LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor
The RCMS410 monitors AC, pulsed DC and smooth DC residual currents in earthed power supply systems. It measures 2 mA…70 A (rms) over 15 Hz…20 kHz and has RS-485 Modbus RTU and NFC interfaces.
- Measuring range rms
- 2 mA…70 A
- Measuring range (peak)
- 3 mA…100 A
- Frequency range
- 15 Hz…20 kHz
- Detection types
- A, F, B, B+
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Four measuring channels make the RCMS410 a residual current monitor for earthed power supply systems. It measures AC, pulsed DC and smooth DC and handles detection types A, F, B and B+, with response values configurable per type.
The measuring range is 2 mA…70 A (rms) and 3 mA…100 A (peak) across 15 Hz…20 kHz. Response values are 6 mA…30 A for type A, 6 mA…30 A for type F and 10 mA…10 A for type B.
The RCMS410-24 runs on DC 24 V with an LED bargraph. The RCMS425-L and RCMS425-D take AC/DC 100…240 V, the first with an LED bargraph and the second with a TFT display. Communication is RS-485 with Modbus RTU plus NFC. Terminals comprise a digital input I, a digital input/output Q and a multifunctional digital/analogue output M+.
The enclosure is 1 TE (1 module) wide, clips on a DIN rail to IEC 60715 and weighs at most 55 g, with protection rating IP20; IP30. Operating temperature is -40…+70 °C and storage temperature -40…+85 °C. Overvoltage category is III and altitude up to 2000 m.
Typical tasks are monitoring residual currents in stationary electrical installations, preventive maintenance, fire hazard locations, EMC monitoring of TN-S systems, monitoring PE and protective-bonding conductors, and spotting overload of N conductors caused by harmonics. The monitor follows DIN EN 62020-1, IEC 62020-1, IEC 60755, VDE 0664-400, UL508 and UL1053.
Technical specifications
| Measuring range rms | 2 mA…70 A |
|---|---|
| Measuring range (peak) | 3 mA…100 A |
| Frequency range | 15 Hz…20 kHz |
| Detection types | A, F, B, B+ |
| Response value type A | 6 mA…30 A |
| Response value type F | 6 mA…30 A |
| Response value type B | 10 mA…10 A |
| Supply voltage | DC 24 V; AC/DC 100…240 V |
| Interfaces | RS-485 (Modbus RTU), NFC |
| Inputs and outputs | 1 digital input (I); 1 digital input/output (Q); 1 multifunctional digital/analogue output (M+) |
| Operating temperature | -40…+70 °C |
| Storage temperature | -40…+85 °C |
| Protection rating | IP20; IP30 |
| Weight | ≤ 55 g |
| Width | 1 TE (1 module) |
| Mounting | DIN rail (IEC 60715) |
Part numbers
Show all part numbers (16)
B84604040, B84604041, B84604042, B84605040, B84605041, B84605042, B84606040, B84606041, B84606042, B75061020, B75061021, B75061022, B94053110, B94053111, B94053112, B80609199
How it compares with similar models
| Parameter | LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor | LINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 A | LINETRAXX® CEP410R-2 residual current monitor for the central earthing point | LINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current device |
|---|---|---|---|---|
| Measuring range rms | 2 mA…70 A | 2 mA…70 A | — | 2 mA…20 A |
| Measuring range (peak) | 3 mA…100 A | 3 mA…100 A | — | 3 mA…28 A |
| Frequency range | 15 Hz…20 kHz | 42 Hz…20 kHz | 42…70 Hz | DC, 15 Hz…20 kHz |
| Supply voltage | DC 24 V; AC/DC 100…240 V | DC 24 V | DC 24 V; AC/DC 100…240 V | DC 24 V; AC/DC 100…240 V |
| Operating temperature | -40…+70 °C | -40…+85 °C | -25…+55 °C | -25…+55 °C |
| Weight | ≤ 55 g | ≤ 55 g | ≤ 100 g | ≤ 125 g |
Request a price and lead time
LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many channels does the RCMS410 have and which currents does it monitor?
It has four channels and covers types A, F, B and B+, that is AC, pulsed DC and smooth DC.
How do the RCMS410-24, RCMS425-L and RCMS425-D differ?
The RCMS410-24 runs on DC 24 V with an LED bargraph. The RCMS425-L and RCMS425-D take AC/DC 100…240 V, with an LED bargraph and a TFT display respectively.
Why monitor N conductors?
To detect overload caused by harmonics. The monitor also covers PE and protective-bonding conductors.