РНМ-01 microprocessor power direction relay, three phase currents and voltages
The РНМ-01 combines directional overcurrent protection with power flow direction detection in three-phase networks. It measures three phase currents (0.2 – 130 A) and three phase voltages (5 – 250 V), has 6 output relays and speaks Modbus RTU and Modbus TCP.
- Nominal operating voltage DC/AC
- =110 / ~100 V; =220 / ~220 V
- Operating supply voltage range
- 90 – 254 V
- Readiness time after power on
- 0.15 s
- Power consumption
- max 3 W
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РНМ-01 relay supplies the directional element that current protection needs on double-fed lines and ring lines. It connects to current and voltage measuring transformers. When power flows from the busbars into the line, the relay, depending on its setting, either releases the protection to trip the fault or blocks it. For power flowing from the line towards the busbars the action is reversed.
Direction is found from the phase angle between the current and voltage harmonics. The relay has a single directional overcurrent stage for phase-to-phase faults: current setting 0.2 – 130 A in steps of 0.01 A, time setting 0.1 – 100 s. The power direction sector is set to line, busbar or sector. The maximum sensitivity angle is adjustable from 0 to 359 degrees in 1 degree steps, with angle hysteresis of 5 – 20 degrees. Minimum sensitivity is 0.02 Inom for current and 0.05 Unom for voltage.
Measuring inputs are three phase currents rated 5 A (thermal withstand 15 A continuous, 400 A for up to 1 s) and three phase voltages rated 100 V with a 5 – 250 V range, at 49 – 51 Hz. There are two opto-isolated digital inputs and six output relays. The relays switch AC voltages of 24 – 400 V with a make and break current of 6 A, and DC voltages of 24 – 300 V with a break current of 0.2 A at L/R = 20 ms.
Auxiliary supply is =110 / ~100 V or =220 / ~220 V within 90 – 254 V, drawing up to 3 W, and the relay is ready 0.15 s after power-up. It includes a digital oscillograph recording for more than 30 s, an event log, an OLED display and 17 LEDs.
A PC connects over USB, and a control system over RS-485 or Ethernet (RJ45), using Modbus RTU or Modbus TCP. Data rate is 9600...115200 bit/s on USB and RS-485 and 10/100 Mbit/s on Ethernet. The case comes in flush-mounted and surface-mounted versions, 231х145х100 mm, with a mass of up to 2 kg. Operating temperature is -40 to +60 °C and humidity up to 98 % at 25 °C.
Technical specifications
| Nominal operating voltage DC/AC | =110 / ~100 V; =220 / ~220 V |
|---|---|
| Operating supply voltage range | 90 – 254 V |
| Readiness time after power on | 0.15 s |
| Power consumption | max 3 W |
| Nominal phase current | 5 A |
| Number of phase currents | 3 |
| Measured current range | 0.2 – 130 A |
| Thermal withstand of current circuits (continuous / up to 1 s) | 15 / 400 A |
| Nominal phase voltage | 100 V |
| Measured phase voltage range | 5 – 250 V |
| Operating frequency range | 49 – 51 Hz |
| Opto-isolated digital inputs | 2 |
| Output relays | 6 |
| Switching voltage AC / DC | 24 – 400 V / 24 – 300 V |
| Current setting | 0.2 – 130 A, крок 0.01 A |
| Time setting | 0.1 – 100 s |
| Maximum sensitivity angle | 0 – 359 град |
| Interfaces and protocols | USB, RS-485, Ethernet (RJ45); Modbus RTU, Modbus TCP |
| Operating temperature | -40 to +60 °C |
| Dimensions (WxHxD) | 231х145х100 mm |
| Mass | max 2 kg |
How it compares with similar models
| Parameter | РНМ-01 microprocessor power direction relay, three phase currents and voltages | РНМ-01М power direction relay with three directional overcurrent stages | РЗЛ-05.АЕ protection and automation unit for 6–35 kV feeders, 24 output relays | РЗЛ-05.РПН on-load tap-changer control device for transformers, 12 output relays, 2 supply channels |
|---|---|---|---|---|
| Power consumption | max 3 W | — | 2x13 W max. | 8 W |
| Number of phase currents | 3 | — | 4; 7 (-Т2); 11 (-Т3) | 4 |
| Output relays | 6 | 8 | 24 (21 normally open, 3 changeover) | — |
| Dimensions (WxHxD) | 231х145х100 mm | 220×207×80.5 mm | — | 205х240х190 mm |
European equivalents
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РНМ-01 microprocessor power direction relay, three phase currents and voltages. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which auxiliary supply voltages are allowed?
=110 / ~100 V or =220 / ~220 V, with an operating range of 90 – 254 V. The relay is ready 0.15 s after power-up.
What interfaces and protocols does the relay have?
USB, RS-485 and Ethernet (RJ45), with data exchange over Modbus RTU and Modbus TCP.
What is the setting range of the maximum sensitivity angle?
0 – 359 degrees in 1 degree steps, with angle hysteresis of 5 – 20 degrees. The direction sector can be line, busbar or sector.
Similar equipment from other manufacturers