International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® isoPV425 with AGH420 insulation monitoring device for AC/DC IT systems up to 690 V / 1000 V

Insulation monitoring device for unearthed AC/DC main circuits, aimed at photovoltaic systems up to AC 690 V / DC 1000 V. It adapts automatically to system leakage capacitance up to 1000 μF and offers response values of 1…500 kΩ. RS-485 interface with Modbus RTU and BMS.

Nominal system voltage Un
3(N)AC, AC, AC/DC 0…690 V or DC 0…1000 V
Supply voltage Us
DC 24…240 V, AC 100…240 V
Max. permissible system leakage capacitance
1000 μF
Response value ranges
1…500 kΩ (Alarm 1, Alarm 2)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Unearthed AC/DC main circuits (IT systems) with a nominal system voltage Un of 3(N)AC, AC, AC/DC 0…690 V or DC 0…1000 V are monitored for insulation resistance by the ISOMETER® isoPV425 with AGH420. Photovoltaic systems are its main application. The device adapts automatically to a system leakage capacitance of up to 1000 μF, measures the nominal system voltage (r.m.s.) and detects undervoltage and overvoltage.

The response values for Alarm 1 and Alarm 2 are selected in ranges of 1…500 kΩ. Alarms are signalled by LEDs, the display and alarm relays. The RS-485 interface carries Modbus RTU, and a BMS interface and isoData are also listed. Supply voltage Us is DC 24…240 V, AC 100…240 V.

Listed uses are solar systems with directly connected inverters, solar systems with high system leakage capacitances, solar systems with high but slow voltage fluctuations, and systems including switched-mode power supplies.

Rated impulse voltage is 8 kV, rated insulation voltage 1000 V, overvoltage category III and pollution degree 3. Measuring voltage Um is ±45 V, measuring current Im at RF, ZF = 0 Ω is ≤ 400 μA and internal resistance Ri, Zi is ≥ 120 kΩ. For UL 508, nominal system voltage Un is AC/DC 0…600 V. The frequency range of Un is DC, 1…460 Hz.

Ambient temperature during operation is −40…+70 °C. The degree of protection is IP30 for built-in components and IP20 for terminals. Weight is ≤ 150 g and overall dimensions are 36 x 93 x 90 mm. Mounting is on a DIN rail or by screws; cooling slots must be ventilated vertically, and for Un > 800 V the distance to adjacent devices is at least 30 mm.

The isoPV425-D4 with AGH420 comes with push-wire terminals (B71036303) or screw-type terminals (B91036303). Accessories: mounting clip B98060008 and mounting frame XM420 (B990994). Standards: IEC 60664-1, IEC 60664-3, IEC 61326-2-4, IEC 60721-3-3, IEC 60721-3-2, IEC 60721-3-1, IEC 60715, DIN EN 60529, UL 508, UL 2231.

Technical specifications

Nominal system voltage Un3(N)AC, AC, AC/DC 0…690 V or DC 0…1000 V
Supply voltage UsDC 24…240 V, AC 100…240 V
Max. permissible system leakage capacitance1000 μF
Response value ranges1…500 kΩ (Alarm 1, Alarm 2)
Rated impulse voltage8 kV
Rated insulation voltage1000 V
Overvoltage categoryIII
Pollution degree3
Measuring voltage Um±45 V
Measuring current Im at RF, ZF = 0 Ω≤ 400 μA
Internal resistance Ri, Zi≥ 120 kΩ
Frequency range of UnDC, 1…460 Hz
Ambient temperature during operation−40…+70 °C
Degree of protectionIP30 (built-in components), IP20 (terminals)
Weight≤ 150 g
Dimensions36 x 93 x 90 mm

Part numbers

Show all part numbers (4)

B71036303, B91036303, B98060008, B990994

How it compares with similar models

ParameterISOMETER® isoPV425 with AGH420 insulation monitoring device for AC/DC IT systems up to 690 V / 1000 VISOMETER® isoNAV685-D insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 VLINETRAXX® RCM420 Type A residual current monitor, 10 mA…10 AISOMETER® isoRW685W-D-B railway insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 V
Nominal system voltage Un3(N)AC, AC, AC/DC 0…690 V or DC 0…1000 VAC 0…690 V; 1…460 Hz / DC 0…1000 V—AC 0…690 V; DC 0…1000 V
Supply voltage UsDC 24…240 V, AC 100…240 VAC 24…240 V; 50…400 Hz / DC 24…240 V—AC 24…240 V; 50…400 Hz / DC 24…240 V
Rated impulse voltage8 kV8 kV2,5 kV (RCM420-D-1); 4 kV (RCM420-D-2)—
Weight≤ 150 g—≤ 150 g< 390 g
Dimensions36 x 93 x 90 mm108 x 93 x 110 mm93 x 90 x 74,5 mm—

Request a price and lead time

ISOMETER® isoPV425 with AGH420 insulation monitoring device for AC/DC IT systems up to 690 V / 1000 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage and leakage capacitance does the isoPV425 handle?

Up to AC 690 V or DC 1000 V, with a permissible system leakage capacitance of up to 1000 μF; the device adapts to it automatically.

What response values can be set?

Alarm 1 and Alarm 2 are selected in ranges of 1…500 kΩ.

Which data interface is provided?

RS-485 with Modbus RTU; a BMS interface and isoData are also listed.