РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs
The РЗЛ-05.ДЗ-Х provides distance protection, automation, signalling and breaker control for 35(110) kV lines. It has four steps, 8 analogue inputs, 20 discrete inputs, 17 relays and an own operating time of 35 ms.
- Application
- distance protection and automation of 35(110) kV lines
- Number of steps
- 4
- Zone Rz setting range, fault loop resistance
- 0.05–200 ohm
- Z setting resolution
- 0.01 ohm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.ДЗ-Х series are microprocessor relay protection and automation units for 35(110) kV power lines in switchgear with DC operating supply. The main function is distance protection, with automation, signalling, fault recording, diagnostics and circuit breaker control. The units work with several breaker types and issue the trip command.
Distance protection has 4 steps. The zone Rz setting covers 0.05–200 ohm of secondary fault loop resistance in 0.01 ohm increments. The zone centre coordinates (0r, 0x) adjust within 0–200 ohm, angles α and β are set from 0 to 360 degrees in steps of 1 degree, and time delay runs from 0 to 10 s in 0.01 s steps. The lower accurate-operation current limit is 1 A and the upper is 150 A. Minimum operating voltage is 10 V and own operating time is 35 ms.
Inputs and outputs: 8 analogue inputs (IA, IB, IC, 3I0, UA, UB, UC, 3U0) plus an input for 1 temperature sensor, 20 discrete inputs (3 of them dry-contact), and 17 relays. Of the relays, 4 have a changeover group, one is the bistable К7 and one is the device integrity relay KWD. Three inputs take fibre-optic arc protection sensors on a 5 m cable.
Communication uses isolated RS-485 ports, Ethernet (TX) and USB, with MODBUS RTU and MODBUS TCP. In versions РЗЛ-05.ДЗ-11…14 Ethernet replaces RS-485. The display is a non-freezing OLED, with 20 LEDs of which 15 are configurable. Other functions are a digital oscillograph, an event log, programmable logic (ВПЛ) and SCADA integration.
Ten versions differ in supply from current circuits, de-shunting, fibre-optic inputs and Ethernet: РЗЛ-05.ДЗ-1…6 and ДЗ-11…14, all with a 220 V (110 V) auxiliary supply. Dimensions are 265 × 240 × 195 mm and operating temperature is −40 to +60 °C. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.
Technical specifications
| Application | distance protection and automation of 35(110) kV lines |
|---|---|
| Number of steps | 4 |
| Zone Rz setting range, fault loop resistance | 0.05–200 ohm |
| Z setting resolution | 0.01 ohm |
| Zone centre coordinates (0r, 0x) | 0–200 ohm |
| Angle α and β setting range | 0–360 degrees (resolution 1) |
| Time delay setting range | 0–10 s (step 0.01 s) |
| Accurate-operation current | 1 A to 150 A |
| Minimum operating voltage | 10 V |
| Own operating time | 35 ms |
| Analogue inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) + 1 temperature sensor |
| Discrete inputs | 20 (3 dry-contact) |
| Output relays | 17 (4 with changeover group, 1 bistable К7, 1 integrity relay KWD) |
| Fibre-optic sensor inputs | 3, 5 m cable (fibre-optic versions) |
| Interfaces | RS-485 or Ethernet (TX) depending on version; USB |
| Protocols | MODBUS RTU, MODBUS TCP |
| Display | OLED; 20 LEDs, 15 configurable |
| Dimensions | 265 × 240 × 195 mm |
| Operating temperature | −40…+60 °C |
Part numbers
Show all part numbers (10)
РЗЛ-05.ДЗ-1, РЗЛ-05.ДЗ-2, РЗЛ-05.ДЗ-3, РЗЛ-05.ДЗ-4, РЗЛ-05.ДЗ-5, РЗЛ-05.ДЗ-6, РЗЛ-05.ДЗ-11, РЗЛ-05.ДЗ-12, РЗЛ-05.ДЗ-13, РЗЛ-05.ДЗ-14
How it compares with similar models
| Parameter | РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs | РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers | РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions | РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions |
|---|---|---|---|---|
| Application | distance protection and automation of 35(110) kV lines | protection and automation of a 110-35-10(6) kV voltage transformer | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections |
| Analogue inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) + 1 temperature sensor | 7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) | 8 | 8 |
| Discrete inputs | 20 (3 dry-contact) | 12 (3 dry-contact) | 12 (3 dry-contact) | 20 |
| Output relays | 17 (4 with changeover group, 1 bistable К7, 1 integrity relay KWD) | 13 (4 with changeover group, 1 bistable К7, 1 KWD) | 13 | 17 |
| Fibre-optic sensor inputs | 3, 5 m cable (fibre-optic versions) | 3 (ТН03 version) | 3 (В3, В4, В6, В13, В14, В16) | 3 (А3, А4, А6, А13, А14) |
| Interfaces | RS-485 or Ethernet (TX) depending on version; USB | — | RS-485, Ethernet, USB | RS-485, Ethernet, USB |
European equivalents
DLF / DLX line differential protection terminal, PROTECTA DTIVA, DZ9, BELplus OZE
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.ДЗ-Х distance protection for 35(110) kV lines, 4 steps, 20 discrete inputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What are the distance protection parameters of the РЗЛ-05.ДЗ-Х?
There are 4 steps, a zone Rz setting of 0.05–200 ohm in 0.01 ohm increments, a time delay of 0–10 s and an own operating time of 35 ms.
How do versions ДЗ-1…6 and ДЗ-11…14 differ?
They differ in supply from current circuits, de-shunting and three fibre-optic inputs. In ДЗ-11…14 Ethernet replaces RS-485.
Is arc protection supported?
Yes, through 3 fibre-optic sensor inputs with a 5 m cable. They are present in versions ДЗ-3, ДЗ-4, ДЗ-6, ДЗ-13 and ДЗ-14.