RZL-100 protection, automation and control device for 6-20 kV substations and feeders
The RZL-100 is a protection, automation, control and signalling device for 6-20 kV feeders that needs no external auxiliary supply. It has 8 analog inputs, 8 discrete inputs, 8 relays, RS-485 and Ethernet ports.
- Type
- Protection, automation and control device for substations and feeders
- Voltage class
- 6-20 kV
- External auxiliary supply
- not required
- Analog inputs
- 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RZL-100 series is a new line of protection and automation devices for 6-20 kV feeders, covering relay protection, automation, control and signalling. No external auxiliary power source is needed. The devices serve as main or backup protection in power systems.
Typical duties are protection of 6-20 kV overhead and cable lines, incoming and section breakers, and backup protection of transformers. A digital oscillograph and an event log are included, with backup power from current transformer circuits, arc protection on fibre optic sensors and desolenoiding of breaker trip coils. SCADA integration runs over RS-485 and Ethernet RJ-45 using Modbus RTU and Modbus TCP.
Hardware: 8 analog inputs (IA, IB, IC, 3I0, UA, UB, UC, 3U0), 8 discrete inputs (4 of them dry contact), a switching group of 8 relays including one bistable relay K3 and a device integrity relay KWD, and 3 fibre optic inputs for arc protection sensors. The display is OLED. The case is 220х207х80.5 mm and the operating temperature is -40°C...+60°C.
Versions: the RZL-100.1-В (У) is basic, with no current circuit power, no desolenoiding and no fibre optic inputs. The RZL-100.2-В (У) is extended, with current circuit power and desolenoiding but no fibre optic inputs. The RZL-100.3-В (У) is full: current circuit power, desolenoiding and 3 fibre optic inputs, with 3 sensors supplied. In the designation the letter У stands for flush mounting and В for surface mounting.
After storage with the power off, leave the device energised for at least 1 hour to charge the internal battery that keeps the clock running.
Technical specifications
| Type | Protection, automation and control device for substations and feeders |
|---|---|
| Voltage class | 6-20 kV |
| External auxiliary supply | not required |
| Analog inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) |
| Discrete inputs | 8 (4 dry contact) |
| Relays | 8 (switching group, including 1 bistable K3 and 1 device integrity relay KWD) |
| Fibre optic inputs | 3 (for arc protection sensors) |
| Communication ports | RS-485, Ethernet RJ-45 |
| Protocols | Modbus RTU, Modbus TCP |
| Display | OLED |
| Operating temperature | -40°C...+60°C |
| Dimensions | 220х207х80.5 mm |
Part numbers
Show all part numbers (3)
RZL-100.1-V (У), RZL-100.2-V (У), RZL-100.3-V (У)
How it compares with similar models
| Parameter | RZL-100 protection, automation and control device for 6-20 kV substations and feeders | RZL-400 protection, automation and control terminal for 6-35 kV substations and feeders | RZL-600 protection, automation and control terminal for 6-154 kV substations and feeders | RZL-50.RPN microprocessor controller for transformer on-load tap changers |
|---|---|---|---|---|
| Type | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders | Protection, automation and control device for substations and feeders | Microprocessor device for automatic control of a transformer on-load tap changer |
| Voltage class | 6-20 kV | 6-35 kV | 6-154 kV | — |
| Analog inputs | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 8 (IA, IB, IC, 3I0, UA, UB, UC, 3U0) | 4 (UAB, 3U0, Iвв, Iсв) |
| Discrete inputs | 8 (4 dry contact) | 9 (3 dry contact) | 21 (including 3 dry contact) | 8, optically isolated |
| Relays | 8 (switching group, including 1 bistable K3 and 1 device integrity relay KWD) | 8 (5 changeover, 3 make) | 17 (8 changeover, 6 make, 1 signalling, 2 double changeover) | 8 free-purpose (K2 and K5 with extra contacts, KWD signalling) |
| Fibre optic inputs | 3 (for arc protection sensors) | 3, in versions .3 and .6 | 3 (cable length 5 m) | — |
European equivalents
BELplus OZE, IRV MV feeder protection terminal (V platform), PROTECTA DTIVA, SPR10
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
RZL-100 protection, automation and control device for 6-20 kV substations and feeders. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the RZL-100 need an external power source?
No. The series needs no external auxiliary supply and draws power from current circuits in the versions that include it (RZL-100.2 and RZL-100.3).
How do RZL-100.1, .2 and .3 differ?
The RZL-100.1 is basic: no current circuit power, no desolenoiding, no fibre optic inputs. The RZL-100.2 adds current circuit power and desolenoiding, and the RZL-100.3 also has 3 fibre optic inputs with 3 sensors included.
Which interfaces and protocols does the RZL-100 have?
RS-485 and Ethernet RJ-45 ports, with Modbus RTU and Modbus TCP protocols for SCADA integration.