РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks
The РЗЛ-01.02К1 protects 6-35 kV cable and overhead lines with non-directional earth fault protection and a power supply from the current circuits. It has three-stage overcurrent protection, auto-reclosing, six discrete inputs, five programmable outputs, and RS485 and RS232 interfaces.
- Rated frequency
- 50 Hz
- Frequency range
- 45–55 Hz
- Rated input current
- 1 A or 5 A
- Operating voltage
- 90–250 V AC/DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-01.02К1 is a member of the РЗЛ-01 microprocessor relay series for 6/35 kV distribution networks. It performs relay protection, automation, control and signalling for outgoing cable and overhead lines, protects incoming and section breakers and can act as backup protection for transformers. This version has non-directional earth fault protection and a power supply unit fed from the current circuits.
It is used as primary or backup protection in switchgear, relay panels and control cabinets at power stations, substations, network companies and industrial plants. Rated input current is 1 A or 5 A, the operating voltage is 90–250 V AC/DC and the frequency is 45–55 Hz. The relay can be fed from the current circuits, and the current circuit draws up to 1 mW per phase at rated current.
Overcurrent protection has three stages with current settings of 0.1–25 In in steps of 0.02 In and independent time delays of 0–32 s in steps of 0.05 s. With the acceleration flag active, the time can be set from 0 to 5 s in steps of 0.1 s. The re-ready time of the auto-reclosing stages is 5–600 s, and auto-reclosing can be blocked by software or by a discrete input.
The relay has six discrete inputs, five programmable output relays (one changeover and four normally open) and a fault relay. Interfaces are RS485 and RS232 with Modbus RTU. Dimensions are 125x180x230 mm.
Technical specifications
| Rated frequency | 50 Hz |
|---|---|
| Frequency range | 45–55 Hz |
| Rated input current | 1 A or 5 A |
| Operating voltage | 90–250 V AC/DC |
| Power consumption, max | 5 VA + 0.4 VA per energised discrete output |
| Short supply voltage loss (at Unom = 220 V) | 500 ms |
| Self-test time after power-up | 250 ms |
| Overcurrent protection | Three-stage |
| Current setting range for each stage | 0.1 – 25 In in steps of 0.02 In |
| Time delay setting range for each stage | 0 – 32 s in steps of 0.05 s |
| Current measurement accuracy, max | 3 % |
| Overcurrent reset ratio | 0.95 |
| Auto-reclosing re-ready time range, stages 1 and 2 | 5 – 600 s in steps of 0.1 s |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover |
| AC switching capacity | 220 V, 5 A, 1000 VA (cosφ ≥ 0.6) |
| Interfaces | RS485, RS232 |
| Protocol | Modbus RTU |
| Dimensions | 125х180х230 mm |
Part numbers
Show all part numbers (1)
РЗЛ-01.02К1
How it compares with similar models
| Parameter | РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks | РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks | РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks | РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks |
|---|---|---|---|---|
| Rated frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz (range 45–55 Hz) |
| Overcurrent protection | Three-stage | Three-stage | Three-stage | three-stage |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | 6, 220 V |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover + 4 normally open |
| Dimensions | 125х180х230 mm | 125х180х230 mm | 125х180х230 mm | 125x180x230 mm |
European equivalents
PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What supply voltage and input currents does the РЗЛ-01.02К1 have?
The operating voltage is 90–250 V AC/DC and the rated input current is 1 A or 5 A.
How many inputs and outputs are there?
Six discrete inputs and five programmable output relays, plus a fault relay.
Where is the РЗЛ-01.02К1 used?
As primary or backup protection in switchgear, relay panels and control cabinets for 6-35 kV lines and for incoming and section breakers.
Similar equipment from other manufacturers