International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® SmartDetect MRCD410R single-channel modular residual current device

The MRCD410R measures AC and pulsed DC residual current in earthed TN and TT networks. It covers 10 mA to 30 A, has RS-485 Modbus RTU and NFC interfaces, and the enclosure is 18 mm wide.

Residual operating current
10 mA…30 A
Frequency range
42…70 Hz
Supply voltage
DC 24 V; AC/DC 100…240 V (MRCD410R-2 only)
Rated voltage
250 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Used in earthed TN and TT networks, the MRCD410R is a single-channel modular residual current device for AC and pulsed DC. It provides protection against indirect contact, protection against thermal effects and system protection.

The residual operating current covers 10 mA…30 A and the frequency range is 42…70 Hz. Two versions exist: the MRCD410R-24 on DC 24 V and the MRCD410R-2 on AC/DC 100…240 V and DC 24 V.

Rated voltage is 250 V, rated insulation voltage 250 V and rated impulse voltage 4 kV. Rated thermal short-term current is 2.4 kA / 1 s, and operating temperature is -25…+55 °C.

Data go over RS-485 with Modbus RTU, and NFC is available for configuration. The DIN rail enclosure is 18 mm wide, 100 mm high and 64 mm deep. A sealable transparent cover, part number B80609199, is a spare part.

The device follows IEC 60947-2 Annex M, IEC 60364-4-41, IEC 60364-4-42, IEC 60364-4-43 and IEC 60364-5-53, together with DIN VDE 0100-410, -420, -430 and -530. UL508, IEC 60664-1, IEC 60664-3, IEC 61010-1 and IEC 60947-5-1 also apply.

Technical specifications

Residual operating current10 mA…30 A
Frequency range42…70 Hz
Supply voltageDC 24 V; AC/DC 100…240 V (MRCD410R-2 only)
Rated voltage250 V
Rated insulation voltage250 V
Rated impulse voltage4 kV
Rated thermal short-term current2.4 kA / 1 s
Operating temperature-25…+55 °C
InterfacesRS-485 (Modbus RTU), NFC
Width x height x depth18 x 100 x 64 mm
MountingDIN rail

Part numbers

Show all part numbers (3)

B74602020, B74603020, B80609199

How it compares with similar models

ParameterLINETRAXX® SmartDetect MRCD410R single-channel modular residual current deviceLINETRAXX® CEP410R-2 residual current monitor for the central earthing pointLINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current deviceLINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 A
Frequency range42…70 Hz42…70 HzDC, 15 Hz…20 kHz—
Supply voltageDC 24 V; AC/DC 100…240 V (MRCD410R-2 only)DC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 V—
MountingDIN railDIN rail to IEC 60715—DIN rail

Request a price and lead time

LINETRAXX® SmartDetect MRCD410R single-channel modular residual current device. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What protection tasks is the MRCD410R used for?

Protection against indirect contact, protection against thermal effects and system protection in earthed TN and TT networks.

What supply do the MRCD410R-24 and MRCD410R-2 use?

The MRCD410R-24 runs on DC 24 V; the MRCD410R-2 takes AC/DC 100…240 V and DC 24 V.

What are the enclosure dimensions?

18 mm wide, 100 mm high and 64 mm deep, for DIN rail mounting.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides