International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

РНМ-01М power direction relay with three directional overcurrent stages

The РНМ-01М provides directional overcurrent protection and determines the direction of current flow in a three-phase network. It has three stages, 6 analog inputs, 8 discrete inputs, 8 output relays, RS-485 and Ethernet.

Type
Microprocessor power direction relay
Rated operating voltage DC/AC
=220 V / ~220 V; =110 V / ~110 V
Rated phase current
5 A (1 A)
Measured current range
0.2 – 130 A (In=5 A); 0.02 – 7 A (In=1 A)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The РНМ-01М combines directional overcurrent protection with determination of the direction of current flow in a three-phase network. It is used for selective operation of overcurrent protection on double-ended fed lines and ring lines, and is connected to current and voltage transformers. Three overcurrent stages are provided.

When power flows from the busbars into the line, the relay permits or blocks (according to the setting) tripping of the protection for faults. When power flows from the line towards the busbars, it blocks or permits the protection in the opposite sense. The power direction (operating sector) is set to ‘into the line’, ‘into the busbars’ or ‘sector’. The angle of maximum sensitivity is adjustable from 0 to 359 deg in steps of 1 deg, with a hysteresis of 5 to 20 deg.

Measurement: three phase currents with a rated value of 5 A (1 A), measured over 0.2 – 130 A (0.02 – 7 A) with an error of ± 2.5 %; three phase voltages with a rated value of 100 V, measured over 5 – 160 V with an error of ± 2.5 %; phase angle error ± 2°. Current settings cover 0.2 – 130 A (0.02 – 7 A) in steps of 0.01 A (0.001 A) and time settings 0.01 – 600 s in steps of 0.01 s.

The operating supply is 220 V or 110 V DC/AC within 88 – 264 V, consumption up to 5 W and readiness time 0.1 s. The relay has 8 discrete inputs (4 optically isolated, 4 powered from the internal +24 V source), 8 output relays switching AC of 24 – 400 V at 8 A and DC of 24 – 300 V, 8 LEDs and an OLED display. Communication uses RS-485 and Ethernet RJ45 with Modbus RTU and Modbus TCP. Settings are made with the ‘Монитор 2’ software.

The flush-mounted case measures 220×207×80.5 mm and weighs up to 3 kg. Operating temperature is -40 to +60 °C and insulation strength is 2.0 kV at 50 Hz and 5 kV impulse.

Technical specifications

TypeMicroprocessor power direction relay
Rated operating voltage DC/AC=220 V / ~220 V; =110 V / ~110 V
Rated phase current5 A (1 A)
Measured current range0.2 – 130 A (In=5 A); 0.02 – 7 A (In=1 A)
Rated phase voltage100 V
Measured phase voltage range5 – 160 V
Voltage and phase angle error± 2.5 % ; ± 2°
Operating frequency range49 – 51 Hz
Discrete inputs8: 4 optically isolated and 4 powered from the internal +24 V source
Output relays8
AC switching24 – 400 V, 8 A
DC switching24 – 300 V; breaking 0.3 A at L/R = 20 ms
Communication interfacesRS-485 x 1, Ethernet (RJ45) x 1
Communication protocolsModbus RTU, Modbus TCP
Directional overcurrent stages3
Current setting range0.2 – 130 A (0.02 – 7 A), step 0.01 A (0.001 A)
Dimensions (WxHxD)220×207×80.5 mm
Weightmax. 3 kg
Operating temperature-40 to +60 °C

Part numbers

Show all part numbers (4)

РНМ-01М-5220V, РНМ-01М-1220V, РНМ-01М-5110V, РНМ-01М-1110V

European equivalents

PRO-N NA10–NA60

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РНМ-01М power direction relay with three directional overcurrent stages. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What rated currents and supply voltages does the РНМ-01М have?

Rated phase current of 5 A or 1 A and an operating supply of 220 V or 110 V, DC/AC, with an operating voltage range of 88 – 264 V. Four versions exist: РНМ-01М-5220В, -1220В, -5110В and -1110В.

What is a power direction relay needed for?

It gives selective operation of overcurrent protection on double-ended fed lines and ring lines: the relay permits or blocks the protection depending on the power direction and the setting.

Which interfaces and protocols does the РНМ-01М support?

RS-485 (9600 to 115200 bit/s) and Ethernet RJ45 (10/100 Mbit/s), with the Modbus RTU and Modbus TCP protocols.