РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs

The РЗЛ-05.ДЗ-Х provides distance protection, automation, signalling and breaker control for 35(110) kV lines. It has four steps, 8 analogue inputs, 20 discrete inputs, 17 relays and an own operating time of 35 ms.

Application
distance protection and automation of 35(110) kV lines
Number of steps
4
Zone Rz setting range, fault loop resistance
0.05–200 ohm
Z setting resolution
0.01 ohm

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РЗЛ-05.ДЗ-Х series are microprocessor relay protection and automation units for 35(110) kV power lines in switchgear with DC operating supply. The main function is distance protection, with automation, signalling, fault recording, diagnostics and circuit breaker control. The units work with several breaker types and issue the trip command.

Distance protection has 4 steps. The zone Rz setting covers 0.05–200 ohm of secondary fault loop resistance in 0.01 ohm increments. The zone centre coordinates (0r, 0x) adjust within 0–200 ohm, angles α and β are set from 0 to 360 degrees in steps of 1 degree, and time delay runs from 0 to 10 s in 0.01 s steps. The lower accurate-operation current limit is 1 A and the upper is 150 A. Minimum operating voltage is 10 V and own operating time is 35 ms.

Inputs and outputs: 8 analogue inputs (IA, IB, IC, 3I0, UA, UB, UC, 3U0) plus an input for 1 temperature sensor, 20 discrete inputs (3 of them dry-contact), and 17 relays. Of the relays, 4 have a changeover group, one is the bistable К7 and one is the device integrity relay KWD. Three inputs take fibre-optic arc protection sensors on a 5 m cable.

Communication uses isolated RS-485 ports, Ethernet (TX) and USB, with MODBUS RTU and MODBUS TCP. In versions РЗЛ-05.ДЗ-11…14 Ethernet replaces RS-485. The display is a non-freezing OLED, with 20 LEDs of which 15 are configurable. Other functions are a digital oscillograph, an event log, programmable logic (ВПЛ) and SCADA integration.

Ten versions differ in supply from current circuits, de-shunting, fibre-optic inputs and Ethernet: РЗЛ-05.ДЗ-1…6 and ДЗ-11…14, all with a 220 V (110 V) auxiliary supply. Dimensions are 265 × 240 × 195 mm and operating temperature is −40 to +60 °C. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.

Technical specifications

Applicationdistance protection and automation of 35(110) kV lines
Number of steps4
Zone Rz setting range, fault loop resistance0.05–200 ohm
Z setting resolution0.01 ohm
Zone centre coordinates (0r, 0x)0–200 ohm
Angle α and β setting range0–360 degrees (resolution 1)
Time delay setting range0–10 s (step 0.01 s)
Accurate-operation current1 A to 150 A
Minimum operating voltage10 V
Own operating time35 ms
Analogue inputs8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) + 1 temperature sensor
Discrete inputs20 (3 dry-contact)
Output relays17 (4 with changeover group, 1 bistable К7, 1 integrity relay KWD)
Fibre-optic sensor inputs3, 5 m cable (fibre-optic versions)
InterfacesRS-485 or Ethernet (TX) depending on version; USB
ProtocolsMODBUS RTU, MODBUS TCP
DisplayOLED; 20 LEDs, 15 configurable
Dimensions265 × 240 × 195 mm
Operating temperature−40…+60 °C

Part numbers

Show all part numbers (10)

РЗЛ-05.ДЗ-1, РЗЛ-05.ДЗ-2, РЗЛ-05.ДЗ-3, РЗЛ-05.ДЗ-4, РЗЛ-05.ДЗ-5, РЗЛ-05.ДЗ-6, РЗЛ-05.ДЗ-11, РЗЛ-05.ДЗ-12, РЗЛ-05.ДЗ-13, РЗЛ-05.ДЗ-14

How it compares with similar models

ParameterРЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputsРЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformersРЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versionsРЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions
Applicationdistance protection and automation of 35(110) kV linesprotection and automation of a 110-35-10(6) kV voltage transformerprotection, automation and breaker control of 6-154 kV connectionsprotection, automation and breaker control of 6-154 kV connections
Analogue inputs8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) + 1 temperature sensor7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1)88
Discrete inputs20 (3 dry-contact)12 (3 dry-contact)12 (3 dry-contact)20
Output relays17 (4 with changeover group, 1 bistable К7, 1 integrity relay KWD)13 (4 with changeover group, 1 bistable К7, 1 KWD)1317
Fibre-optic sensor inputs3, 5 m cable (fibre-optic versions)3 (ТН03 version)3 (В3, В4, В6, В13, В14, В16)3 (А3, А4, А6, А13, А14)
InterfacesRS-485 or Ethernet (TX) depending on version; USB—RS-485, Ethernet, USBRS-485, Ethernet, USB

European equivalents

DLF / DLX line differential protection terminal, PROTECTA DTIVA, DZ9, BELplus OZE

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What are the distance protection parameters of the РЗЛ-05.ДЗ-Х?

There are 4 steps, a zone Rz setting of 0.05–200 ohm in 0.01 ohm increments, a time delay of 0–10 s and an own operating time of 35 ms.

How do versions ДЗ-1…6 and ДЗ-11…14 differ?

They differ in supply from current circuits, de-shunting and three fibre-optic inputs. In ДЗ-11…14 Ethernet replaces RS-485.

Is arc protection supported?

Yes, through 3 fibre-optic sensor inputs with a 5 m cable. They are present in versions ДЗ-3, ДЗ-4, ДЗ-6, ДЗ-13 and ДЗ-14.