LINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 A
The LINETRAXX® RCM420 watches residual currents in earthed TN and TT systems and responds to AC and pulsed DC. Response range 10 mA…10 A, two adjustable response values, two alarm relays and an LC display.
- Response range IΔn
- 10 mA…10 A
- Frequency range
- 42…2000 Hz
- Supply voltage US (RCM420-D-1)
- DC 9,6…94 V / AC 16…72 V, 42…460 Hz
- Supply voltage US (RCM420-D-2)
- DC 70…300 V / AC 70…300 V, 42…460 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Fault and residual currents in earthed TN and TT power supplies are what the LINETRAXX® RCM420 monitors. As a Type A device to DIN EN 62020 it is sensitive to AC and pulsed DC. A fault triggers an alarm and the circuit is not disconnected. Single conductors such as PE can be monitored too, including conductors that are de-energised in normal operation.
Residual current is picked up by external measuring current transformers of the CTAC, WR or WS series. The response range IΔn is 10 mA…10 A over 42…2000 Hz. Two separately adjustable response values, IΔ1 and IΔ2, separate a prewarning from the main alarm, and delay times and a fault memory are selectable. An LC display shows the measured value, the connection to the transformer is monitored, there are two separate alarm relays and settings are password protected.
The RCM420-D-1 runs from DC 9,6…94 V / AC 16…72 V, 42…460 Hz, with a rated insulation voltage of 100 V and a rated impulse voltage of 2,5 kV. The RCM420-D-2 runs from DC 70…300 V / AC 70…300 V, 42…460 Hz, with 250 V insulation and 4 kV impulse voltage. Overvoltage category is III and pollution degree 3. Terminals are push-wire or screw-type, and Option W covers climatic conditions 3K23/3M12.
The unit clips onto a DIN rail (IEC 60715) or is screw mounted (2 x M4 with mounting clip B98060008); mounting frame XM420 is B990994. It measures 93 x 90 x 74,5 mm and weighs up to 150 g, with IP30 for internal components, IP20 for terminals and an operating temperature of -25…+55 ºC. Typical uses include socket-outlet circuits for equipment that runs unattended for long periods, alarm systems and safety devices, air conditioning, EDP systems, cooling equipment holding valuable frozen goods, canteen kitchens, trace heating and stray current monitoring.
Technical specifications
| Response range IΔn | 10 mA…10 A |
|---|---|
| Frequency range | 42…2000 Hz |
| Supply voltage US (RCM420-D-1) | DC 9,6…94 V / AC 16…72 V, 42…460 Hz |
| Supply voltage US (RCM420-D-2) | DC 70…300 V / AC 70…300 V, 42…460 Hz |
| Rated insulation voltage | 100 V (RCM420-D-1); 250 V (RCM420-D-2) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Rated impulse voltage | 2,5 kV (RCM420-D-1); 4 kV (RCM420-D-2) |
| Operating temperature | -25…+55 ºC |
| Protection class, internal components | IP30 |
| Protection class, terminals | IP20 |
| Weight | ≤ 150 g |
| Dimensions | 93 x 90 x 74,5 mm |
Part numbers
Show all part numbers (6)
B74014001, B94014001, B74014001W, B94014001W, B74014002, B94014002
How it compares with similar models
| Parameter | LINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 A | LINETRAXX® RCMA420 Type B AC/DC residual current monitor, 10…500 mA | ISOMETER® isoPV425 with AGH420 insulation monitoring device for AC/DC IT systems up to 690 V / 1000 V | LINETRAXX® RCMA423 Type B AC/DC residual current monitor, 30 mA…3 A |
|---|---|---|---|---|
| Response range IΔn | 10 mA…10 A | 10…500 mA | — | 30 mA…3 A |
| Rated insulation voltage | 100 V (RCM420-D-1); 250 V (RCM420-D-2) | 100 V (RCMA420-D-1) / 250 V (RCMA420-D-2) | 1000 V | 100 V (RCMA423-D-1), 250 V (RCMA423-D-2) |
| Rated impulse voltage | 2,5 kV (RCM420-D-1); 4 kV (RCM420-D-2) | 2.5 kV (RCMA420-D-1) / 4 kV (RCMA420-D-2) | 8 kV | 2.5 kV (RCMA423-D-1), 4 kV (RCMA423-D-2) |
| Dimensions | 93 x 90 x 74,5 mm | 93 x 90 x 70,5 mm | 36 x 93 x 90 mm | 93 x 70.5 x 36 mm |
Request a price and lead time
LINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which systems is the RCM420 intended for?
Earthed two, three or four conductor TN and TT systems. As a Type A device it responds to AC and pulsed DC.
Which supply versions exist?
The RCM420-D-1 runs from DC 9,6…94 V / AC 16…72 V and the RCM420-D-2 from DC 70…300 V / AC 70…300 V.
Which current transformers can be connected?
External measuring current transformers of the CTAC, WR or WS series.
Similar equipment from other manufacturers