ISOMETER® isoPV with AGH-PV insulation monitor for PV, up to AC 793 V / DC 1100 V
The isoPV with coupling device AGH-PV monitors insulation in unearthed AC, AC/DC and DC IT systems of photovoltaic plants. Two response values 0.2…100 kΩ, leakage capacitance up to 2000 µF, 0(4)…20 mA output, RS-485 (BMS).
- Purpose
- Insulation monitoring of IT systems in PV plants
- Nominal system voltage Un
- AC 0…793 V / DC 0…1100 V
- Supply voltage Us (isoPV-327)
- AC 19.2…55 V / DC 19.2…72 V
- Supply voltage Us (isoPV-335)
- AC 88…264 V / DC 77…286 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The isoPV and its coupling device AGH-PV form an insulation monitoring set for unearthed AC, AC/DC and DC IT systems in photovoltaic plants, up to AC 793 V / DC 1100 V. Typical sites are solar systems with directly connected inverters, high system leakage capacitance, high but slow voltage fluctuations or switched-mode power supplies, and coupled IT systems.
Measurement uses the patented AMPPlus method. The device adapts itself to a leakage capacitance of up to 2000 µF and to slow voltage fluctuations. Response values Ran1 and Ran2 are set separately between 0.2 and 100 kΩ, and alarms go to two potential-free changeover contacts.
A two-line LC display shows the status and an automatic self-test checks the device. Data goes over RS-485 using the BMS protocol, and a 0(4)…20 mA current output is provided. An external kΩ measuring instrument is available as an option.
The isoPV-327 is supplied with AC 19.2…55 V / DC 19.2…72 V, and the isoPV-335 with AC 88…264 V / DC 77…286 V. Frequency fn is DC, 10…460 Hz. Operating temperature is −25…+65 °C, enclosure protection IP30 and terminals IP20. The isoPV weighs up to 510 g and the AGH-PV up to 230 g.
Mounting is on a DIN rail or by screws, using a screw mounting kit. The set complies with IEC 61557-8 and IEC 60664-1 and holds UL approval (UL 508).
Technical specifications
| Purpose | Insulation monitoring of IT systems in PV plants |
|---|---|
| Nominal system voltage Un | AC 0…793 V / DC 0…1100 V |
| Supply voltage Us (isoPV-327) | AC 19.2…55 V / DC 19.2…72 V |
| Supply voltage Us (isoPV-335) | AC 88…264 V / DC 77…286 V |
| Response value Ran1, Ran2 | 0.2…100 kΩ |
| System leakage capacitance Ce | ≤ 2000 µF |
| Frequency fn | DC, 10…460 Hz |
| Operating temperature | -25…+65 °C |
| Enclosure protection | IP30 |
| Terminal protection | IP20 |
| Weight isoPV | ≤ 510 g |
| Weight AGH-PV | ≤ 230 g |
| Interface and output | RS-485 (BMS), 0(4)…20 mA |
Part numbers
Show all part numbers (5)
B91065132W, B91065130W, B98039020W, B91065133W, B91065131W
Request a price and lead time
ISOMETER® isoPV with AGH-PV insulation monitor for PV, up to AC 793 V / DC 1100 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What leakage capacitance can the isoPV with AGH-PV handle?
A system leakage capacitance of up to 2000 µF.
How do the isoPV-327 and isoPV-335 differ?
In supply voltage: the isoPV-327 runs on AC 19.2…55 V / DC 19.2…72 V, the isoPV-335 on AC 88…264 V / DC 77…286 V.
Which interfaces and outputs are provided?
An RS-485 interface with the BMS protocol, a 0(4)…20 mA current output and two potential-free changeover contacts.