IDF / IDV / IDX transformer differential protection terminal

IDF, IDV and IDX protect, control and measure a power transformer bay of any voltage class, including phase-shifting transformers. The terminal has up to 4 three-phase groups of current inputs, differential protection with restraint, harmonic blocking and an unrestrained differential element, and supports IEC 61850 Ed.2.

Object
two- and three-winding transformers and autotransformers, reactors, SVC, generators, motors
Differential protection
with restraint and harmonic blocking + unrestrained differential element
Current inputs
up to 4 three-phase groups (one-and-a-half breaker scheme, ring)
Additional
restricted earth fault protection (REF), overexcitation protection

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The protected object can be two- and three-winding transformers, autotransformers, reactors, SVC, generators and motors. The four groups of current inputs are connected in one-and-a-half breaker and ring schemes, where the transformer is fed through several breakers. Restraint and harmonic blocking make the protection immune to magnetising inrush currents, and the unrestrained differential element quickly trips large internal faults. In addition there are restricted earth fault protection REF and overexcitation protection. The relay is modular and has an IEC 61850 certificate for editions 1 and 2.

Technical specifications

Objecttwo- and three-winding transformers and autotransformers, reactors, SVC, generators, motors
Differential protectionwith restraint and harmonic blocking + unrestrained differential element
Current inputsup to 4 three-phase groups (one-and-a-half breaker scheme, ring)
Additionalrestricted earth fault protection (REF), overexcitation protection
ProtocolIEC 61850 Ed.2

Request a price and lead time

IDF / IDV / IDX transformer differential protection terminal. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8536 49 00 90
HS, 6 digits8536 49
CN (EU)8536 49 00
HTSUS (USA)8536 49 00 80
China customs tariff8536 49 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which objects does the IDF / IDV / IDX terminal protect?

Two- and three-winding transformers and autotransformers of any voltage class, including phase-shifting ones, as well as reactors, SVC, generators and motors.

How many groups of current inputs does the terminal have?

Up to 4 three-phase groups. This is enough for one-and-a-half breaker and ring schemes.

Which additional protections are built in?

Restricted earth fault protection REF and overexcitation protection. Communication with the SCADA is over IEC 61850 Ed.2.