ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V
The isoPV1685DP monitors insulation in unearthed IT systems of large photovoltaic plants and battery energy storage systems. Response values 200 Ω…200 kΩ, leakage capacitance 0...4000 µF, RS-485 with Modbus RTU and BMS.
- Purpose
- Insulation monitoring of IT systems in PV plants and BESS
- Nominal voltage Un
- AC 0…1000 V; DC 0…1500 V
- Supply voltage Us
- DC 18…30 V
- Response value Ran
- 200 Ω…200 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Large photovoltaic plants and battery energy storage systems (BESS) run as unearthed IT systems, and the isoPV1685DP watches their insulation resistance. The nominal system voltage is AC 0…1000 V, DC 0…1500 V. The isoPV1685DP-425 version is supplied with DC 24 V ±25%.
The measuring method is adapted to the slow voltage swings caused by MPP tracking. The device adjusts itself to a system leakage capacitance anywhere within 0...4000 µF, and its response values lie between 200 Ω and 200 kΩ. For fault location, an integrated injector sends locating current pulses of up to 50 mA.
Data leaves the device over RS-485 using Modbus RTU or BMS, and settings can be changed remotely through a COMTRAXX® gateway. The unit has an integrated display, three changeover contacts and freely programmable digital inputs. Separate device profiles exist for PV and for BESS. A self-test runs after connection to the supply and during operation.
The display measures 40 × 40 mm, the degree of protection is IP30 and the ambient temperature range is −40…+70 °C. Weight is up to 1600 g and power consumption ≤9 W. The device is mounted on a DIN rail inside a control cabinet, so its messages must still be audible or visible outside the cabinet. It complies with IEC 61557-8 and IEC 61557-9 and carries CE and UKCA marks.
Technical specifications
| Purpose | Insulation monitoring of IT systems in PV plants and BESS |
|---|---|
| Nominal voltage Un | AC 0…1000 V; DC 0…1500 V |
| Supply voltage Us | DC 18…30 V |
| Response value Ran | 200 Ω…200 kΩ |
| System leakage capacitance Ce | 0...4000 µF |
| Locating current IL | DC ≤ 50 mA |
| Power consumption | ≤9 W |
| Weight | ≤1600 g |
| Display size | 40 × 40 mm |
| Degree of protection | IP30 |
| Ambient temperature | −40…+70 °C |
| Interface | RS-485, Modbus RTU, BMS |
Part numbers
Show all part numbers (1)
B91065808
How it compares with similar models
| Parameter | ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V | ISOMETER® isoHR1685DW-925 insulation monitor for elevating work platforms, AC 0…1000 V / DC 0…1500 V | ISOMETER® isoPV1685RTU/isoPV1685P insulation monitoring for PV systems up to AC 1000 V / DC 1500 V | ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V |
|---|---|---|---|---|
| Purpose | Insulation monitoring of IT systems in PV plants and BESS | Insulation monitoring of mobile insulated elevating work platforms | — | Insulation monitoring of unearthed IT systems |
| Weight | ≤1600 g | — | ≤ 1300 g | ≤ 510 g |
Request a price and lead time
ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltage and leakage capacitance does the isoPV1685DP cover?
Systems of AC 0…1000 V / DC 0…1500 V with a leakage capacitance of 0...4000 µF.
How are data and settings handled?
Data goes over RS-485 with Modbus RTU or BMS, and settings can be changed remotely through a COMTRAXX® gateway.
What locating current does the built-in injector supply?
DC current of up to 50 mA.