РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks

The РЗЛ-01.02К1 protects 6-35 kV cable and overhead lines with non-directional earth fault protection and a power supply from the current circuits. It has three-stage overcurrent protection, auto-reclosing, six discrete inputs, five programmable outputs, and RS485 and RS232 interfaces.

Rated frequency
50 Hz
Frequency range
45–55 Hz
Rated input current
1 A or 5 A
Operating voltage
90–250 V AC/DC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РЗЛ-01.02К1 is a member of the РЗЛ-01 microprocessor relay series for 6/35 kV distribution networks. It performs relay protection, automation, control and signalling for outgoing cable and overhead lines, protects incoming and section breakers and can act as backup protection for transformers. This version has non-directional earth fault protection and a power supply unit fed from the current circuits.

It is used as primary or backup protection in switchgear, relay panels and control cabinets at power stations, substations, network companies and industrial plants. Rated input current is 1 A or 5 A, the operating voltage is 90–250 V AC/DC and the frequency is 45–55 Hz. The relay can be fed from the current circuits, and the current circuit draws up to 1 mW per phase at rated current.

Overcurrent protection has three stages with current settings of 0.1–25 In in steps of 0.02 In and independent time delays of 0–32 s in steps of 0.05 s. With the acceleration flag active, the time can be set from 0 to 5 s in steps of 0.1 s. The re-ready time of the auto-reclosing stages is 5–600 s, and auto-reclosing can be blocked by software or by a discrete input.

The relay has six discrete inputs, five programmable output relays (one changeover and four normally open) and a fault relay. Interfaces are RS485 and RS232 with Modbus RTU. Dimensions are 125x180x230 mm.

Technical specifications

Rated frequency50 Hz
Frequency range45–55 Hz
Rated input current1 A or 5 A
Operating voltage90–250 V AC/DC
Power consumption, max5 VA + 0.4 VA per energised discrete output
Short supply voltage loss (at Unom = 220 V)500 ms
Self-test time after power-up250 ms
Overcurrent protectionThree-stage
Current setting range for each stage0.1 – 25 In in steps of 0.02 In
Time delay setting range for each stage0 – 32 s in steps of 0.05 s
Current measurement accuracy, max3 %
Overcurrent reset ratio0.95
Auto-reclosing re-ready time range, stages 1 and 25 – 600 s in steps of 0.1 s
Discrete inputsAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom
Command output relays1 changeover, 4 normally open; fault relay changeover
AC switching capacity220 V, 5 A, 1000 VA (cosφ ≥ 0.6)
InterfacesRS485, RS232
ProtocolModbus RTU
Dimensions125х180х230 mm

Part numbers

Show all part numbers (1)

РЗЛ-01.02К1

How it compares with similar models

ParameterРЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networksРЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networksРЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networksРЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks
Rated frequency50 Hz50 Hz50 Hz50 Hz (range 45–55 Hz)
Overcurrent protectionThree-stageThree-stageThree-stagethree-stage
Discrete inputsAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 UnomAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 UnomAC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom6, 220 V
Command output relays1 changeover, 4 normally open; fault relay changeover1 changeover, 4 normally open; fault relay changeover1 changeover, 4 normally open; fault relay changeover1 changeover + 4 normally open
Dimensions125х180х230 mm125х180х230 mm125х180х230 mm125x180x230 mm

European equivalents

PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What supply voltage and input currents does the РЗЛ-01.02К1 have?

The operating voltage is 90–250 V AC/DC and the rated input current is 1 A or 5 A.

How many inputs and outputs are there?

Six discrete inputs and five programmable output relays, plus a fault relay.

Where is the РЗЛ-01.02К1 used?

As primary or backup protection in switchgear, relay panels and control cabinets for 6-35 kV lines and for incoming and section breakers.