LINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V
The LINETRAXX® VMD258 monitors three-phase AC systems for undervoltage and overvoltage using a window function. Nominal system voltages 3AC 100…690 V, supplied from the monitored system, separate alarm relays for each threshold.
- Type
- Undervoltage/overvoltage relay, 3AC
- Nominal system voltage Un
- 3AC 690/500/480/440/400/230/110/100 V
- Supply voltage
- from the monitored system
- Supply frequency range
- 45…66 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
One relay, eight voltage versions. The LINETRAXX® VMD258 supervises three-phase AC systems against undervoltage and overvoltage with a window function. Typical duties are monitoring the power supply of machines and electrical installations, monitoring loads, switching electrical systems on and off at a certain voltage level, monitoring stand-by and emergency supply systems and supply voltage monitoring of portable loads.
The design is pure analogue technology and needs no separate supply: the relay draws its supply from the monitored system and uses double isolation. Nominal system voltages Un are 3AC 690/500/480/440/400/230/110/100 V, selected through the part number (B93010060 for 100 V, B93010061 for 110 V, B93010062 for 230 V, B93010063 for 400 V, B93010064 for 440 V, B93010065 for 480 V, B93010066 for 500 V, B93010067 for 690 V).
Response values are continuously adjustable: undervoltage <U between 0.7…0.95 x Un and overvoltage >U between 1.05…1.3 x Un, with a response delay of 0…5 s. The operating range is 0.5…1.3 x US, the supply frequency 45…66 Hz and the power consumption up to 10 VA. LEDs indicate operation, overvoltage and undervoltage.
Two alarm relays are fitted, each with two changeover contacts (2 x 2), and the electrical endurance is 10000. Where the delay must survive a supply failure, the external energy storage ES258 (B93010068) is added.
The polycarbonate enclosure (UL94 V-0) measures 110,10 x 93 x 72 mm, weighs 825 g and sits on a DIN rail or is screwed down with additional mounting clips B98060008. Terminals are screw type, AWG 24…13, tightening torque 0.5…0.6 Nm, with IP20 on terminals and IP30 on internal components, for -20…+70 °C. Listed standards are DIN EN 60255-1 VDE 0435-300, IEC 60255-127, IEC 60255-27, IEC 60947-5-1 and IEC 60715, and a CE declaration exists.
Technical specifications
| Type | Undervoltage/overvoltage relay, 3AC |
|---|---|
| Nominal system voltage Un | 3AC 690/500/480/440/400/230/110/100 V |
| Supply voltage | from the monitored system |
| Supply frequency range | 45…66 Hz |
| Operating range | 0.5…1.3 x US |
| Setting range | 0.7…1.3 x Un |
| Undervoltage <U (alarm) | 0.7…0.95 x Un |
| Overvoltage >U (alarm) | 1.05…1.3 x Un |
| Response delay | 0…5 s |
| Power consumption | ≤ 10 VA |
| Switching elements | 2 x 2 changeover contacts |
| Electrical endurance | 10000 |
| Degree of protection | IP20 (terminals), IP30 (internal components) |
| Operating temperature | -20…+70 °C |
| Weight | 825 g |
Part numbers
Show all part numbers (10)
B93010060, B93010061, B93010062, B93010063, B93010064, B93010065, B93010066, B93010067, B93010068, B98060008
How it compares with similar models
| Parameter | LINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V | LINETRAXX® ES258 Backup Device for the VMD258 Voltage Relay | LINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 A | LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V |
|---|---|---|---|---|
| Type | Undervoltage/overvoltage relay, 3AC | Energy backup device (capacitor) | Four-channel load current monitor | Voltage and frequency monitoring relay for 3(N)AC |
| Supply voltage | from the monitored system | DC 42…47 V (±35 %) | DC 24 V | — |
| Power consumption | ≤ 10 VA | — | ≤ 2 W | ≤ 3,5 VA (VMD423-D), ≤ 5 VA (VMD423H) |
| Operating temperature | -20…+70 °C | -20…+70 °C | -40…+85 °C | — |
| Weight | 825 g | ≤ 160 g | ≤ 55 g | — |
Request a price and lead time
LINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the VMD258 need a separate supply?
No. It takes its supply from the monitored system, and the version is chosen to match the nominal voltage Un (100…690 V).
What are the adjustment limits of the thresholds?
Undervoltage 0.7…0.95 x Un and overvoltage 1.05…1.3 x Un, with a response delay of 0…5 s.
What is the ES258 for?
It is an external energy storage that powers the relay through a supply failure so that the set response delay stays effective.