International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 A

The LINETRAXX® SmartDetect LCM410 monitors AC and pulsed load currents on four channels in TN, TT and IT networks. Main alarm threshold 6 mA…50 A, frequency range 42 Hz…20 kHz, supply DC 24 V.

Type
Four-channel load current monitor
Supply voltage
DC 24 V
Frequency range
42 Hz…20 kHz
Measuring range (peak)
3 mA…100 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Four feeders, one 1 DU housing. The LINETRAXX® SmartDetect LCM410 watches alternating and pulsating load currents on four independent channels in TN, TT and IT networks, over a frequency range of 42 Hz…20 kHz. The measuring range is 3 mA…100 A (peak) or 2 mA…70 A (rms).

Each channel is evaluated for AC rms and pulsed current and triggers a pre-warning and a main alarm at adjustable thresholds. The main alarm ILn is set between 6 mA…50 A (factory setting 16 A) and the pre-warning between 10…100 % x ILn (70 %). Operating uncertainty is ±10 % at 0.5…5 x ILn, and the rated response load current is 50 A.

Permissible continuous load current depends on how many channels are in use: 85 A on one channel, 60 A on two, 49 A on three and 42 A on four. The supply is DC 24 V with a power consumption of up to 2 W, and the operating temperature is -40…+85 °C.

Parameters are set from the Connect app over NFC (13.56 MHz) or over RS-485 using Modbus RTU at up to 115.2 kbits/s. Cable length is limited to 1200 m at 9.6 kbits/s, and the device address runs from 1…247. The unit also offers digital input I, digital input/output Q and a multifunctional digital/analogue output M+.

The polycarbonate enclosure (flammability class UL94 V-0) clips onto a DIN rail to IEC 60715 and weighs no more than 55 g. Terminals are IP20 and internal components IP30. The device was developed to DIN EN IEC 61010-1 and UL508, with EU and UKCA declarations of conformity. A sealable transparent cover (B80609199), STEP-PS/1 power supplies and CTAC, CTAS, W, WR and WS current transformers are listed as options.

Technical specifications

TypeFour-channel load current monitor
Supply voltageDC 24 V
Frequency range42 Hz…20 kHz
Measuring range (peak)3 mA…100 A
Measuring range rms2 mA…70 A
Rated response load current50 A
Main alarm threshold ILn6 mA…50 A (16 A)
Pre-warning10…100 % x ILn (70 %)
Operating uncertainty±10 % (at 0.5…5 x ILn)
Continuous load current, 1 / 2 / 3 / 4 channels85 A / 60 A / 49 A / 42 A
Power consumption≤ 2 W
InterfacesRS-485 (Modbus RTU), NFC
Degree of protectionIP20 (terminals), IP30 (internal components)
Weight≤ 55 g
Operating temperature-40…+85 °C

Part numbers

Show all part numbers (5)

B85604049, B80609199, B94053110, B94053111, B94053112

How it compares with similar models

ParameterLINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 ALINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitorLINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current deviceLINETRAXX® CEP410R-2 residual current monitor for the central earthing point
Supply voltageDC 24 VDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 V
Frequency range42 Hz…20 kHz15 Hz…20 kHzDC, 15 Hz…20 kHz42…70 Hz
Measuring range (peak)3 mA…100 A3 mA…100 A3 mA…28 A—
Measuring range rms2 mA…70 A2 mA…70 A2 mA…20 A—
Degree of protectionIP20 (terminals), IP30 (internal components)—IP20IP20
Weight≤ 55 g≤ 55 g≤ 125 g≤ 100 g

Request a price and lead time

LINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How are the thresholds set on the LCM410?

From the Connect app over NFC, or over RS-485 with Modbus RTU. The main alarm ILn is adjustable between 6 mA…50 A.

What continuous current is allowed with several channels in use?

85 A on one channel, 60 A on two, 49 A on three and 42 A on four.

How long may the RS-485 line be?

Up to 1200 m at 9.6 kbits/s; the baud rate goes up to 115.2 kbits/s and the device address is 1…247.