ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V
Insulation monitoring device for large-scale photovoltaic systems built as IT systems, up to AC 1000 V / DC 1500 V. Response values 200 Ω…1 MΩ and system leakage capacitance up to 2000 μF. The isoPV1685P version includes a locating current injector of up to 50 mA.
- Nominal system voltage Un
- AC 0…1000 V, DC 0…1500 V
- Supply voltage Us
- DC 18…30 V
- Response value Ran1 (Alarm 1)
- 200 Ω…1 MΩ
- Response value Ran2 (Alarm 2)
- 200 Ω…1 MΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Insulation resistance in large-scale photovoltaic systems operated as IT systems, with a nominal voltage of AC 0…1000 V or DC 0…1500 V, is what the ISOMETER® isoPV1685RTU/isoPV1685P monitors. Its measuring method is intended for slow voltage fluctuations such as those caused by MPP tracking. The device adapts automatically to high system leakage capacitances, with a permissible capacitance Ce of up to 2000 μF.
The response values Ran1 (Alarm 1) and Ran2 (Alarm 2) are each adjustable within 200 Ω…1 MΩ. Supply voltage Us is DC 18…30 V and power consumption is ≤ 7 W. Data are available on an RS-485 interface (BMS bus or Modbus RTU) and on CAN.
There are two versions. The isoPV1685RTU-425 (B91065603) has no integrated locating current injector, and its RS-485 interface is switched between BMS bus and Modbus with a DIP switch. The isoPV1685P-425 (B91065604) has an integrated locating current injector of up to 50 mA for fault localisation, and its RS-485 interface works with the BMS bus.
Rated voltage is DC 1500 V, rated impulse voltage 10 kV, pollution degree 2 and nominal frequency 50/60 Hz ±1 Hz. The degree of protection is IP30, weight is ≤ 1300 g, and mounting is on a DIN rail. Standards: DIN EN 60664-1 (VDE 0110-1), DIN EN 61557-8 (VDE 0413-8), IEC 60730-1, IEC 61326-2-4, IEC 61557-8, UL 1998 (software), UL 508, IEC 60721-3-3, IEC 60721-3-2, IEC 60721-3-1 and IEC 60947-5-1.
Intended use: large PV systems designed as IT systems up to AC 1000 V / DC 1500 V.
Technical specifications
| Nominal system voltage Un | AC 0…1000 V, DC 0…1500 V |
|---|---|
| Supply voltage Us | DC 18…30 V |
| Response value Ran1 (Alarm 1) | 200 Ω…1 MΩ |
| Response value Ran2 (Alarm 2) | 200 Ω…1 MΩ |
| Permissible system leakage capacitance Ce | ≤ 2000 μF |
| Rated voltage | DC 1500 V |
| Rated impulse voltage | 10 kV |
| Pollution degree | 2 |
| Nominal frequency | 50/60 Hz ±1 Hz |
| Power consumption | ≤ 7 W |
| Weight | ≤ 1300 g |
| Degree of protection | IP30 |
| Interfaces | RS-485, CAN |
| Protocols | BMS, Modbus RTU |
Part numbers
Show all part numbers (2)
B91065603 (isoPV1685RTU-425), B91065604 (isoPV1685P-425)
How it compares with similar models
| Parameter | ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V | ISOMETER® isoRW685W-D-B railway insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 V | ISOMETER® isoRW685W-D insulation monitoring device for rolling stock IT systems, AC 0…690 V, DC 0…1000 V | ISOMETER® isoHR685W high-resistance insulation monitoring device up to 10 GΩ, IT systems AC 0…1000 V, DC 0…1300 V |
|---|---|---|---|---|
| Nominal system voltage Un | AC 0…1000 V, DC 0…1500 V | AC 0…690 V; DC 0…1000 V | AC 0…690 V; DC 0…1000 V | AC 0…1000 V; 0.1…460 Hz / DC 0…1300 V |
| Supply voltage Us | DC 18…30 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | AC 24…240 V; 50…400 Hz / DC 24…240 V |
| Weight | ≤ 1300 g | < 390 g | < 390 g | < 390 g |
| Interfaces | RS-485, CAN | RS-485, Ethernet, web server | RS-485, Ethernet, web server | RS-485, Ethernet, BCOM, BS bus |
| Protocols | BMS, Modbus RTU | Modbus RTU, Modbus TCP | Modbus RTU, Modbus TCP, BCOM, BS bus, isoData | Modbus RTU, Modbus TCP |
Request a price and lead time
ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Up to what voltage can the isoPV1685 be used?
Up to AC 1000 V or DC 1500 V in large PV systems designed as IT systems.
What system leakage capacitance is permitted?
Up to 2000 μF; the device adapts to it automatically.
What separates the isoPV1685RTU from the isoPV1685P?
The P version has an integrated locating current injector of up to 50 mA, while the RTU has an RS-485 interface switchable between BMS bus and Modbus.