РЗЛ-05.РПН on-load tap-changer control device for transformers, 12 output relays, 2 supply channels
The РЗЛ-05.РПН controls the on-load tap-changer drives of two- and three-winding power transformers during automatic and manual voltage regulation. It has 12 output relays, two independent supply channels of 90–254 V, and USB and RS-485 interfaces with Modbus RTU. Operating temperature is -40...+55 °C.
- Operating supply voltage, DC/AC
- 90 - 254 V
- Number of independent supply channels
- 2
- Power consumption
- 8 W
- Readiness time, max
- 0.2 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.РПН is intended for full control of the tap-changer (OLTC) drives of a two- or three-winding power transformer under load. It works in automatic and manual voltage regulation by changing the transformation ratio. The device monitors the voltage level, holds it within the set limits, issues commands to the OLTC drive, supervises the drive and implements the required interlocking logic. A digital oscillograph, an event log, SCADA integration and logic programming are included.
The measuring section has four phase currents with a rated value of 5 A, a rated phase voltage of 100 V and four measured line voltages in the range 1–150 V. The current circuits withstand 10 A continuously and 100 A for up to 1 s, and the voltage inputs withstand 130 V continuously. One temperature input covers 0–125 °C. The device monitors two busbar systems.
Discrete inputs are rated at 220 V with an operating threshold of 132–176 V and a signal duration of at least 40 ms. There are twelve output relays: switching voltage is 300 V DC and 400 V AC, AC making and breaking current is 8 A, and for relay К1 it is 16 A. Communication is by USB and two RS-485 ports with Modbus RTU at 9600, 19200 or 38400 bit/s.
Two independent channels supply the unit, operating supply voltage is 90–254 V DC/AC, power consumption is 8 W and readiness time is up to 0.2 s. The case is recessed, 205x240x190 mm, with a mass of up to 6 kg and 20 LEDs, 8 of them programmable. Insulation resistance is at least 50 MΩ, insulation strength is 5 / 2 kV and permissible humidity is 98 % at 25 °C.
Technical specifications
| Operating supply voltage, DC/AC | 90 - 254 V |
|---|---|
| Number of independent supply channels | 2 |
| Power consumption | 8 W |
| Readiness time, max | 0.2 s |
| Rated input phase current | 5 A |
| Number of phase currents | 4 |
| Current circuit thermal withstand: continuous / up to 1 s | 10 A / 100 A |
| Rated phase voltage | 100 V |
| Number of measured line voltages | 4 |
| Measured voltage range | 1 - 150 V |
| Measured temperature range, 1 input | 0 - 125 °C |
| Interfaces | USB 1 pc, RS-485 2 pcs |
| RS-485 protocol | Modbus RTU |
| Discrete input operating voltage level | 132 - 176 V |
| Number of output relays | 12 |
| Switching voltage | DC 300 V, AC 400 V |
| Dimensions (WxHxD) | 205х240х190 mm |
| Mass, max | 6 kg |
| LEDs, total / programmable | 20 / 8 |
| Operating temperature range | -40... +55 °C |
How it compares with similar models
| Parameter | РЗЛ-05.РПН on-load tap-changer control device for transformers, 12 output relays, 2 supply channels | РЗЛ-05.ЦС microprocessor central signalling unit, 40 inputs, 9 relays | РЗЛ-05.АЕ protection and automation unit for 6–35 kV feeders, 24 output relays | РНМ-01 microprocessor power direction relay, three phase currents and voltages |
|---|---|---|---|---|
| Power consumption | 8 W | 9 W | 2x13 W max. | max 3 W |
| Number of phase currents | 4 | — | 4; 7 (-Т2); 11 (-Т3) | 3 |
| Interfaces | USB 1 pc, RS-485 2 pcs | USB 1 pc, RS-485 2 pcs | RS-485 – 2 pcs, Ethernet; USB (front port) | — |
| Dimensions (WxHxD) | 205х240х190 mm | 300х240х128 mm | — | 231х145х100 mm |
| Operating temperature range | -40... +55 °C | -40... +55 °C | −40…+60 °C | — |
European equivalents
REGSys REG-D / REG-DA, BELplus ARN / BELplus SZR, TAPCON 230 / 250 voltage regulator for transformers with OLTC, PROTECTA DTRV/TR
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.РПН on-load tap-changer control device for transformers, 12 output relays, 2 supply channels. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which transformers does the РЗЛ-05.РПН serve?
Two- and three-winding power transformers with an on-load tap-changer, in automatic and manual voltage regulation.
How many output relays and supply channels does the device have?
12 output relays and two independent supply channels of 90–254 V DC/AC.
Which interfaces are fitted?
USB and two RS-485 ports with Modbus RTU at 9600, 19200 or 38400 bit/s.