International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V

The isoPV1685DP monitors insulation in unearthed IT systems of large photovoltaic plants and battery energy storage systems. Response values 200 Ω…200 kΩ, leakage capacitance 0...4000 µF, RS-485 with Modbus RTU and BMS.

Purpose
Insulation monitoring of IT systems in PV plants and BESS
Nominal voltage Un
AC 0…1000 V; DC 0…1500 V
Supply voltage Us
DC 18…30 V
Response value Ran
200 Ω…200 kΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Large photovoltaic plants and battery energy storage systems (BESS) run as unearthed IT systems, and the isoPV1685DP watches their insulation resistance. The nominal system voltage is AC 0…1000 V, DC 0…1500 V. The isoPV1685DP-425 version is supplied with DC 24 V ±25%.

The measuring method is adapted to the slow voltage swings caused by MPP tracking. The device adjusts itself to a system leakage capacitance anywhere within 0...4000 µF, and its response values lie between 200 Ω and 200 kΩ. For fault location, an integrated injector sends locating current pulses of up to 50 mA.

Data leaves the device over RS-485 using Modbus RTU or BMS, and settings can be changed remotely through a COMTRAXX® gateway. The unit has an integrated display, three changeover contacts and freely programmable digital inputs. Separate device profiles exist for PV and for BESS. A self-test runs after connection to the supply and during operation.

The display measures 40 × 40 mm, the degree of protection is IP30 and the ambient temperature range is −40…+70 °C. Weight is up to 1600 g and power consumption ≤9 W. The device is mounted on a DIN rail inside a control cabinet, so its messages must still be audible or visible outside the cabinet. It complies with IEC 61557-8 and IEC 61557-9 and carries CE and UKCA marks.

Technical specifications

PurposeInsulation monitoring of IT systems in PV plants and BESS
Nominal voltage UnAC 0…1000 V; DC 0…1500 V
Supply voltage UsDC 18…30 V
Response value Ran200 Ω…200 kΩ
System leakage capacitance Ce0...4000 µF
Locating current ILDC ≤ 50 mA
Power consumption≤9 W
Weight≤1600 g
Display size40 × 40 mm
Degree of protectionIP30
Ambient temperature−40…+70 °C
InterfaceRS-485, Modbus RTU, BMS

Part numbers

Show all part numbers (1)

B91065808

How it compares with similar models

ParameterISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 VISOMETER® isoHR1685DW-925 insulation monitor for elevating work platforms, AC 0…1000 V / DC 0…1500 VISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 VISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V
PurposeInsulation monitoring of IT systems in PV plants and BESSInsulation monitoring of mobile insulated elevating work platforms—Insulation monitoring of unearthed IT systems
Weight≤1600 g—≤ 1300 g≤ 510 g

Request a price and lead time

ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage and leakage capacitance does the isoPV1685DP cover?

Systems of AC 0…1000 V / DC 0…1500 V with a leakage capacitance of 0...4000 µF.

How are data and settings handled?

Data goes over RS-485 with Modbus RTU or BMS, and settings can be changed remotely through a COMTRAXX® gateway.

What locating current does the built-in injector supply?

DC current of up to 50 mA.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides