International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V

Insulation monitoring device for large-scale photovoltaic systems built as IT systems, up to AC 1000 V / DC 1500 V. Response values 200 Ω…1 MΩ and system leakage capacitance up to 2000 μF. The isoPV1685P version includes a locating current injector of up to 50 mA.

Nominal system voltage Un
AC 0…1000 V, DC 0…1500 V
Supply voltage Us
DC 18…30 V
Response value Ran1 (Alarm 1)
200 Ω…1 MΩ
Response value Ran2 (Alarm 2)
200 Ω…1 MΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Insulation resistance in large-scale photovoltaic systems operated as IT systems, with a nominal voltage of AC 0…1000 V or DC 0…1500 V, is what the ISOMETER® isoPV1685RTU/isoPV1685P monitors. Its measuring method is intended for slow voltage fluctuations such as those caused by MPP tracking. The device adapts automatically to high system leakage capacitances, with a permissible capacitance Ce of up to 2000 μF.

The response values Ran1 (Alarm 1) and Ran2 (Alarm 2) are each adjustable within 200 Ω…1 MΩ. Supply voltage Us is DC 18…30 V and power consumption is ≤ 7 W. Data are available on an RS-485 interface (BMS bus or Modbus RTU) and on CAN.

There are two versions. The isoPV1685RTU-425 (B91065603) has no integrated locating current injector, and its RS-485 interface is switched between BMS bus and Modbus with a DIP switch. The isoPV1685P-425 (B91065604) has an integrated locating current injector of up to 50 mA for fault localisation, and its RS-485 interface works with the BMS bus.

Rated voltage is DC 1500 V, rated impulse voltage 10 kV, pollution degree 2 and nominal frequency 50/60 Hz ±1 Hz. The degree of protection is IP30, weight is ≤ 1300 g, and mounting is on a DIN rail. Standards: DIN EN 60664-1 (VDE 0110-1), DIN EN 61557-8 (VDE 0413-8), IEC 60730-1, IEC 61326-2-4, IEC 61557-8, UL 1998 (software), UL 508, IEC 60721-3-3, IEC 60721-3-2, IEC 60721-3-1 and IEC 60947-5-1.

Intended use: large PV systems designed as IT systems up to AC 1000 V / DC 1500 V.

Technical specifications

Nominal system voltage UnAC 0…1000 V, DC 0…1500 V
Supply voltage UsDC 18…30 V
Response value Ran1 (Alarm 1)200 Ω…1 MΩ
Response value Ran2 (Alarm 2)200 Ω…1 MΩ
Permissible system leakage capacitance Ce≤ 2000 μF
Rated voltageDC 1500 V
Rated impulse voltage10 kV
Pollution degree2
Nominal frequency50/60 Hz ±1 Hz
Power consumption≤ 7 W
Weight≤ 1300 g
Degree of protectionIP30
InterfacesRS-485, CAN
ProtocolsBMS, Modbus RTU

Part numbers

Show all part numbers (2)

B91065603 (isoPV1685RTU-425), B91065604 (isoPV1685P-425)

How it compares with similar models

ParameterISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 VISOMETER® isoRW685W-D-B railway insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 VISOMETER® isoRW685W-D insulation monitoring device for rolling stock IT systems, AC 0…690 V, DC 0…1000 VISOMETER® isoHR685W high-resistance insulation monitoring device up to 10 GΩ, IT systems AC 0…1000 V, DC 0…1300 V
Nominal system voltage UnAC 0…1000 V, DC 0…1500 VAC 0…690 V; DC 0…1000 VAC 0…690 V; DC 0…1000 VAC 0…1000 V; 0.1…460 Hz / DC 0…1300 V
Supply voltage UsDC 18…30 VAC 24…240 V; 50…400 Hz / DC 24…240 VAC 24…240 V; 50…400 Hz / DC 24…240 VAC 24…240 V; 50…400 Hz / DC 24…240 V
Weight≤ 1300 g< 390 g< 390 g< 390 g
InterfacesRS-485, CANRS-485, Ethernet, web serverRS-485, Ethernet, web serverRS-485, Ethernet, BCOM, BS bus
ProtocolsBMS, Modbus RTUModbus RTU, Modbus TCPModbus RTU, Modbus TCP, BCOM, BS bus, isoDataModbus RTU, Modbus TCP

Request a price and lead time

ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Up to what voltage can the isoPV1685 be used?

Up to AC 1000 V or DC 1500 V in large PV systems designed as IT systems.

What system leakage capacitance is permitted?

Up to 2000 μF; the device adapts to it automatically.

What separates the isoPV1685RTU from the isoPV1685P?

The P version has an integrated locating current injector of up to 50 mA, while the RTU has an RS-485 interface switchable between BMS bus and Modbus.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides