РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks
The РЗЛ-01.02 carries out protection, automation, control and signalling for 6-35 kV cable and overhead lines, with non-directional earth fault protection and a power supply from the current circuits. Versions РЗЛ-01.02-Д2 and РЗЛ-01.02-Д3 add extra discrete inputs.
- Rated frequency
- 50 Hz
- Frequency range
- 45–55 Hz
- Input currents
- 1 A or 5 A
- Operating voltage
- 90–250 V AC/DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-01.02 is part of the РЗЛ-01 range of microprocessor protection relays for 6-35 kV distribution networks. It provides relay protection, automation, control and signalling for outgoing cable and overhead lines, for incoming and section breakers, and backup protection for transformers. This version has non-directional earth fault protection and a power supply unit fed from the current circuits.
The relay is used as primary or backup protection in switchgear, on relay panels and in control cabinets. Input currents are 1 A or 5 A, the operating voltage is 90–250 V AC/DC and the rated frequency is 50 Hz. The current-circuit supply draws up to 1 mW per phase at rated current, and the relay rides through a short loss of supply of 500 ms at Unom = 220 V.
The three-stage overcurrent protection has current settings of 0.1–25 In and time delays of 0–32 s, independent for every stage. Settings are made by software and can be blocked, including by any discrete input. Auto-reclosing has a re-ready time setting of 5–600 s. Current measurement accuracy is up to 3 %.
Six discrete inputs for 50 Hz AC, five programmable output relays and a fault relay are fitted. The contacts switch 220 V AC at 5 A and 1000 VA. Interfaces are RS485 and RS232 with Modbus RTU. The РЗЛ-01.02-Д2 version has two extra discrete inputs (D5, D6) and the РЗЛ-01.02-Д3 has three (D4, D5, D6). Dimensions are 125x180x230 mm.
Technical specifications
| Rated frequency | 50 Hz |
|---|---|
| Frequency range | 45–55 Hz |
| Input currents | 1 A or 5 A |
| Operating voltage | 90–250 V AC/DC |
| Power consumption, max | 5 VA + 0.4 VA per energised discrete output |
| Short supply voltage loss (at Unom = 220 V) | 500 ms |
| Self-test time after power-up | 250 ms |
| Overcurrent protection | Three-stage |
| Current setting range for each stage | 0.1 – 25 In in steps of 0.02 In |
| Time delay setting range for each stage | 0 – 32 s in steps of 0.05 s |
| Current measurement accuracy, max | 3 % |
| Overcurrent reset ratio | 0.95 |
| Auto-reclosing re-ready time range, stages 1 and 2 | 5 – 600 s in steps of 0.1 s |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover |
| AC switching capacity | 220 V, 5 A, 1000 VA (cosφ ≥ 0.6) |
| Interfaces | RS485, RS232 |
| Protocol | Modbus RTU |
| Dimensions | 125х180х230 mm |
Part numbers
Show all part numbers (3)
РЗЛ-01.02, РЗЛ-01.02-Д2, РЗЛ-01.02-Д3
How it compares with similar models
| Parameter | РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks | РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks | РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks | РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks |
|---|---|---|---|---|
| Rated frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz (range 45–55 Hz) |
| Overcurrent protection | Three-stage | Three-stage | Three-stage | three-stage |
| Discrete inputs | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | 6, 220 V |
| Command output relays | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover + 4 normally open |
| Dimensions | 125х180х230 mm | 125х180х230 mm | 125х180х230 mm | 125x180x230 mm |
European equivalents
PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which versions of the РЗЛ-01.02 exist?
The base РЗЛ-01.02, РЗЛ-01.02-Д2 with two extra discrete inputs and РЗЛ-01.02-Д3 with three.
What input currents and supply voltage are allowed?
Input currents of 1 A or 5 A and an operating voltage of 90–250 V AC/DC.
How is the overcurrent protection set?
Three stages with current settings of 0.1–25 In and time delays of 0–32 s, set by software and can be blocked.
Similar equipment from other manufacturers