RZL-50.RPN microprocessor controller for transformer on-load tap changers
The RZL-50.RPN drives the on-load tap changer of a power transformer. It has 4 analog inputs, 8 discrete inputs, 8 relays, an RS-485 port, a digital oscillograph and an event log.
- Type
- Microprocessor device for automatic control of a transformer on-load tap changer
- Controlled transformer
- 2- or 3-winding power transformer
- Analog inputs
- 4 (UAB, 3U0, Iвв, Iсв)
- Discrete inputs
- 8, optically isolated
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RZL-50.RPN controls the tap changer drive of a 2- or 3-winding power transformer while it is under load, in automatic, remote and local voltage regulation. By changing the transformation ratio it monitors the voltage level, holds it within the set limits, supervises the tap changer and applies the required interlocking logic.
A digital oscillograph and an event log are built in, and the device connects to SCADA systems over RS-485 using Modbus RTU. Local control and indication are on an OLED display. Operating temperature is -40°C...+60°C. The device acts on the tap changer drive in automatic, remote and local regulation modes, events are written to the log, and fault waveforms are captured by the digital oscillograph. It is intended for power stations and substations of 6-35 kV.
Hardware: 4 analog inputs (UAB, 3U0, Iвв, Iсв), 8 optically isolated discrete inputs and 8 free-purpose relays. Relays K2 and K5 carry extra contacts, and a separate KWD relay is used for signalling.
It is fitted in the relay compartments of КРП and КРПН switchgear at power stations and substations, and on panels and control cabinets in relay rooms and control desks. The case is 170х96х180 mm, 139.2х88.2х177 mm without the front panel, and the mounting window is 143х92 mm. It is flush-mounted: the panel needs a 143х92 mm cut-out and the front panel projects beyond it. Software version is 17.
After storage with the power off, the device should be left energised for at least 1 hour to charge the internal battery that keeps the clock running.
Technical specifications
| Type | Microprocessor device for automatic control of a transformer on-load tap changer |
|---|---|
| Controlled transformer | 2- or 3-winding power transformer |
| Analog inputs | 4 (UAB, 3U0, Iвв, Iсв) |
| Discrete inputs | 8, optically isolated |
| Relays | 8 free-purpose (K2 and K5 with extra contacts, KWD signalling) |
| Communication port | RS-485 |
| Protocol | Modbus RTU |
| Display | OLED |
| Operating temperature | -40°C...+60°C |
| Dimensions | 170х96х180 mm |
| Dimensions without front panel | 139.2х88.2х177 mm |
| Mounting window | 143х92 mm |
| Software version | 17 |
Part numbers
Show all part numbers (1)
RZL-50.RPN
How it compares with similar models
| Parameter | RZL-50.RPN microprocessor controller for transformer on-load tap changers | RZL-400 protection, automation and control terminal for 6-35 kV substations and feeders | RZL-100 protection, automation and control device for 6-20 kV substations and feeders | RZL-600 protection, automation and control terminal for 6-154 kV substations and feeders |
|---|---|---|---|---|
| Type | Microprocessor device for automatic control of a transformer on-load tap changer | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders |
| Analog inputs | 4 (UAB, 3U0, Iвв, Iсв) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) |
| Discrete inputs | 8, optically isolated | 9 (3 dry contact) | 8 (4 dry contact) | 21 (including 3 dry contact) |
| Relays | 8 free-purpose (K2 and K5 with extra contacts, KWD signalling) | 8 (5 changeover, 3 make) | 8 (switching group, including 1 bistable K3 and 1 device integrity relay KWD) | 17 (8 changeover, 6 make, 1 signalling, 2 double changeover) |
| Dimensions | 170х96х180 mm | 220х207х80.5 mm | 220х207х80.5 mm | 270х220х110.5 |
European equivalents
TAPCON 230 / 250 voltage regulator for transformers with OLTC, SPRECON-E-C-AVR, PROTECTA DTRV/TR, BELplus ARN / BELplus SZR
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
RZL-50.RPN microprocessor controller for transformer on-load tap changers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which transformers does the RZL-50.RPN control?
It controls the on-load tap changer drive of a 2- or 3-winding power transformer, with automatic, remote and local voltage regulation.
What inputs and outputs does it have?
4 analog inputs (UAB, 3U0, Iвв, Iсв), 8 optically isolated discrete inputs and 8 free-purpose relays. Communication is via the RS-485 port using Modbus RTU.
What are the operating temperature range and dimensions?
-40°C to +60°C. The device measures 170х96х180 mm and needs a 143х92 mm mounting window.
Similar equipment from other manufacturers