УАВР-01 (6-35 kV) and УАВР-02 (0.4 kV) automatic transfer switching units
УАВР-01 and УАВР-02 connect a backup power source in the protection and automation schemes of switchgear with two busbar sections. УАВР-01 serves 6-35 kV, УАВР-02 serves 0.4 kV. Each has 4 voltage inputs, 6 discrete inputs and 8 output relays.
- Versions
- УАВР-01 (6-35 kV), УАВР-02 (0.4 kV); protruding (В) or recessed (У) mounting
- Voltage inputs
- 4
- Nominal line input voltage
- 100, 220, 380 V depending on version
- Measuring range
- 40 - 130 % Uном
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The УАВР series are automatic transfer switching units. In relay protection and automation schemes of switchgear with two busbar sections they bring in the backup power source. УАВР-01 is for energy facilities rated from 6 to 35 kV and УАВР-02 is for 0.4 kV.
The unit measures voltage at the incomers and on the busbar sections, and starts the transfer when voltage drops. The voltage drop setting is 60 - 80 % Unom, the healthy-section voltage needed to start the transfer is 80 - 100 % Unom, operating time is 0.5 - 30.0 s and readiness time is 5.0 - 20.0 s, both in steps of 0.1 s. The measuring range is 40 - 130 % Unom with a basic error of ±5.0 %.
After a successful transfer the units can return to normal mode automatically once voltage is back on the supply line of the tripped incomer; two modes of this function are available. A built-in digital display shows incomer voltage, and LEDs show breaker positions and whether voltage is present on the two busbar sections.
The four voltage inputs are rated 100, 220 or 380 V line voltage depending on version and withstand 1.2 Unom continuously and 1.3 Unom briefly. The six discrete inputs are supplied from an internal source of 130 ± 15 V that is galvanically separate, with input power up to 0.8 W. The eight output relays switch up to 300 V DC and 400 V AC, with an AC make and break current of 8 A, a DC break current of 0.3 A at L/R = 20 ms and 5 A continuously through the contacts.
The suffix В marks protruding mounting and У marks recessed mounting. УАВР-01 is made for 100, 220 and 380 V with 100 V discrete inputs, while УАВР-02 has 220 or 380 V inputs with 220 or 380 V discrete inputs. A metal case screens the unit from interference. Power draw is up to 5 W, insulation resistance at least 50 MOhm, mass up to 2 kg, and the unit carries 20 LEDs.
Technical specifications
| Versions | УАВР-01 (6-35 kV), УАВР-02 (0.4 kV); protruding (В) or recessed (У) mounting |
|---|---|
| Voltage inputs | 4 |
| Nominal line input voltage | 100, 220, 380 V depending on version |
| Measuring range | 40 - 130 % Uном |
| Basic voltage measurement error | ±5.0 % |
| Voltage drop setting | 60 - 80 % Uном |
| Healthy section voltage setting for ATS start | 80 - 100 % Uном |
| Operating time setting | 0.5 - 30.0 s |
| Readiness time setting | 5.0 - 20.0 s |
| Discrete inputs | 6 |
| Internal source voltage | 130 ± 15 V |
| Output relays | 8 |
| Max switched voltage DC / AC | 300 V / 400 V |
| AC make and break current | 8 A |
| DC break current at L/R = 20 ms | 0.3 A |
| Continuous contact current | 5 A |
| LEDs | 20 |
| Operating temperature range | -40 °C to +55 °C |
| Insulation resistance | min 50 MOhm |
| Power consumption | max 5 W |
| Mass | max 2 kg |
Part numbers
Show all part numbers (4)
УАВР-01-V, УАВР-01-У, УАВР-02-V, УАВР-02-У
How it compares with similar models
| Parameter | УАВР-01 (6-35 kV) and УАВР-02 (0.4 kV) automatic transfer switching units | РНМ-01 microprocessor power direction relay, three phase currents and voltages | РНМ-01М power direction relay with three directional overcurrent stages | ВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply |
|---|---|---|---|---|
| Output relays | 8 | 6 | 8 | — |
| Power consumption | max 5 W | max 3 W | — | 5 W max. |
European equivalents
SO-52v11-eMSZR, BELplus ARN / BELplus SZR, PROTECTA HSBT, METRA
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
УАВР-01 (6-35 kV) and УАВР-02 (0.4 kV) automatic transfer switching units. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which networks are УАВР-01 and УАВР-02 made for?
УАВР-01 serves facilities from 6 to 35 kV and УАВР-02 serves 0.4 kV, both with two busbar sections.
What are the setting ranges?
Voltage drop 60 - 80 % Unom, healthy-section voltage for transfer start 80 - 100 % Unom, operating time 0.5 - 30.0 s and readiness time 5.0 - 20.0 s.
Which mounting and voltage versions exist?
Protruding (В) or recessed (У) mounting, with input voltage of 100, 220 or 380 V depending on version.