LINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485
The LINETRAXX® RCMB330 measures residual currents of 10…500 mA from DC to 100 kHz with an integrated split-core transformer. RS-485 interface with Modbus RTU and two adjustable response values.
- Measuring range RMS
- 10…500 mA
- Frequency range
- DC…100 kHz
- Supply voltage
- DC 24 V (19.2…28.8 V)
- Power consumption
- ≤ 2.5 W
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Fault currents in earthed electrical systems are what the LINETRAXX® RCMB330 measures. The module is AC/DC sensitive and contains an integrated split-core measuring current transformer with a 25 mm internal diameter, so the conductor does not have to be cut.
Residual current IΔ is evaluated from 10 to 500 mA (RMS) across DC…100 kHz, with digital filters applied to the acquired value. Classification is Type B to IEC 62020-1 and Type B+ to VDE 0664-400. Two separately adjustable response values separate a prewarning from the main alarm.
Data leave the module over RS-485 using Modbus RTU at 1.2…57.6 kBit/s, with cable lengths of 0…1200 m. Supply is DC 24 V (19.2…28.8 V) at up to 2.5 W. Rated voltage is 800 V, overvoltage category III, pollution degree 2 and rated current In 100 A.
It mounts on a DIN rail or with screws via an adapter and measures 25 x 65.5 x 100.4 mm. Commissioning is for electrically skilled persons only. An RS-485/USB converter (B95012045) is available for connecting a PC. Standards: IEC 60755, VDE 0664-400, IEC 60664-1, IEC 60664-3, IEC 62020-1, DGUV Vorschrift 3.
Technical specifications
| Measuring range RMS | 10…500 mA |
|---|---|
| Frequency range | DC…100 kHz |
| Supply voltage | DC 24 V (19.2…28.8 V) |
| Power consumption | ≤ 2.5 W |
| Rated voltage | 800 V |
| Overvoltage category / pollution degree | III / 2 |
| Rated current In | 100 A |
| Measuring current transformer internal diameter | 25 mm |
| Classification | Type B (IEC 62020-1) |
| Interface / protocol | RS-485 / Modbus RTU |
| Baud rate | 1.2…57.6 kBit/s |
| Cable length | 0…1200 m |
| Mounting | DIN rail or screw |
| Dimensions | 25 x 65.5 x 100.4 mm |
Part numbers
Show all part numbers (1)
B74043160
How it compares with similar models
| Parameter | LINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485 | LINETRAXX® RCMB300 residual current monitoring module for AC and DC, up to 20 A | LINETRAXX® CTBS25 split-core type B current transformer for residual currents of 10…500 mA | LINETRAXX® RCMA420 Type B AC/DC residual current monitor, 10…500 mA |
|---|---|---|---|---|
| Frequency range | DC…100 kHz | DC…100 kHz | — | 0…2000 Hz |
| Power consumption | ≤ 2.5 W | — | ≤ 0.25 W typ. (2.5 W max.) | ≤ 6.5 VA |
| Dimensions | 25 x 65.5 x 100.4 mm | — | 65.5 x 100.4 x 25 mm | 93 x 90 x 70,5 mm |
Request a price and lead time
LINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What measuring range does the RCMB330 cover?
Residual currents of 10…500 mA (RMS) from DC to 100 kHz.
Which interface and line length are supported?
RS-485 with Modbus RTU at 1.2…57.6 kBit/s over cable lengths of 0…1200 m.
Must the conductor be disconnected for installation?
No. The integrated split-core transformer has a 25 mm internal diameter.