РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions
The РЗЛ-05.ВХ provides protection, automation, signalling and breaker control for 6-154 kV connections. It has 8 analogue inputs, 12 discrete inputs and 13 relays, in 12 versions with CT-circuit supply, de-shunting, fibre-optic inputs and Ethernet.
- Application
- protection, automation and breaker control of 6-154 kV connections
- Auxiliary supply voltage
- 220 V (110 V)
- Analogue inputs
- 8
- Discrete inputs
- 12 (3 dry-contact)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.ВХ series are microprocessor protection and automation units for the connections of 6-154 kV switchgear. They cover protection, automation, signalling, fault recording, diagnostics and breaker control. Typical uses are overhead and cable lines, incomer and section breakers, and backup protection of transformers. The units work with several breaker types.
Measuring inputs are 8 analogue channels and 1 temperature sensor input. There are 12 discrete inputs, 3 of them dry-contact, and 13 output relays. Other functions are a digital oscillograph, an event log, freely programmable logic (СПЛ), SCADA integration and integrated arc protection with fibre-optic sensors. Interfaces are RS-485, Ethernet and USB, with MODBUS RTU and MODBUS TCP.
The twelve versions РЗЛ-05.В1…В6 and В11…В16 all use a 220 V (110 V) auxiliary supply. Backup supply from CT circuits is in В2, В4, В5, В6, В12, В14, В15 and В16. De-shunting of breaker current solenoids is in В5, В6, В15 and В16. Three fibre-optic sensor inputs are in В3, В4, В6, В13, В14 and В16. The Ethernet port is in versions В11…В16.
The РЗЛ-05.В5 measures 205 × 240 × 195 mm and the РЗЛ-05.В6 measures 220 × 260 × 195 mm. Mounting is in a panel or cabinet. Operating temperature is −40 to +60 °C.
Free programmable logic is written with external circuits disconnected. Before settings or parameters are changed, the connection is taken out and left for at least two minutes. After storage without power, the unit is kept energised for at least 1 hour to charge its internal battery.
Technical specifications
| Application | protection, automation and breaker control of 6-154 kV connections |
|---|---|
| Auxiliary supply voltage | 220 V (110 V) |
| Analogue inputs | 8 |
| Discrete inputs | 12 (3 dry-contact) |
| Output relays | 13 |
| Backup supply from CT circuits | В2, В4, В5, В6, В12, В14, В15, В16 |
| De-shunting of current solenoids | В5, В6, В15, В16 |
| Fibre-optic sensor inputs | 3 (В3, В4, В6, В13, В14, В16) |
| Ethernet port | В11…В16 |
| Interfaces | RS-485, Ethernet, USB |
| Protocols | MODBUS RTU, MODBUS TCP |
| РЗЛ-05.В5 dimensions | 205 × 240 × 195 mm |
| РЗЛ-05.В6 dimensions | 220 × 260 × 195 mm |
| Operating temperature | −40…+60 °C |
Part numbers
Show all part numbers (12)
РЗЛ-05.В1, РЗЛ-05.В2, РЗЛ-05.В3, РЗЛ-05.В4, РЗЛ-05.В5, РЗЛ-05.В6, РЗЛ-05.В11, РЗЛ-05.В12, РЗЛ-05.В13, РЗЛ-05.В14, РЗЛ-05.В15, РЗЛ-05.В16
How it compares with similar models
| Parameter | РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions | РЗЛ-05.АХ protection unit with extended configuration for 6-154 kV connections, 10 versions | РЗЛ-05.ФХ protection, automation and monitoring unit for 6-154 kV connections, 6 versions | РЗЛ-05.ТН protection and automation unit for 110-35-10(6) kV voltage transformers |
|---|---|---|---|---|
| Application | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections | protection, automation and breaker control of 6-154 kV connections | protection and automation of a 110-35-10(6) kV voltage transformer |
| Analogue inputs | 8 | 8 | 5 (IA, IB, IC, 3I0, 3U0) | 7 (UA, UB, UC, 3U0, UТСН1, UТСН2, UТН1) |
| Discrete inputs | 12 (3 dry-contact) | 20 | 12 (3 dry-contact) | 12 (3 dry-contact) |
| Output relays | 13 | 17 | 13 | 13 (4 with changeover group, 1 bistable К7, 1 KWD) |
| Backup supply from CT circuits | В2, В4, В5, В6, В12, В14, В15, В16 | А2, А4, А5, А6, А12, А14 | Ф2, Ф4, Ф5, Ф6 | — |
| De-shunting of current solenoids | В5, В6, В15, В16 | А5, А6 | Ф5, Ф6 | — |
European equivalents
BELplus OZE, IDF / IDV / IDX transformer differential protection terminal, PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection)
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.ВХ protection, automation and monitoring unit for 6-154 kV connections, 12 versions. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do versions РЗЛ-05.В1…В16 differ?
They differ in CT-circuit backup supply, de-shunting, three fibre-optic inputs and the Ethernet port. Versions В11…В16 have Ethernet.
What inputs and outputs does the РЗЛ-05.ВХ have?
It has 8 analogue inputs, a temperature sensor input, 12 discrete inputs (3 dry-contact) and 13 relays.
Which connections is the unit meant for?
Overhead and cable lines, incomer and section breakers, and backup protection of transformers at 6-154 kV.
Similar equipment from other manufacturers