LINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 A
RCM410R-24 and RCM410R-2 monitor residual current in AC TN, TT and IT systems. They are type A, with IΔn from 10 mA to 30 A, 42…70 Hz, and RS-485 Modbus RTU and NFC interfaces.
- Residual operating current IΔn
- 10 mA…30 A
- Type
- A (AC and pulsed DC)
- Supply RCM410R-24
- DC 24 V
- Supply RCM410R-2
- AC/DC 100…240 V; DC 24 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RCM410R is a single-channel monitor for residual current in AC systems, sensitive to AC and pulsed DC (type A). It is used in TN, TT and IT systems, with adjustable response values for prewarning and main alarm.
The residual operating current IΔn spans 10 mA…30 A and the frequency range is 42…70 Hz. The RCM410R-24 runs on DC 24 V, while the RCM410R-2 takes AC/DC 100…240 V, DC 24 V.
RS-485 with Modbus RTU and an NFC interface handle communication and set-up. The relay clips onto a DIN rail. Weight is at most 60 g for the RCM410R-24 and 70 g for the RCM410R-2, and operating temperature is -25…+55 °C.
It was developed to DIN EN IEC 62020-1, UL508 and UL1053. IEC 60664-1, IEC 60664-3 and IEC 61010-1 cover insulation coordination and safety, IEC 60947-5-1 covers control switches, the IEC 60721-3 series covers environmental conditions, and IEC 60715 covers rail mounting.
Technical specifications
| Residual operating current IΔn | 10 mA…30 A |
|---|---|
| Type | A (AC and pulsed DC) |
| Supply RCM410R-24 | DC 24 V |
| Supply RCM410R-2 | AC/DC 100…240 V; DC 24 V |
| Frequency | 42…70 Hz |
| Interfaces | RS-485 (Modbus RTU), NFC |
| Operating temperature | -25…+55 °C |
| Weight RCM410R-24 | ≤ 60 g |
| Weight RCM410R-2 | ≤ 70 g |
| Mounting | DIN rail |
| Standards | DIN EN IEC 62020-1, UL508, UL1053, IEC 60664-1, IEC 61010-1, IEC 60947-5-1 |
Part numbers
Show all part numbers (2)
B74602000, B74603000
How it compares with similar models
| Parameter | LINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 A | LINETRAXX® CEP410R-2 residual current monitor for the central earthing point | LINETRAXX® SmartDetect MRCD410R single-channel modular residual current device | LINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor |
|---|---|---|---|---|
| Operating temperature | -25…+55 °C | -25…+55 °C | -25…+55 °C | -40…+70 °C |
| Mounting | DIN rail | DIN rail to IEC 60715 | DIN rail | DIN rail (IEC 60715) |
Request a price and lead time
LINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the RCM410R-24 and RCM410R-2 differ?
In supply and weight. The RCM410R-24 runs on DC 24 V and weighs at most 60 g; the RCM410R-2 takes AC/DC 100…240 V, DC 24 V and weighs at most 70 g.
In which systems does the RCM410R operate?
It monitors residual current in AC TN, TT and IT systems as a type A device, with IΔn from 10 mA to 30 A.
How are data transmitted?
Over RS-485 with Modbus RTU. An NFC interface is also fitted for configuration.