LINETRAXX® RCMS150 six-channel Type B residual current monitor, up to 500 mA

The LINETRAXX® RCMS150 series monitors six circuits with integrated current transformers in earthed AC/DC systems. Residual current up to 500 mA, load currents up to 32 A, RS-485 with BMS or Modbus RTU protocol.

Number of channels
6 (1 RMS and 1 DC each)
Measuring range
±500 mA
Frequency range
0…2000 Hz
Load current
32 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Six circuits at once are covered by the LINETRAXX® RCMS150 series, Type B residual current monitors with integrated measuring current transformers for earthed AC/DC systems (TN and TT). Each of the six channels (K1…6) has two measuring channels, one RMS and one DC, and load currents up to 32 A are permitted.

Residual currents up to 500 mA (range ±500 mA) are measured across DC 0…2 kHz. Every channel has two separately adjustable response values, prewarning IΔn1 and alarm IΔn2. IΔn2 RMS is set from 3…300 mA, IΔn2 DC from 3…300 mA, the ratio IΔn2 RMS / IΔn2 DC from 0.2…5, the prewarning from 50…100 % and the hysteresis from 10…25 %. Measured value resolution is 1 % of the set response value.

Three versions are listed: RCMS150 with BMS protocol (B94053025), RCMS150-01 with Modbus RTU (B94053026) and RCMS150-W-01 with Modbus RTU (B94053026W). The RS-485 interface uses terminals A/B, device addresses 2…90 and cable lengths up to 1200 m. Recommended cable is CAT6/CAT7 of at least AWG23 or J-Y(St)Y of at least 2 x 0.8, shield earthed on one side to PE, with an external 120 Ω (0.25 W) bus terminating resistor. A Condition Monitor with integrated gateway and an RS-485 repeater are options.

Nominal supply is DC 24 V ±20 % at under 4 W, rated insulation voltage 300 V, overvoltage category III. Dual plug-in push-wire terminals accept 0.2…1.5 mm² / AWG 24…16. Mounting is by screws to standard distribution panels of 12 TE (2 x M6, tightening torque 1.5 Nm) or on a DIN rail with the optional clip.

Technical specifications

Number of channels6 (1 RMS and 1 DC each)
Measuring range±500 mA
Frequency range0…2000 Hz
Load current32 A
IΔn2 RMS3…300 mA
IΔn2 DC3…300 mA
Prewarning IΔn1 RMS/DC50…100 %
Hysteresis10…25 %
Nominal supply voltage USDC 24 V ±20 %
Power consumption< 4 W
Rated insulation voltage300 V
Interface / protocolRS-485 / BMS or Modbus RTU
Cable length≤ 1200 m
Device address2…90

Part numbers

Show all part numbers (3)

B94053025 (BMS), B94053026 (Modbus RTU), B94053026W (W-01)

How it compares with similar models

ParameterLINETRAXX® RCMS150 six-channel Type B residual current monitor, up to 500 mALINETRAXX® RCMA420 Type B AC/DC residual current monitor, 10…500 mALINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485LINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 A
Frequency range0…2000 Hz0…2000 HzDC…100 kHz42…2000 Hz
Power consumption< 4 W≤ 6.5 VA≤ 2.5 W—
Rated insulation voltage300 V100 V (RCMA420-D-1) / 250 V (RCMA420-D-2)—100 V (RCM420-D-1); 250 V (RCM420-D-2)

Request a price and lead time

LINETRAXX® RCMS150 six-channel Type B residual current monitor, up to 500 mA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many channels does the RCMS150 have?

Six channels, each with two measuring channels: one RMS and one DC.

Which protocols does the series support?

The RCMS150 uses BMS, the RCMS150-01 and RCMS150-W-01 use Modbus RTU, all over RS-485.

What is the maximum load current?

The device is suitable for load currents up to 32 A.