International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® RCMB300 residual current monitoring module for AC and DC, up to 20 A

The RCMB300 series measures AC and DC fault currents in earthed TN and TT systems. It covers DC to 100 kHz and residual currents up to 20 A, with two adjustable response values between 30 mA and 3 A.

Detection type
AC/DC sensitive, type B and B+
Frequency range
DC…100 kHz
Maximum residual current
20 A
Response values
30 mA…3 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The RCMB300 series measures AC and DC fault currents in earthed TN and TT systems. A module is built from RCMB301 evaluation electronics and a CTBC measuring current transformer, and acquires the fault current as AC/DC sensitive type B or B+.

Residual currents up to 20 A are measured across DC to 100 kHz with an accuracy of ±1 %. Two adjustable response values, a prewarning and an alarm, can be set from 30 mA to 3 A, and output relays K1 and K2 switch when a value is reached. The supply is DC 24 V (19.2…28.8 V). An RS-485 interface with Modbus RTU carries the data.

The CTBC cores come in internal diameters of 20, 35, 60, 120 and 210 mm (CTBC20 to CTBC210), and the CTBC…P versions add a full magnetic shield. Rated current depends on the core, for example 80 A for CTBC20P, 160 A for CTBC35P, 320 A for CTBC60P and 1000 A for CTBC210P. The series suits circuits with high load or inrush currents.

Thermal current Ith is 30 A, short-time thermal current 2.4 kA / 1 s, and dynamic current 6 kA / 40 ms and 50 kA / 50 ms. Operating temperature is -25…70 °C. The series follows IEC 60755, VDE 0664-400 and IEC 62020.

Modules mount on a DIN rail or with screws, and snap-on mounting exists for CTBC20(P) and CTBC35(P). Dimensions are 81 x 46 x 60 mm with CTBC20(P) and 302 x 67 x 113 mm with CTBC210(P); weight starts from 160 g. Parts ordered separately are plugged together and calibrated at commissioning. Accessories include a USB to RS-485 interface converter and a terminal block for RCMB301.

Technical specifications

Detection typeAC/DC sensitive, type B and B+
Frequency rangeDC…100 kHz
Maximum residual current20 A
Response values30 mA…3 A
Measurement accuracy±1 %
Supply voltageDC 24 V (19.2…28.8 V)
InterfaceRS-485, Modbus RTU
CTBC internal diameter20, 35, 60, 120, 210 mm
Rated current CTBC20P / CTBC35P / CTBC60P80 / 160 / 320 A
Thermal current Ith30 A
Short-time thermal current2.4 kA / 1 s
Dynamic current6 kA / 40 ms; 50 kA / 50 ms
Operating temperature-25…70 °C
Weightfrom 160 g
MountingDIN rail, screw mounting

Part numbers

Show all part numbers (18)

B74043100, B98120001, B98120002, B98120003, B98120004, B98120005, B98120006, B98120007, B98120020, B98120008, B98120021, B95012045, B74043124, B91080111, B91080112, B94053110, B94053111, B94053112

How it compares with similar models

ParameterLINETRAXX® RCMB300 residual current monitoring module for AC and DC, up to 20 ALINETRAXX® MRCDB300 AC/DC sensitive residual current monitoring module for MRCDLINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485LINETRAXX® CEP410R-2 residual current monitor for the central earthing point
Frequency rangeDC…100 kHzDC…100 kHzDC…100 kHz42…70 Hz
Supply voltageDC 24 V (19.2…28.8 V)DC 24 V (19.2…28.8 V)DC 24 V (19.2…28.8 V)DC 24 V; AC/DC 100…240 V
MountingDIN rail, screw mounting—DIN rail or screwDIN rail to IEC 60715

Request a price and lead time

LINETRAXX® RCMB300 residual current monitoring module for AC and DC, up to 20 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which residual currents does the RCMB300 monitor?

AC and DC residual currents up to 20 A across DC…100 kHz, with an accuracy of ±1 %. The prewarning and alarm values are adjustable from 30 mA to 3 A.

How do I choose the CTBC measuring current transformer?

By the internal diameter (20, 35, 60, 120 or 210 mm) that the monitored conductors must pass through, and by the rated current. The CTBC…P versions have a full magnetic shield.

Does the module have a data interface?

Yes, RS-485 with Modbus RTU. A USB to RS-485 interface converter, part number B95012045, is available for connection over USB.