International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® iso685 insulation monitoring device for IT systems, AC up to 690 V and DC up to 1000 V

Insulation monitoring device for AC IT systems of 0…690 V and DC IT systems of 0…1000 V. Response values 1 kΩ…10 MΩ, RS-485 and Ethernet interfaces, and Modbus TCP, Modbus RTU, BCOM, BS bus and isoData protocols. Available with display (D) or without (S).

Nominal system voltage Un
AC 0…690 V; 1…460 Hz / DC 0…1000 V
Supply voltage Us
AC 24…240 V; 50…400 Hz / DC 24…240 V
Response value Ran1 (ALARM 1)
1 kΩ … 10 MΩ
Response value Ran2 (ALARM 2)
1 kΩ … 10 MΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

AC IT systems with galvanically connected rectifiers and inverters, and DC IT systems, are the field of the ISOMETER® iso685, which monitors their insulation resistance. The nominal system voltage Un is AC 0…690 V, 1…460 Hz / DC 0…1000 V, and the supply voltage Us is AC 24…240 V, 50…400 Hz / DC 24…240 V.

The response values Ran1 (ALARM 1) and Ran2 (ALARM 2) are adjustable from 1 kΩ to 10 MΩ. The device includes a web server, RS-485 and Ethernet (RJ45) interfaces, a current output of 0(4)…20 mA, voltage outputs of 0…10 V and 2…10 V, three digital inputs and two digital outputs. It speaks Modbus TCP, Modbus RTU, BCOM, BS bus and isoData.

The versions differ in equipment. The iso685-D has an integrated graphic LC display with controls and cannot be combined with the FP200. The iso685-S has no display and is operated from the FP200 front panel (iso685-S + FP200). Versions marked W (iso685W-D, iso685W-S + FP200W) carry Option W for extreme climatic and mechanical conditions (3K23, 3M12).

Operating temperature is −25…+55 °C, or −40…+70 °C with Option W, at altitudes up to 3000 m AMSL. Weight is under 390 g. Mounting is on a DIN rail to IEC 60715 or by screws.

Order codes: B91067010, B91067010W, B91067210, B91067210W, B91067110, B91067110W. Accessories: a set of screw terminals B91067901, a set of push-wire terminals B91067902, and enclosure accessories (terminal cover, two mounting clips) B91067903.

Technical specifications

Nominal system voltage UnAC 0…690 V; 1…460 Hz / DC 0…1000 V
Supply voltage UsAC 24…240 V; 50…400 Hz / DC 24…240 V
Response value Ran1 (ALARM 1)1 kΩ … 10 MΩ
Response value Ran2 (ALARM 2)1 kΩ … 10 MΩ
InterfacesRS-485, Ethernet (RJ45)
Analogue outputsCurrent 0(4)…20 mA; voltage 0…10 V, 2…10 V
Digital inputs / outputs3 / 2
ProtocolsModbus TCP, Modbus RTU, BCOM, BS bus, isoData
Operating temperature−25…+55 °C
Operating temperature (Option W)−40…+70 °C
Altitude≤ 3000 m AMSL
Weight< 390 g
MountingDIN rail to IEC 60715, screws

Part numbers

Show all part numbers (9)

B91067010, B91067010W, B91067210, B91067210W, B91067110, B91067110W, B91067901, B91067902, B91067903

How it compares with similar models

ParameterISOMETER® iso685 insulation monitoring device for IT systems, AC up to 690 V and DC up to 1000 VISOMETER® iso685-…-B insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 VISOMETER® isoRW685W-D-B railway insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 VISOMETER® isoRW685W-D insulation monitoring device for rolling stock IT systems, AC 0…690 V, DC 0…1000 V
Nominal system voltage UnAC 0…690 V; 1…460 Hz / DC 0…1000 V—AC 0…690 V; DC 0…1000 VAC 0…690 V; DC 0…1000 V
Response value Ran1 (ALARM 1)1 kΩ … 10 MΩ—1 kΩ…10 MΩ1 kΩ…10 MΩ
Response value Ran2 (ALARM 2)1 kΩ … 10 MΩ—1 kΩ…10 MΩ1 kΩ…10 MΩ
InterfacesRS-485, Ethernet (RJ45)RS-485, EthernetRS-485, Ethernet, web serverRS-485, Ethernet, web server
ProtocolsModbus TCP, Modbus RTU, BCOM, BS bus, isoDataModbus TCP, Modbus RTU, BCOM, isoDataModbus RTU, Modbus TCPModbus RTU, Modbus TCP, BCOM, BS bus, isoData
Operating temperature−25…+55 °C−25…+55 °C−40…+70 °C−40…+70 °C

Request a price and lead time

ISOMETER® iso685 insulation monitoring device for IT systems, AC up to 690 V and DC up to 1000 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which systems is the iso685 intended for?

AC IT systems of 0…690 V (1…460 Hz) with galvanically connected rectifiers and inverters, and DC IT systems of 0…1000 V.

How do the iso685-D and iso685-S differ?

The iso685-D has an integrated graphic display; the iso685-S has none and is operated from the FP200 front panel.

What is Option W for?

Option W is for extreme climatic and mechanical conditions, with an operating temperature of −40…+70 °C.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides