International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks

The РЗЛ-01.03 provides relay protection, automation, control and signalling for 6-35 kV cable and overhead lines and for incoming and section breakers. It has a power supply from the current circuits with de-shunting, three-stage overcurrent protection and RS485 and RS232 interfaces with Modbus RTU.

Rated frequency
50 Hz
Frequency range
45–55 Hz
Rated input current
5 A
Continuous permissible input current
20 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РЗЛ-01.03 belongs to the РЗЛ-01 microprocessor relay series and performs relay protection, automation, control and signalling. It is installed on outgoing cable and overhead power lines of 6-35 kV and on incoming and section breakers, and it can serve as backup protection for transformers. This version has non-directional earth fault protection, a power supply unit fed from the current circuits and de-shunting.

Overcurrent protection has three stages. Each stage has a current setting of 0.1–25 In in steps of 0.02 In and a time delay of 0 to 32 s in steps of 0.05 s. Settings are made by software and can be blocked, including by any discrete input. Current measurement accuracy is up to 3 % and the reset ratio is 0.95. For auto-reclosing, the re-ready time of stages 1 and 2 is 5–600 s in steps of 0.1 s.

There are six discrete inputs for 50 Hz AC with Unom 220 V. Five programmable command relays are fitted, one changeover and four normally open, plus a separate fault relay with a changeover contact. The contacts switch 220 V AC at 5 A and 1000 VA. Communication is through RS485 and RS232 with Modbus RTU.

Rated input current is 5 A with 20 A permissible continuously, and the power drawn from each phase on a supply from the voltage circuits is 2.5 VA. Versions РЗЛ-01.03-Д2 for an incoming breaker and РЗЛ-01.03-Д3 for a 35-6 kV section breaker are offered with extra discrete inputs. Dimensions are 125x180x230 mm.

Technical specifications

Rated frequency50 Hz
Frequency range45–55 Hz
Rated input current5 A
Continuous permissible input current20 A
Power consumption, max5 VA + 0.4 VA per energised discrete output
Short supply voltage loss (at Unom = 220 V)500 ms
Self-test time after power-up250 ms
Overcurrent protectionThree-stage
Current setting range for each stage0.1 – 25 In in steps of 0.02 In
Time delay setting range for each stage0 – 32 s in steps of 0.05 s
Current measurement accuracy, max3 %
Overcurrent reset ratio0.95
Auto-reclosing re-ready time range, stages 1 and 25 – 600 s in steps of 0.1 s
Discrete inputsAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom
Command output relays1 changeover, 4 normally open; fault relay changeover
AC switching capacity220 V, 5 A, 1000 VA (cosφ ≥ 0.6)
InterfacesRS485, RS232
ProtocolModbus RTU
Dimensions125х180х230 mm

Part numbers

Show all part numbers (3)

РЗЛ-01.03, РЗЛ-01.03-Д2, РЗЛ-01.03-Д3

How it compares with similar models

ParameterРЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networksРЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networksРЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networksРЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks
Rated frequency50 Hz50 Hz50 Hz50 Hz (range 45–55 Hz)
Overcurrent protectionThree-stageThree-stageThree-stagethree-stage
Discrete inputsAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 UnomAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 UnomAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom6, 220 V
Command output relays1 changeover, 4 normally open; fault relay changeover1 changeover, 4 normally open; fault relay changeover1 changeover, 4 normally open; fault relay changeover1 changeover + 4 normally open
Dimensions125х180х230 mm125х180х230 mm125х180х230 mm125x180x230 mm

European equivalents

PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which circuits is the РЗЛ-01.03 intended for?

Outgoing cable and overhead lines of 6-35 kV, incoming and section breakers, and as backup protection for transformers.

How do РЗЛ-01.03-Д2 and РЗЛ-01.03-Д3 differ?

Д2 is for an incoming 35-6 kV breaker and has two extra discrete inputs, Д3 is for a section breaker and has three extra.

What settings does the overcurrent protection have?

Three stages, each with a current setting of 0.1–25 In and a time delay of 0–32 s.