ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V
The isoLR275 with coupling device AGH-LR monitors unearthed AC, AC/DC and DC IT systems. Two adjustable response ranges of 0.2…100 kΩ, leakage capacitance up to 500 µF, 0(4)…20 mA output and RS-485.
- Purpose
- Insulation monitoring of unearthed IT systems
- Nominal system voltage
- AC 0…793 V / DC 0…1100 V
- Supply voltage (isoLR275-327 + AGH-LR-3)
- AC 19.2…55 V / DC 19.2…72 V
- Supply voltage (isoLR275-335 + AGH-LR)
- AC 88…264 V / DC 77…286 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The isoLR275 and its coupling device AGH-LR monitor insulation in unearthed AC, AC/DC and DC IT systems with a nominal voltage of AC 0…793 V / DC 0…1100 V. Typical uses are AC, DC and AC/DC main circuits, IT systems with directly connected inverters, high system leakage capacitance, high but slow voltage fluctuations, switched-mode power supplies and coupled IT systems.
The patented AMPPlus method superimposes a pulsating AC measuring voltage on the system. The device adapts itself to the leakage capacitance present and calculates the insulation resistance from it. The maximum permissible leakage capacitance is 500 µF. Alarm 1 and Alarm 2 have separately adjustable response ranges of 0.2 kΩ…100 kΩ.
A history memory with real-time clock stores events. The unit provides an RS-485 interface (BMS), a 0(4)…20 mA current output and two changeover contacts, and it can disconnect itself internally in interconnected systems.
The isoLR275-327 with AGH-LR-3 takes AC 19.2…55 V / DC 19.2…72 V, while the isoLR275-335 with AGH-LR takes AC 88…264 V / DC 77…286 V. Operating temperature is −25…+65 °C, protection IP30 and weight up to 510 g.
Mounting is on a DIN rail (IEC 60715). For UL and CSA applications, 5 A fuses are mandatory. The device complies with IEC 61557-8 (VDE 0413-8) and holds VDE, UL and CSA approvals.
Technical specifications
| Purpose | Insulation monitoring of unearthed IT systems |
|---|---|
| Nominal system voltage | AC 0…793 V / DC 0…1100 V |
| Supply voltage (isoLR275-327 + AGH-LR-3) | AC 19.2…55 V / DC 19.2…72 V |
| Supply voltage (isoLR275-335 + AGH-LR) | AC 88…264 V / DC 77…286 V |
| Response value | 0.2 kΩ…100 kΩ |
| Maximum leakage capacitance | 500 µF |
| Operating temperature | -25…+65 °C |
| Degree of protection | IP30 |
| Mounting | DIN rail |
| Weight | ≤ 510 g |
| Interface and output | RS-485 (BMS), 0(4)…20 mA |
Part numbers
Show all part numbers (4)
B91065702W, B91065700W, B98039022W, B91065703W
How it compares with similar models
| Parameter | ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V | ISOMETER® isoPV with AGH-PV insulation monitor for PV, up to AC 793 V / DC 1100 V | ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V | ISOMETER® isoMED527 insulation monitor for medical IT systems, AC 100…240 V, NFC and RS-485 |
|---|---|---|---|---|
| Purpose | Insulation monitoring of unearthed IT systems | Insulation monitoring of IT systems in PV plants | Insulation monitoring of unearthed IT systems | Insulation monitoring of medical IT systems |
| Operating temperature | -25…+65 °C | -25…+65 °C | — | -25…+55 °C |
| Degree of protection | IP30 | — | IP30 | IP20 |
| Weight | ≤ 510 g | — | ≤ 1600 g | ≤ 130 g |
Request a price and lead time
ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What leakage capacitance can the isoLR275 handle?
The maximum permissible system leakage capacitance is 500 µF.
Which supply voltage versions exist?
The isoLR275-327 with AGH-LR-3 for AC 19.2…55 V / DC 19.2…72 V and the isoLR275-335 with AGH-LR for AC 88…264 V / DC 77…286 V.
What applies to UL and CSA installations?
5 A fuses are mandatory for these applications.