International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DC

The LINETRAXX® RCMS490-L monitors residual currents on 12 measuring channels in earthed AC, DC and AC/DC systems (TN and TT). Each channel has its own alarm contact, and there are two alarm relays and a BMS bus for up to 90 devices.

Number of measuring channels
12
Response ranges
10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)
Supply voltage US (L-1)
DC 16…94 V / AC 16…72 V, 42…460 Hz
Supply voltage US (L-2)
DC 70…276 V / AC 70…276 V, 42…460 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Earthed AC, DC and AC/DC systems (TN and TT) with many feeders are the target of the LINETRAXX® RCMS490-L. It detects and evaluates fault, residual and operating currents, and is used for fire protection, plant protection, personnel protection, monitoring of flammable atmospheres, EMC monitoring of TN-S systems, overload monitoring of N conductors and monitoring of PE and equipotential bonding conductors.

Up to 12 measuring channels connect to measuring current transformers of Type A or Type B. The frequency response is adjustable between 0…2000 Hz and 42…2000 Hz. Response ranges are 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz) and 100 mA…125 A (42…2000 Hz). Harmonics, DC and THD are analysed, and measurement can be set to AC, pulsed DC or AC/DC sensitivity.

On the RCMS490-L each channel has an alarm contact of its own, in addition to two alarm relays with changeover contacts. The data logger holds 300 data records per channel and the history memory stamps entries with date and time. Up to 90 monitors can be linked on a BMS bus (RS-485).

The RCMS490-L-1 runs from DC 16…94 V / AC 16…72 V, 42…460 Hz and the RCMS490-L-2 from DC 70…276 V / AC 70…276 V, 42…460 Hz. Rated insulation voltage is 100 V or 250 V, overvoltage category III, and dimensions are 162 x 93 x 74 mm. Mounting is on a DIN rail to IEC 60715, with M4 screws, or in distribution panels to DIN 43871. Options include transformers CTBS25, CTUB100, CTAC…, WR…, WS…, WF…, MK2430 alarm indicators, the DI-1PSM RS-485 repeater (B95012044), mounting frame XM490 B990996 and clip XM420 B98060008.

Technical specifications

Number of measuring channels12
Response ranges10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)
Supply voltage US (L-1)DC 16…94 V / AC 16…72 V, 42…460 Hz
Supply voltage US (L-2)DC 70…276 V / AC 70…276 V, 42…460 Hz
Rated insulation voltage100 V; 250 V
Rated impulse voltage / pollution degree2.5 kV/3; 4 kV/3; 6 kV/3
Overvoltage categoryIII
Alarm relays2 changeover + one contact per channel
Electrical endurance10000 cycles
InterfaceRS-485, BMS bus
Dimensions162 x 93 x 74 mm

Part numbers

Show all part numbers (2)

B94053007, B94053008

How it compares with similar models

ParameterLINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DCLINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DCLINETRAXX® RCMA420 Type B AC/DC residual current monitor, 10…500 mALINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 A
Rated insulation voltage100 V; 250 V—100 V (RCMA420-D-1) / 250 V (RCMA420-D-2)100 V (RCM420-D-1); 250 V (RCM420-D-2)
Dimensions162 x 93 x 74 mm—93 x 90 x 70,5 mm93 x 90 x 74,5 mm

Request a price and lead time

LINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DC. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many channels does the RCMS490-L have?

12 measuring channels, each with its own alarm contact, plus two alarm relays with changeover contacts.

Which response ranges are available?

10 mA…10 A (0…2000 Hz), 6 mA…20 A and 100 mA…125 A (both 42…2000 Hz).

How many devices can share the bus?

Up to 90 devices on the BMS bus (RS-485).

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides