LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor

The RCMS410 monitors AC, pulsed DC and smooth DC residual currents in earthed power supply systems. It measures 2 mA…70 A (rms) over 15 Hz…20 kHz and has RS-485 Modbus RTU and NFC interfaces.

Measuring range rms
2 mA…70 A
Measuring range (peak)
3 mA…100 A
Frequency range
15 Hz…20 kHz
Detection types
A, F, B, B+

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Four measuring channels make the RCMS410 a residual current monitor for earthed power supply systems. It measures AC, pulsed DC and smooth DC and handles detection types A, F, B and B+, with response values configurable per type.

The measuring range is 2 mA…70 A (rms) and 3 mA…100 A (peak) across 15 Hz…20 kHz. Response values are 6 mA…30 A for type A, 6 mA…30 A for type F and 10 mA…10 A for type B.

The RCMS410-24 runs on DC 24 V with an LED bargraph. The RCMS425-L and RCMS425-D take AC/DC 100…240 V, the first with an LED bargraph and the second with a TFT display. Communication is RS-485 with Modbus RTU plus NFC. Terminals comprise a digital input I, a digital input/output Q and a multifunctional digital/analogue output M+.

The enclosure is 1 TE (1 module) wide, clips on a DIN rail to IEC 60715 and weighs at most 55 g, with protection rating IP20; IP30. Operating temperature is -40…+70 °C and storage temperature -40…+85 °C. Overvoltage category is III and altitude up to 2000 m.

Typical tasks are monitoring residual currents in stationary electrical installations, preventive maintenance, fire hazard locations, EMC monitoring of TN-S systems, monitoring PE and protective-bonding conductors, and spotting overload of N conductors caused by harmonics. The monitor follows DIN EN 62020-1, IEC 62020-1, IEC 60755, VDE 0664-400, UL508 and UL1053.

Technical specifications

Measuring range rms2 mA…70 A
Measuring range (peak)3 mA…100 A
Frequency range15 Hz…20 kHz
Detection typesA, F, B, B+
Response value type A6 mA…30 A
Response value type F6 mA…30 A
Response value type B10 mA…10 A
Supply voltageDC 24 V; AC/DC 100…240 V
InterfacesRS-485 (Modbus RTU), NFC
Inputs and outputs1 digital input (I); 1 digital input/output (Q); 1 multifunctional digital/analogue output (M+)
Operating temperature-40…+70 °C
Storage temperature-40…+85 °C
Protection ratingIP20; IP30
Weight≤ 55 g
Width1 TE (1 module)
MountingDIN rail (IEC 60715)

Part numbers

Show all part numbers (16)

B84604040, B84604041, B84604042, B84605040, B84605041, B84605042, B84606040, B84606041, B84606042, B75061020, B75061021, B75061022, B94053110, B94053111, B94053112, B80609199

How it compares with similar models

ParameterLINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitorLINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 ALINETRAXX® CEP410R-2 residual current monitor for the central earthing pointLINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current device
Measuring range rms2 mA…70 A2 mA…70 A—2 mA…20 A
Measuring range (peak)3 mA…100 A3 mA…100 A—3 mA…28 A
Frequency range15 Hz…20 kHz42 Hz…20 kHz42…70 HzDC, 15 Hz…20 kHz
Supply voltageDC 24 V; AC/DC 100…240 VDC 24 VDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 V
Operating temperature-40…+70 °C-40…+85 °C-25…+55 °C-25…+55 °C
Weight≤ 55 g≤ 55 g≤ 100 g≤ 125 g

Request a price and lead time

LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many channels does the RCMS410 have and which currents does it monitor?

It has four channels and covers types A, F, B and B+, that is AC, pulsed DC and smooth DC.

How do the RCMS410-24, RCMS425-L and RCMS425-D differ?

The RCMS410-24 runs on DC 24 V with an LED bargraph. The RCMS425-L and RCMS425-D take AC/DC 100…240 V, with an LED bargraph and a TFT display respectively.

Why monitor N conductors?

To detect overload caused by harmonics. The monitor also covers PE and protective-bonding conductors.