РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions

The РЗЛ-05.ВХ provides protection, automation, signalling and breaker control for 6-154 kV connections. It has 8 analogue inputs, 12 discrete inputs and 13 relays, in 12 versions with CT-circuit supply, de-shunting, fibre-optic inputs and Ethernet.

Application
protection, automation and breaker control of 6-154 kV connections
Auxiliary supply voltage
220 V (110 V)
Analogue inputs
8
Discrete inputs
12 (3 dry-contact)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РЗЛ-05.ВХ series are microprocessor protection and automation units for the connections of 6-154 kV switchgear. They cover protection, automation, signalling, fault recording, diagnostics and breaker control. Typical uses are overhead and cable lines, incomer and section breakers, and backup protection of transformers. The units work with several breaker types.

Measuring inputs are 8 analogue channels and 1 temperature sensor input. There are 12 discrete inputs, 3 of them dry-contact, and 13 output relays. Other functions are a digital oscillograph, an event log, freely programmable logic (СПЛ), SCADA integration and integrated arc protection with fibre-optic sensors. Interfaces are RS-485, Ethernet and USB, with MODBUS RTU and MODBUS TCP.

The twelve versions РЗЛ-05.В1…В6 and В11…В16 all use a 220 V (110 V) auxiliary supply. Backup supply from CT circuits is in В2, В4, В5, В6, В12, В14, В15 and В16. De-shunting of breaker current solenoids is in В5, В6, В15 and В16. Three fibre-optic sensor inputs are in В3, В4, В6, В13, В14 and В16. The Ethernet port is in versions В11…В16.

The РЗЛ-05.В5 measures 205 × 240 × 195 mm and the РЗЛ-05.В6 measures 220 × 260 × 195 mm. Mounting is in a panel or cabinet. Operating temperature is −40 to +60 °C.

Free programmable logic is written with external circuits disconnected. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.

Technical specifications

Applicationprotection, automation and breaker control of 6-154 kV connections
Auxiliary supply voltage220 V (110 V)
Analogue inputs8
Discrete inputs12 (3 dry-contact)
Output relays13
Backup supply from CT circuitsВ2, В4, В5, В6, В12, В14, В15, В16
De-shunting of current solenoidsВ5, В6, В15, В16
Fibre-optic sensor inputs3 (В3, В4, В6, В13, В14, В16)
Ethernet portВ11…В16
InterfacesRS-485, Ethernet, USB
ProtocolsMODBUS RTU, MODBUS TCP
РЗЛ-05.В5 dimensions205 × 240 × 195 mm
РЗЛ-05.В6 dimensions220 × 260 × 195 mm
Operating temperature−40…+60 °C

Part numbers

Show all part numbers (12)

РЗЛ-05.В1, РЗЛ-05.В2, РЗЛ-05.В3, РЗЛ-05.В4, РЗЛ-05.В5, РЗЛ-05.В6, РЗЛ-05.В11, РЗЛ-05.В12, РЗЛ-05.В13, РЗЛ-05.В14, РЗЛ-05.В15, РЗЛ-05.В16

How it compares with similar models

ParameterРЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versionsРЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versionsРЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versionsРЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers
Applicationprotection, automation and breaker control of 6-154 kV connectionsprotection, automation and breaker control of 6-154 kV connectionsprotection, automation and breaker control of 6-154 kV connectionsprotection and automation of a 110-35-10(6) kV voltage transformer
Analogue inputs885 (IA, IB, IC, 3I0, 3U0)7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1)
Discrete inputs12 (3 dry-contact)2012 (3 dry-contact)12 (3 dry-contact)
Output relays13171313 (4 with changeover group, 1 bistable К7, 1 KWD)
Backup supply from CT circuitsВ2, В4, В5, В6, В12, В14, В15, В16А2, А4, А5, А6, А12, А14Ф2, Ф4, Ф5, Ф6—
De-shunting of current solenoidsВ5, В6, В15, В16А5, А6Ф5, Ф6—

European equivalents

BELplus OZE, IDF / IDV / IDX transformer differential protection terminal, PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection)

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do versions РЗЛ-05.В1…В16 differ?

They differ in CT-circuit backup supply, de-shunting, three fibre-optic inputs and the Ethernet port. Versions В11…В16 have Ethernet.

What inputs and outputs does the РЗЛ-05.ВХ have?

It has 8 analogue inputs, a temperature sensor input, 12 discrete inputs (3 dry-contact) and 13 relays.

Which connections is the unit meant for?

Overhead and cable lines, incomer and section breakers, and backup protection of transformers at 6-154 kV.