РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks
The РЗЛ-01.03 provides relay protection, automation, control and signalling for 6-35 kV cable and overhead lines and for incoming and section breakers. It has a power supply from the current circuits with de-shunting, three-stage overcurrent protection and RS485 and RS232 interfaces with Modbus RTU.
- Rated frequency
- 50 Hz
- Frequency range
- 45–55 Hz
- Rated input current
- 5 A
- Continuous permissible input current
- 20 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-01.03 belongs to the РЗЛ-01 microprocessor relay series and performs relay protection, automation, control and signalling. It is installed on outgoing cable and overhead power lines of 6-35 kV and on incoming and section breakers, and it can serve as backup protection for transformers. This version has non-directional earth fault protection, a power supply unit fed from the current circuits and de-shunting.
Overcurrent protection has three stages. Each stage has a current setting of 0.1–25 In in steps of 0.02 In and a time delay of 0 to 32 s in steps of 0.05 s. Settings are made by software and can be blocked, including by any discrete input. Current measurement accuracy is up to 3 % and the reset ratio is 0.95. For auto-reclosing, the re-ready time of stages 1 and 2 is 5–600 s in steps of 0.1 s.
There are six discrete inputs for 50 Hz AC with Unom 220 V. Five programmable command relays are fitted, one changeover and four normally open, plus a separate fault relay with a changeover contact. The contacts switch 220 V AC at 5 A and 1000 VA. Communication is through RS485 and RS232 with Modbus RTU.
Rated input current is 5 A with 20 A permissible continuously, and the power drawn from each phase on a supply from the voltage circuits is 2.5 VA. Versions РЗЛ-01.03-Д2 for an incoming breaker and РЗЛ-01.03-Д3 for a 35-6 kV section breaker are offered with extra discrete inputs. Dimensions are 125x180x230 mm.
Technical specifications
| Rated frequency | 50 Hz |
|---|---|
| Frequency range | 45–55 Hz |
| Rated input current | 5 A |
| Continuous permissible input current | 20 A |
| Power consumption, max | 5 VA + 0.4 VA per energised discrete output |
| Short supply voltage loss (at Unom = 220 V) | 500 ms |
| Self-test time after power-up | 250 ms |
| Overcurrent protection | Three-stage |
| Current setting range for each stage | 0.1 – 25 In in steps of 0.02 In |
| Time delay setting range for each stage | 0 – 32 s in steps of 0.05 s |
| Current measurement accuracy, max | 3 % |
| Overcurrent reset ratio | 0.95 |
| Auto-reclosing re-ready time range, stages 1 and 2 | 5 – 600 s in steps of 0.1 s |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover |
| AC switching capacity | 220 V, 5 A, 1000 VA (cosφ ≥ 0.6) |
| Interfaces | RS485, RS232 |
| Protocol | Modbus RTU |
| Dimensions | 125х180х230 mm |
Part numbers
Show all part numbers (3)
РЗЛ-01.03, РЗЛ-01.03-Д2, РЗЛ-01.03-Д3
How it compares with similar models
| Parameter | РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks | РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks | РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks | РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks |
|---|---|---|---|---|
| Rated frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz (range 45–55 Hz) |
| Overcurrent protection | Three-stage | Three-stage | Three-stage | three-stage |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | 6, 220 V |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover + 4 normally open |
| Dimensions | 125х180х230 mm | 125х180х230 mm | 125х180х230 mm | 125x180x230 mm |
European equivalents
PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which circuits is the РЗЛ-01.03 intended for?
Outgoing cable and overhead lines of 6-35 kV, incoming and section breakers, and as backup protection for transformers.
How do РЗЛ-01.03-Д2 and РЗЛ-01.03-Д3 differ?
Д2 is for an incoming 35-6 kV breaker and has two extra discrete inputs, Д3 is for a section breaker and has three extra.
What settings does the overcurrent protection have?
Three stages, each with a current setting of 0.1–25 In and a time delay of 0–32 s.