RZL-400 protection, automation and control terminal for 6-35 kV substations and feeders
The RZL-400 provides relay protection, automation, signalling and breaker control on 6-35 kV feeders. It has 8 analog inputs, 9 discrete inputs and 8 relays, comes in six versions, and talks Modbus RTU/TCP and IEC 60870-5-101/103/104.
- Type
- Protection, automation and control device for substations and feeders
- Voltage class
- 6-35 kV
- Analog inputs
- 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0)
- Discrete inputs
- 9 (3 dry contact)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RZL-400 series has an extended logic configuration, with free programmable logic in some versions. It covers relay protection, automation, signalling, recording of fault parameters, diagnostics and breaker control on 6-35 kV substations and feeders. It is intended for compact switchgear (КРУ) running on direct, alternating or rectified operating current.
Typical duties are protection of overhead and cable lines, incoming and section breakers, backup protection of transformers, and switchgear for power station auxiliaries. Arc protection uses fibre optic sensors. A digital oscillograph and an event log are built in, together with SCADA integration, desolenoiding of breaker trip coils and backup power from current transformer circuits.
Hardware: 8 analog inputs (IA, IB, IC, 3I0, UA, UB, UC, 3U0), 9 discrete inputs (3 of them dry contact) and 8 relays (5 changeover, 3 make). It has an OLED display, a USB port and RS-485 and Ethernet RJ-45 interfaces, with Modbus RTU/TCP and IEC 60870-5-101/103/104 communication. The case is 220х207х80.5 mm and the operating temperature is -40°C...+60°C.
The six versions differ in three options: power from current circuits, 3 fibre optic inputs and free programmable logic. RZL-400.1-В(У) has none of them. RZL-400.2-В(У) has current circuit power. RZL-400.3-В(У) has current circuit power and 3 fibre optic inputs. RZL-400.4-В(У) has free programmable logic only. RZL-400.5-В(У) has current circuit power and free programmable logic. RZL-400.6-В(У) has current circuit power, 3 fibre optic inputs and free programmable logic.
Protection, automation and control logic can be run as free programmable logic (FPL). In the version designation the letter У stands for flush mounting and the letter В for surface mounting. Events go to a log, fault waveforms are captured by a digital oscillograph, and data reach SCADA systems through the RS-485 and Ethernet RJ-45 ports.
Technical specifications
| Type | Protection, automation and control device for substations and feeders |
|---|---|
| Voltage class | 6-35 kV |
| Analog inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) |
| Discrete inputs | 9 (3 dry contact) |
| Relays | 8 (5 changeover, 3 make) |
| Fibre optic inputs | 3, in versions .3 and .6 |
| Interfaces | RS-485, Ethernet RJ-45, USB |
| Protocols | Modbus RTU/TCP, IEC 60870-5-101/103/104 |
| Display | OLED |
| Operating temperature | -40°C...+60°C |
| Dimensions | 220х207х80.5 mm |
Part numbers
Show all part numbers (6)
RZL-400.1-V(У), RZL-400.2-V(У), RZL-400.3-V(У), RZL-400.4-V(У), RZL-400.5-V(У), RZL-400.6-V(У)
How it compares with similar models
| Parameter | RZL-400 protection, automation and control terminal for 6-35 kV substations and feeders | RZL-100 protection, automation and control device for 6-20 kV substations and feeders | RZL-600 protection, automation and control terminal for 6-154 kV substations and feeders | RZL-50.RPN microprocessor controller for transformer on-load tap changers |
|---|---|---|---|---|
| Type | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders | Microprocessor device for automatic control of a transformer on-load tap changer |
| Voltage class | 6-35 kV | 6-20 kV | 6-154 kV | — |
| Analog inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 4 (UAB, 3U0, Iвв, Iсв) |
| Discrete inputs | 9 (3 dry contact) | 8 (4 dry contact) | 21 (including 3 dry contact) | 8, optically isolated |
| Relays | 8 (5 changeover, 3 make) | 8 (switching group, including 1 bistable K3 and 1 device integrity relay KWD) | 17 (8 changeover, 6 make, 1 signalling, 2 double changeover) | 8 free-purpose (K2 and K5 with extra contacts, KWD signalling) |
| Fibre optic inputs | 3, in versions .3 and .6 | 3 (for arc protection sensors) | 3 (cable length 5 m) | — |
European equivalents
BELplus OZE, ZLF / ZLV distance protection terminal for HV lines, PROTECTA DTIVA, SMPR / SMPR-2 / SMPR ETH multifunction protection terminals for MV feeders (current, voltage, power, directional protection)
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
RZL-400 protection, automation and control terminal for 6-35 kV substations and feeders. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the six RZL-400 versions differ?
They differ in three features: power from current circuits (.2, .3, .5, .6), 3 fibre optic inputs (.3, .6) and free programmable logic (.4, .5, .6). The basic RZL-400.1 has none of them.
Which communication protocols does the RZL-400 support?
Modbus RTU/TCP and IEC 60870-5-101/103/104 through the RS-485 and Ethernet RJ-45 ports.
How many inputs and relays does the RZL-400 have?
8 analog inputs, 9 discrete inputs (3 dry contact) and 8 relays: 5 changeover and 3 make.
Similar equipment from other manufacturers