ISOMETER® IR425-D4 insulation monitor for AC/DC IT systems 0…300 V, response values 1…200 kΩ

The IR425-D4 monitors insulation in unearthed AC/DC control circuits (IT systems) of 0…300 V. Two separately set response values of 1…200 kΩ, a multi-functional LC display, two alarm relays and a 36 mm enclosure.

Purpose
Insulation monitoring of AC/DC control circuits (IT systems)
Nominal system voltage Un
0…300 V
Nominal frequency fn
15…460 Hz
Supply voltage Us (IR425-D4-1, IR425-D4W-1)
DC 9.6…94 V / AC 16…72 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The IR425-D4 checks the insulation resistance of unearthed AC/DC control and auxiliary circuits (IT systems) with a nominal voltage of 0…300 V and a frequency of 15…460 Hz. Uses include control circuits to DIN EN 60204-1, auxiliary circuits to DIN VDE 0100-725, mechanical engineering, power plants, lifts, automation systems and small AC/DC IT systems such as lighting.

It works on the AMP measuring principle, superimposing a pulsating measuring voltage on the system. Response values Ran1 (ALARM 1) and Ran2 (ALARM 2) are set separately within 1…200 kΩ, one serving as prewarning and the other as alarm. The relays can work as N/O or N/C, and fault memory and an adjustable response delay are available.

The front has a multi-functional LC display, and two separate alarm relays are fitted, together with monitoring of the system-to-earth connection. The two-module enclosure is 36 mm wide, measures 93 × 74.5 × 70.5 mm and weighs approximately 150 g.

The -1 version is supplied with DC 9.6…94 V / AC 16…72 V and the -2 version with AC 70…300 V / DC 70…300 V, at 15…460 Hz and ≤ 4 VA. System leakage capacitance must stay below 20 µF. Rated insulation voltage is 250 V, rated impulse voltage 4 kV, pollution degree 3, and operating temperature −25…+55 °C. The D4W types are also made in -1 and -2 variants.

Terminals are push-wire or screw-type. The device mounts on a DIN rail or with screws through a mounting clip, and the mounting frame XM420 is offered separately. It complies with IEC 61557-8, IEC 60204-1 and IEC 60664-1 and carries CE and UKCA marks.

Technical specifications

PurposeInsulation monitoring of AC/DC control circuits (IT systems)
Nominal system voltage Un0…300 V
Nominal frequency fn15…460 Hz
Supply voltage Us (IR425-D4-1, IR425-D4W-1)DC 9.6…94 V / AC 16…72 V
Supply voltage Us (IR425-D4-2, IR425-D4W-2)AC 70…300 V / DC 70…300 V
Power consumption≤ 4 VA
Response value Ran1 (ALARM 1)1…200 kΩ
Response value Ran2 (ALARM 2)1…200 kΩ
System leakage capacitance Ce< 20 µF
Rated insulation voltage250 V
Rated impulse voltage / pollution degree4 kV / 3
Operating temperature-25…+55 °C
Weightapprox. 150 g
Dimensions93 × 74.5 × 70.5 mm

Part numbers

Show all part numbers (8)

B71036403, B91036403, B71036402, B91036402, B71036403W, B91036403W, B71036402W, B91036402W

How it compares with similar models

ParameterISOMETER® IR425-D4 insulation monitor for AC/DC IT systems 0…300 V, response values 1…200 kΩISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 VISOMETER® IR420-D4 insulation monitoring device for AC IT control circuits, 0…300 VISOMETER® isoMED427 insulation monitor for medical IT systems, AC 70…264 V
Nominal system voltage Un0…300 VAC 0…300 VAC 0…300 V—
Nominal frequency fn15…460 Hz30…460 Hz42…460 Hz—
Power consumption≤ 4 VA—≤ 4 VA≤ 3 W
Operating temperature-25…+55 °C-25…+55 °C; option W -40…+70 °C-25…+55 °C—
Weightapprox. 150 g≤ 150 g≤ 150 g—
Dimensions93 × 74.5 × 70.5 mm93 x 74.5 x 45 mm93 x 74,5 x 45 mm93 × 70.5 × 36 mm

Request a price and lead time

ISOMETER® IR425-D4 insulation monitor for AC/DC IT systems 0…300 V, response values 1…200 kΩ. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What system voltage and frequency does the IR425-D4 cover?

A nominal voltage of 0…300 V and a frequency of 15…460 Hz.

How do the -1 and -2 versions differ?

In supply voltage: the -1 runs on DC 9.6…94 V / AC 16…72 V, the -2 on AC 70…300 V / DC 70…300 V.

Which response values can be set?

Two separate values, Ran1 and Ran2, each within 1…200 kΩ.