РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers

The РЗЛ-05.ТН handles protection, automation, control, recording and signalling for a 110-35-10(6) kV voltage transformer in switchgear. It has 7 analogue and 12 discrete inputs, 13 relays, two RS-485 ports and USB.

Application
protection and automation of a 110-35-10(6) kV voltage transformer
Auxiliary supply voltage
220 V (110 V)
Analogue inputs
7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1)
Temperature sensor input
1

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РЗЛ-05.ТН is built for protection, automation, control, recording and signalling of a 110-35-10(6) kV voltage transformer in switchgear at power and industrial sites. It is installed in distribution points, transformer substations and stations with a DC operating supply. Typical cubicles are КСО, КРУ and КРУН.

Measuring inputs are 7 analogue channels (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) and 1 temperature sensor input. There are 12 discrete inputs, 3 of them dry-contact. Outputs are 13 relays: 4 with a changeover group, the bistable К7 and the device integrity relay KWD. Three inputs take fibre-optic sensors for integrated arc protection.

Communication uses two isolated RS-485 ports and USB, with the MODBUS RTU protocol. The unit includes a digital oscillograph (32 records of 65 seconds), an event log of 254 records and freely programmable logic (СПЛ). The OLED display is accompanied by 20 LEDs, of which 15 are configurable. SCADA integration is supported.

Two versions exist. РЗЛ-05.ТН01 has no fibre-optic sensor inputs and РЗЛ-05.ТН03 has three, and both run from a 220 V (110 V) auxiliary supply. Dimensions are 205 × 240 × 182 mm. Mounting is in a panel or cabinet, flush or protruding with special fasteners. Operating temperature is −40 to +60 °C.

Free programmable logic is written with external circuits disconnected. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.

Technical specifications

Applicationprotection and automation of a 110-35-10(6) kV voltage transformer
Auxiliary supply voltage220 V (110 V)
Analogue inputs7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1)
Temperature sensor input1
Discrete inputs12 (3 dry-contact)
Output relays13 (4 with changeover group, 1 bistable К7, 1 KWD)
Fibre-optic sensor inputs3 (ТН03 version)
Communication ports2 isolated RS-485; USB
ProtocolMODBUS RTU
DisplayOLED; 20 LEDs, 15 configurable
Event log254 records
Oscillograms32 records of 65 s
Dimensions205 × 240 × 182 mm
Operating temperature−40…+60 °C

Part numbers

Show all part numbers (2)

РЗЛ-05.ТН01 220В (110 В), РЗЛ-05.ТН03 220В (110 В)

How it compares with similar models

ParameterРЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformersРЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versionsРЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versionsРЗЛ-05.Т2 and РЗЛ-05.Т3 protection units for 35–110 kV transformers and autotransformers
Applicationprotection and automation of a 110-35-10(6) kV voltage transformerprotection, automation and breaker control of 6-154 kV connectionsprotection, automation and breaker control of 6-154 kV connectionsmain protection of two- and three-winding transformers and autotransformers with high voltage 35–110 kV
Analogue inputs7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1)5 (IA, IB, IC, 3I0, 3U0)8РЗЛ-05.Т2 – 11; РЗЛ-05.Т3 – 14
Discrete inputs12 (3 dry-contact)12 (3 dry-contact)12 (3 dry-contact)РЗЛ-05.Т2 – 12; РЗЛ-05.Т3 – 20
Output relays13 (4 with changeover group, 1 bistable К7, 1 KWD)1313РЗЛ-05.Т2 – 13; РЗЛ-05.Т3 – 17
Fibre-optic sensor inputs3 (ТН03 version)3 (Ф3, Ф4, Ф6)3 (В3, В4, В6, В13, В14, В16)3 (-Д version)

European equivalents

SPR10, BELplus OZE, IDF / IDV / IDX transformer differential protection terminal, PROTECTA DTIVA

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What inputs and outputs does the РЗЛ-05.ТН have?

It has 7 analogue inputs (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1), 12 discrete inputs, 13 relays and a temperature sensor input.

How do РЗЛ-05.ТН01 and РЗЛ-05.ТН03 differ?

The ТН01 has no fibre-optic sensor inputs. The ТН03 has 3 such inputs for arc protection. Both use a 220 V (110 V) supply.

What communication and recording functions are included?

Two isolated RS-485 ports, USB and MODBUS RTU. The event log holds 254 records and the oscillograph stores 32 records of 65 s.