokes or additional voltage transformers. HPCI combines current injection and the pulse cabinet function, so one unit covers both coil tuning and earth fault location. All versions can be retrofitted to existing REG-DP and REG-DPA regulators.

Technical specifications

CIFstandard version for 20 kV networks up to 1000 A capacitive current, manual reduction of power
MCImulti-frequency injection, 20 kV networks up to 1300 A, no chokes or additional voltage transformers
HPCIcurrent injection + pulse cabinet function for earth fault location
Applicationneutral displacement voltage < 0.5 %
Compatibilityretrofit to existing REG-DP / REG-DPA

Request a price and lead time

CIF / MCI / HPCI — current injection units for arc suppression coil tuning and pulse earth fault location. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)9032 89 00 00
HS, 6 digits9032 89
CN (EU)9032 89 00
HTSUS (USA)9032 89 60 85
China customs tariff9032 89 90 10

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

For what capacitive network current are CIF and MCI designed?

CIF is used in 20 kV networks up to 1000 A, MCI in 20 kV networks up to 1300 A.

When is current injection needed for tuning arc suppression coils?

In highly symmetrical networks where the neutral displacement voltage is below 0.5 %.

Can the system be added to an existing regulator?

Yes, CIF, MCI and HPCI can be retrofitted to existing REG-DP and REG-DPA.