РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions
The РЗЛ-05.АХ, with an extended hardware and logic configuration, provides protection, automation, signalling and breaker control for 6-154 kV connections. It has 8 analogue inputs, 20 discrete inputs, 17 relays and 10 versions.
- Application
- protection, automation and breaker control of 6-154 kV connections
- Auxiliary supply voltage
- 220 V (110 V)
- Analogue inputs
- 8
- Discrete inputs
- 20
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.АХ series are microprocessor protection and automation units with an extended hardware and logic configuration, made for the connections of 6-154 kV switchgear. They cover protection, automation, signalling, fault recording, diagnostics and breaker control. Typical uses are overhead and cable lines, incomer and section breakers, and backup protection of transformers.
Measuring inputs are 8 analogue channels and 1 temperature sensor input. The unit has 20 discrete inputs and 17 output relays. Other functions are a digital oscillograph, an event log, freely programmable logic (СПЛ), SCADA integration and integrated arc protection with fibre-optic sensors. Interfaces are RS-485, Ethernet and USB, with MODBUS RTU and MODBUS TCP.
The ten versions РЗЛ-05.А1…А6 and А11…А14 all use a 220 V (110 V) auxiliary supply. Backup supply from CT circuits is in А2, А4, А5, А6, А12 and А14. De-shunting of breaker current solenoids is in А5 and А6. Three fibre-optic sensor inputs are in А3, А4, А6, А13 and А14. The Ethernet port is in versions А11…А14.
The РЗЛ-05.А5 measures 265 × 240 × 195 mm and the РЗЛ-05.А6 measures 280 × 260 × 195 mm. Mounting is in a panel or cabinet. Operating temperature is −40 to +60 °C.
Free programmable logic is written with external circuits disconnected. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.
Technical specifications
| Application | protection, automation and breaker control of 6-154 kV connections |
|---|---|
| Auxiliary supply voltage | 220 V (110 V) |
| Analogue inputs | 8 |
| Discrete inputs | 20 |
| Output relays | 17 |
| Backup supply from CT circuits | А2, А4, А5, А6, А12, А14 |
| De-shunting of current solenoids | А5, А6 |
| Fibre-optic sensor inputs | 3 (А3, А4, А6, А13, А14) |
| Ethernet port | А11…А14 |
| Interfaces | RS-485, Ethernet, USB |
| Protocols | MODBUS RTU, MODBUS TCP |
| РЗЛ-05.А5 dimensions | 265 × 240 × 195 mm |
| РЗЛ-05.А6 dimensions | 280 × 260 × 195 mm |
| Operating temperature | −40…+60 °C |
Part numbers
Show all part numbers (10)
РЗЛ-05.А1, РЗЛ-05.А2, РЗЛ-05.А3, РЗЛ-05.А4, РЗЛ-05.А5, РЗЛ-05.А6, РЗЛ-05.А11, РЗЛ-05.А12, РЗЛ-05.А13, РЗЛ-05.А14
How it compares with similar models
| Parameter | РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions | РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions | РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions | РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers |
|---|---|---|---|---|
| Application | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections | protection and automation of a 110-35-10(6) kV voltage transformer |
| Analogue inputs | 8 | 8 | 5 (IA, IB, IC, 3I0, 3U0) | 7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) |
| Discrete inputs | 20 | 12 (3 dry-contact) | 12 (3 dry-contact) | 12 (3 dry-contact) |
| Output relays | 17 | 13 | 13 | 13 (4 with changeover group, 1 bistable К7, 1 KWD) |
| Backup supply from CT circuits | А2, А4, А5, А6, А12, А14 | В2, В4, В5, В6, В12, В14, В15, В16 | Ф2, Ф4, Ф5, Ф6 | — |
| De-shunting of current solenoids | А5, А6 | В5, В6, В15, В16 | Ф5, Ф6 | — |
European equivalents
BELplus OZE, IDF / IDV / IDX transformer differential protection terminal, PROTECTA DTIVA, DZ9
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the РЗЛ-05.АХ differ from the РЗЛ-05.ВХ?
The РЗЛ-05.АХ has an extended hardware and logic configuration, with 20 discrete inputs and 17 relays against 12 and 13 on the ВХ.
Which versions have backup supply from CT circuits?
А2, А4, А5, А6, А12 and А14. De-shunting is in А5 and А6, and fibre-optic inputs are in А3, А4, А6, А13 and А14.
Which interfaces and protocols are supported?
RS-485, Ethernet (in versions А11…А14) and USB, with MODBUS RTU and MODBUS TCP.