ISOMETER® isoHR685W high-resistance insulation monitoring device up to 10 GΩ, IT systems AC 0…1000 V, DC 0…1300 V
The isoHR685W measures insulation resistance up to 10 GΩ and monitors long parallel cables in IT systems. Response values 1 kΩ…3 GΩ, integrated web server, Modbus TCP/RTU and ISOsync synchronisation.
- Nominal system voltage Un
- AC 0…1000 V; 0.1…460 Hz / DC 0…1300 V
- Supply voltage Us
- AC 24…240 V; 50…400 Hz / DC 24…240 V
- Response value Ran1 (ALARM 1)
- 1 kΩ…3 GΩ
- Response value Ran2 (ALARM 2)
- 1 kΩ…3 GΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The isoHR685W measures high insulation resistances of up to 10 GΩ and is used to monitor long parallel cables. It is an insulation monitoring device for AC, DC and AC/DC IT systems with a nominal system voltage of AC 0…1000 V; 0.1…460 Hz and DC 0…1300 V. The insulation resistance measuring range is 0.1 kΩ…10 GΩ.
The device uses profile-specific measuring methods (AMPPlus) and raises an alarm when the resistance falls below the preset response values Ran1 and Ran2, each adjustable from 1 kΩ to 3 GΩ. It adapts automatically to the system leakage capacitance, and the ISOsync function synchronises units in capacitively coupled IT systems.
An integrated web server and Modbus TCP and Modbus RTU communication provide access to the data. RS-485, Ethernet, BCOM and BS bus interfaces are fitted, together with 3 digital inputs, 2 digital outputs and 1 analogue output; the outputs are galvanically separated. The history memory has a real-time clock.
The version with an integrated display (isoHR685W-D-I-B) has a graphical LC display. The isoHR685W-S-I-B has a detached sensor without a display and is operated with the FP200W front panel. Remote diagnosis over the Internet is available through the manufacturer's service only.
Supply is AC 24…240 V; 50…400 Hz / DC 24…240 V and the operating temperature is −40…+70 °C. The enclosure measures 108 × 93 × 110 mm, weighs under 390 g and mounts on a DIN rail or with screws. Standards include IEC 61557-8, IEC 60664-1/-3, IEC 61010-1, IEC 61326-2-4 and IEC 60947-5-1, and the device carries CE and UKCA marks. Terminal kits B91067901 and B91067902, enclosure accessories B91067903 and the BB bus 6TE connector B98110001 are ordered separately.
Technical specifications
| Nominal system voltage Un | AC 0…1000 V; 0.1…460 Hz / DC 0…1300 V |
|---|---|
| Supply voltage Us | AC 24…240 V; 50…400 Hz / DC 24…240 V |
| Response value Ran1 (ALARM 1) | 1 kΩ…3 GΩ |
| Response value Ran2 (ALARM 2) | 1 kΩ…3 GΩ |
| Measuring range (insulation resistance) | 0.1 kΩ…10 GΩ |
| Inputs/outputs | 3 digital inputs, 2 digital outputs, 1 analogue output |
| Interfaces | RS-485, Ethernet, BCOM, BS bus |
| Protocols | Modbus RTU, Modbus TCP |
| Operating temperature | −40…+70 °C |
| Dimensions (W × H × D) | 108 × 93 × 110 mm |
| Weight | < 390 g |
Part numbers
Show all part numbers (6)
B91067025W, B91067225W, kits B91067901, B91067902, B91067903, B98110001
How it compares with similar models
| Parameter | ISOMETER® isoHR685W high-resistance insulation monitoring device up to 10 GΩ, IT systems AC 0…1000 V, DC 0…1300 V | ISOMETER® isoRW685W-D-B railway insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 V | ISOMETER® isoRW685W-D insulation monitoring device for rolling stock IT systems, AC 0…690 V, DC 0…1000 V | ISOMETER® iso685-…-B insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 V |
|---|---|---|---|---|
| Nominal system voltage Un | AC 0…1000 V; 0.1…460 Hz / DC 0…1300 V | AC 0…690 V; DC 0…1000 V | AC 0…690 V; DC 0…1000 V | — |
| Response value Ran1 (ALARM 1) | 1 kΩ…3 GΩ | 1 kΩ…10 MΩ | 1 kΩ…10 MΩ | — |
| Response value Ran2 (ALARM 2) | 1 kΩ…3 GΩ | 1 kΩ…10 MΩ | 1 kΩ…10 MΩ | — |
| Inputs/outputs | 3 digital inputs, 2 digital outputs, 1 analogue output | 3 digital inputs, 2 digital outputs, 1 analogue output | 3 DI, 2 DO, 1 AO | 3 digital inputs, 2 digital outputs, 1 analogue output |
| Interfaces | RS-485, Ethernet, BCOM, BS bus | RS-485, Ethernet, web server | RS-485, Ethernet, web server | RS-485, Ethernet |
| Protocols | Modbus RTU, Modbus TCP | Modbus RTU, Modbus TCP | Modbus RTU, Modbus TCP, BCOM, BS bus, isoData | Modbus TCP, Modbus RTU, BCOM, isoData |
Request a price and lead time
ISOMETER® isoHR685W high-resistance insulation monitoring device up to 10 GΩ, IT systems AC 0…1000 V, DC 0…1300 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What insulation resistance can the isoHR685W measure?
The measuring range is 0.1 kΩ…10 GΩ, and the response values Ran1 and Ran2 are adjustable within 1 kΩ…3 GΩ.
How do the D and S versions differ?
The D version has an integrated graphical LC display, while the S version has a detached sensor with no display and needs the FP200W front panel.
Which communication channels does it have?
RS-485, Ethernet, BCOM and BS bus carrying Modbus RTU and Modbus TCP, plus an integrated web server.