РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks
РЗЛ-01.01 is a microprocessor relay for protection, automation, control and signalling in 6-35 kV distribution networks. It has three overcurrent stages, two auto-reclose stages, 6 discrete inputs, 5 command relays and Modbus RTU.
- Rated input currents
- 5 A or 1 A
- Rated frequency
- 50 Hz (range 45–55 Hz)
- Auxiliary supply
- 90-250 V DC or AC
- Power consumption
- not more than 5 VA + 0,4 VA per energised discrete output
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-01.01 belongs to the РЗЛ-01 series of microprocessor protection devices for 6-35 kV distribution networks. It covers protection, automation, control and signalling for outgoing cable and overhead lines, incoming and sectionalising breakers, and serves as backup protection for transformers. It can act as main or backup protection in switchgear cells, relay panels and control cabinets.
Overcurrent protection has three stages. Each stage takes a current setting of 0,1 – 25 In in steps of 0,02 In and a time delay of 0 – 32 s in steps of 0,05 s; the delays of all stages are independent. Current measurement accuracy is not more than 3% and the reset ratio is 0,95. Settings are entered in software, and any stage can be blocked, including from any discrete input.
Auto-reclosing has two stages. The operating time of the stages is 0 - 600 s in steps of 0,1 s, the re-ready time is 5 - 600 s in steps of 0,1 s. Stages are blocked either in software or through a discrete input.
There are 6 optically isolated discrete inputs for a control voltage of 220 V DC or 220 V AC at 50 Hz. The programmable command relays number five, one changeover and four normally open, plus a separate changeover fault relay. Contacts switch 220 V AC at 5 A, 1000 VA (cosφ ≥ 0,6), with a continuous current of 8 A.
The auxiliary supply is 90-250 V DC or AC and the rated input current is 5 A or 1 A. After power-up the self-test takes 250 ms, and a short supply loss of up to 500 ms is tolerated at Uном = 220 V. Communication runs over RS485 or RS232 with the Modbus RTU protocol, and configuration software is available. Dimensions are 125x180x230 mm.
Technical specifications
| Rated input currents | 5 A or 1 A |
|---|---|
| Rated frequency | 50 Hz (range 45–55 Hz) |
| Auxiliary supply | 90-250 V DC or AC |
| Power consumption | not more than 5 VA + 0,4 VA per energised discrete output |
| Overcurrent protection | three-stage |
| Current settings (each stage) | 0,1 – 25 In, step 0,02 In |
| Stage time delay | 0 – 32 s, step 0,05 s |
| Current measurement accuracy | not more than 3% |
| Reset ratio | 0,95 |
| Auto-reclose stage time | 0 - 600 s, step 0,1 s |
| Auto-reclose ready time | 5 - 600 s, step 0,1 s |
| Discrete inputs | 6, 220 V |
| Command output relays | 1 changeover + 4 normally open |
| Fault relay | 1 changeover |
| Contact rating, AC | 220 V, 5 A, 1000 VA (cosφ ≥ 0,6) |
| Continuous contact current | 8 A |
| Interfaces and protocol | RS485, RS232; Modbus RTU |
| Dimensions | 125x180x230 mm |
Part numbers
Show all part numbers (1)
РЗЛ-01.01
How it compares with similar models
| Parameter | РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks | РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks | РЗЛ-01.02К1 microprocessor protection and automation relay for 6/35 kV distribution networks | РЗЛ-01.02 microprocessor protection and automation relay for 6/35 kV networks |
|---|---|---|---|---|
| Rated frequency | 50 Hz (range 45–55 Hz) | 50 Hz | 50 Hz | 50 Hz |
| Overcurrent protection | three-stage | Three-stage | Three-stage | Three-stage |
| Discrete inputs | 6, 220 V | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom | AC 50 Hz, Unom 220 V, U1 above 0.8 Unom, U0 below 0.45 Unom |
| Command output relays | 1 changeover + 4 normally open | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover | 1 changeover, 4 normally open; fault relay changeover |
| Dimensions | 125x180x230 mm | 125х180х230 mm | 125х180х230 mm | 125х180х230 mm |
European equivalents
PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection), IRV MV feeder protection terminal (V platform), BELplus OZE
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-01.01 microprocessor protection and automation relay for 6-35 kV networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many overcurrent stages does the РЗЛ-01.01 have and what are the settings?
There are three stages. The current setting of each stage is 0,1 – 25 In in steps of 0,02 In, and the time delay is 0 – 32 s in steps of 0,05 s.
Which communication interfaces and protocol are fitted?
The device has RS485 and RS232 interfaces and uses the Modbus RTU protocol.
What supply and rated currents does the РЗЛ-01.01 need?
The auxiliary supply is 90-250 V DC or AC, and the rated input current is 5 A or 1 A at 50 Hz.
Similar equipment from other manufacturers