РЗЛ-05.Т2 and РЗЛ-05.Т3 protection units for 35–110 kV transformers and autotransformers
The РЗЛ-05.Т2 and РЗЛ-05.Т3 are main protection units for two- and three-winding transformers or autotransformers with a high-voltage side of 35–110 kV. The Т2 has 11 analogue and 12 discrete inputs, the Т3 has 14 and 20. Both include a digital oscillograph and an event log.
- Application
- main protection of two- and three-winding transformers and autotransformers with high voltage 35–110 kV
- Rated supply voltage
- 220 V, 110 V
- Supply type
- AC, DC, rectified voltage
- Rated measured current (Inom)
- 5 A or 1 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.Т2 and РЗЛ-05.Т3 are microprocessor relay protection and automation units that act as main protection for a transformer or autotransformer with a high-voltage side of 35–110 kV. The Т2 serves two-winding units and the Т3 three-winding units. Functions include differential protection with harmonic restraint and overcurrent protection. The units connect to SCADA systems and carry a digital oscillograph and an event log.
The input and output count depends on the model. The РЗЛ-05.Т2 has 11 analogue inputs, 12 discrete inputs and 13 relays. The РЗЛ-05.Т3 has 14 analogue inputs, 20 discrete inputs and 17 relays. Three of the discrete inputs are dry-contact type. Rated measured current Inom is 5 A or 1 A, and the supply is 220 V or 110 V, which may be AC, DC or rectified.
Integrated arc protection works with fibre-optic sensors. Versions with the -Д suffix have 3 sensor inputs, with a sensor cable length of 5 m. Logic can be programmed (СПЛ). The event log holds 254 records and the oscillograph stores 32 records of 65 seconds each. Communication with the upper level is by RS-485 and USB using MODBUS RTU.
The version code sets the secondary currents. The digits after the model designation give the 1 A or 5 A rating of each winding, and the last digit gives the 3I0 current. For example, РЗЛ-05.Т2-55-1 has 5 A on the high-voltage side and first low-voltage winding, and 1 A for 3I0. The -Д suffix means three fibre-optic inputs.
The РЗЛ-05.Т2 measures 205 × 240 × 195 mm and the РЗЛ-05.Т3 measures 265 × 240 × 195 mm. Operating temperature is −40 to +60 °C. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.
Technical specifications
| Application | main protection of two- and three-winding transformers and autotransformers with high voltage 35–110 kV |
|---|---|
| Rated supply voltage | 220 V, 110 V |
| Supply type | AC, DC, rectified voltage |
| Rated measured current (Inom) | 5 A or 1 A |
| Analogue inputs | РЗЛ-05.Т2 – 11; РЗЛ-05.Т3 – 14 |
| Discrete inputs | РЗЛ-05.Т2 – 12; РЗЛ-05.Т3 – 20 |
| Dry-contact discrete inputs | 3 |
| Output relays | РЗЛ-05.Т2 – 13; РЗЛ-05.Т3 – 17 |
| Fibre-optic sensor inputs | 3 (-Д version) |
| Sensor cable length | 5 m |
| Event log | 254 records |
| Oscillograms | 32 records of 65 s each |
| Interfaces | RS-485, USB |
| Protocol | MODBUS RTU |
| РЗЛ-05.Т2 dimensions | 205 × 240 × 195 mm |
| РЗЛ-05.Т3 dimensions | 265 × 240 × 195 mm |
| Operating temperature | −40…+60 °C |
Part numbers
Show all part numbers (18)
РЗЛ-05.Т2-55-1, РЗЛ-05.Т2-55-5, РЗЛ-05.Т2-15-1, РЗЛ-05.Т2-11-1, РЗЛ-05.Т2-55-1-Д, РЗЛ-05.Т2-55-5-Д, РЗЛ-05.Т2-15-1-Д, РЗЛ-05.Т2-11-1-Д, РЗЛ-05.Т3-555-1, РЗЛ-05.Т3-555-5, РЗЛ-05.Т3-111-1, РЗЛ-05.Т3-155-1, РЗЛ-05.Т3-115-1, РЗЛ-05.Т3-555-1-Д, РЗЛ-05.Т3-555-5-Д, РЗЛ-05.Т3-111-1-Д, РЗЛ-05.Т3-155-1-Д, РЗЛ-05.Т3-115-1-Д
How it compares with similar models
| Parameter | РЗЛ-05.Т2 and РЗЛ-05.Т3 protection units for 35–110 kV transformers and autotransformers | РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers | РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions | РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs |
|---|---|---|---|---|
| Application | main protection of two- and three-winding transformers and autotransformers with high voltage 35–110 kV | protection and automation of a 110-35-10(6) kV voltage transformer | protection, automation and breaker control of 6-154 kV connections | distance protection and automation of 35(110) kV lines |
| Analogue inputs | РЗЛ-05.Т2 – 11; РЗЛ-05.Т3 – 14 | 7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) | 5 (IA, IB, IC, 3I0, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) + 1 temperature sensor |
| Discrete inputs | РЗЛ-05.Т2 – 12; РЗЛ-05.Т3 – 20 | 12 (3 dry-contact) | 12 (3 dry-contact) | 20 (3 dry-contact) |
| Output relays | РЗЛ-05.Т2 – 13; РЗЛ-05.Т3 – 17 | 13 (4 with changeover group, 1 bistable К7, 1 KWD) | 13 | 17 (4 with changeover group, 1 bistable К7, 1 integrity relay KWD) |
| Fibre-optic sensor inputs | 3 (-Д version) | 3 (ТН03 version) | 3 (Ф3, Ф4, Ф6) | 3, 5 m cable (fibre-optic versions) |
| Interfaces | RS-485, USB | — | RS-485, USB | RS-485 or Ethernet (TX) depending on version; USB |
European equivalents
IDF / IDV / IDX transformer differential protection terminal, BELplus OZE, SPR10, PROTECTA DTIVA
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.Т2 and РЗЛ-05.Т3 protection units for 35–110 kV transformers and autotransformers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the РЗЛ-05.Т2 differ from the РЗЛ-05.Т3?
The Т2 is for two-winding transformers, with 11 analogue inputs, 12 discrete inputs, 13 relays and dimensions of 205 × 240 × 195 mm. The Т3 is for three-winding units, with 14, 20 and 17, and dimensions of 265 × 240 × 195 mm.
What does the -Д suffix in a part number mean?
It marks the version with three inputs for fibre-optic arc protection sensors. Sensor cable length is 5 m.
What rated current and supply apply?
Rated measured current is 5 A or 1 A, depending on the version code. Supply is 220 V or 110 V, AC, DC or rectified.