ISOMETER® IR420-D4 insulation monitoring device for AC IT control circuits, 0…300 V
The ISOMETER® IR420-D4 watches the insulation resistance of unearthed AC control circuits (IT systems) up to AC 0…300 V. It has two separately adjustable response values of 1…200 kΩ, two alarm relays and a multi-functional LC display.
- Nominal system voltage Un
- AC 0…300 V
- Nominal frequency fn
- 42…460 Hz
- Supply voltage Us (IR420-D4-1)
- DC 9,6…94 V / AC 16…72 V
- Supply voltage Us (IR420-D4-2)
- AC/DC 70…300 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The IR420-D4 is built for unearthed AC control circuits (IT systems) with a nominal system voltage of AC 0…300 V and a frequency of 42…460 Hz. Typical uses are industrial control circuits, mechanical engineering, power plants, elevators and automation systems, AC auxiliary circuits to DIN VDE 0100-725, and smaller AC IT systems such as lighting installations and mobile generators.
It measures by superimposing a DC voltage on the system: measuring voltage ±12 V, measuring current up to 200 µA, permissible system leakage capacitance up to 20 μF. DC components in the monitored system, for example switched-mode power supplies or solenoid valves, can affect the display and operating characteristics, because the readings and response values apply to pure AC systems. An external supply voltage allows de-energised systems to be monitored as well.
The measured insulation resistance is shown on the LC display. When it falls below a preset response value, the response delay ton (0…99 s) starts; once it has elapsed, relays K1/K2 switch and LEDs AL1/AL2 light. Two separate values separate a pre-warning from an alarm. The relays return to their initial position when the release value (response value plus hysteresis) is exceeded. With the fault memory enabled they stay in the alarm state until the reset button is pressed or the supply is switched off. N/O or N/C operation is selectable.
Connections to the system (L1/L2) and to earth (E/KE) are checked automatically every 24 h, on the test button and at power-up. If a lead breaks, relay K2 switches, the ON/AL1/AL2 LEDs flash and the display shows E.02 (fault in the leads to the system) or E.01 (leads to PE). After first switch-on the Preset function measures the nominal system voltage and sets the basic parameters. The device monitors itself and signals an alarm on internal faults.
IR420-D4-1 takes DC 9,6…94 V / AC 16…72 V as supply, IR420-D4-2 takes AC/DC 70…300 V. The two-module enclosure (36 mm) mounts on a DIN rail or with screws using clip B98060008; mounting frame XM420 (B990994) is available. Terminals are push-wire, two per connection. The device complies with IEC 61557-8, EN 61557-8, ASTM F 1207M-96 (2007) and is RoHS compliant.
Technical specifications
| Nominal system voltage Un | AC 0…300 V |
|---|---|
| Nominal frequency fn | 42…460 Hz |
| Supply voltage Us (IR420-D4-1) | DC 9,6…94 V / AC 16…72 V |
| Supply voltage Us (IR420-D4-2) | AC/DC 70…300 V |
| Power consumption | ≤ 4 VA |
| Response values Ran1, Ran2 | 1…200 kΩ |
| Response time tan | ≤1 s |
| Start-up delay | 0…10 s |
| Response delay ton | 0…99 s |
| Measuring voltage Um | ±12 V |
| Measuring current Im | ≤ 200 µA |
| Permissible system leakage capacitance Ce | ≤ 20 μF |
| Display range | 1 kΩ…1 MΩ |
| Operating temperature | -25…+55 °C |
| Weight | ≤ 150 g |
| Dimensions | 93 x 74,5 x 45 mm |
Part numbers
Show all part numbers (6)
B71016409, B91016409, B71016405, B91016405, clip B98060008, frame XM420 B990994
How it compares with similar models
| Parameter | ISOMETER® IR420-D4 insulation monitoring device for AC IT control circuits, 0…300 V | ISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 V | ISOMETER® IR425-D4 insulation monitor for AC/DC IT systems 0…300 V, response values 1…200 kΩ | ISOMETER® iso415R insulation monitoring device for AC/DC IT systems up to 400 V |
|---|---|---|---|---|
| Nominal system voltage Un | AC 0…300 V | AC 0…300 V | 0…300 V | — |
| Nominal frequency fn | 42…460 Hz | 30…460 Hz | 15…460 Hz | — |
| Response time tan | ≤1 s | ≤ 1 s | — | ≤ 10 s |
| Operating temperature | -25…+55 °C | -25…+55 °C; option W -40…+70 °C | -25…+55 °C | −25…+55 °C |
| Weight | ≤ 150 g | ≤ 150 g | approx. 150 g | ≤ 100 g |
| Dimensions | 93 x 74,5 x 45 mm | 93 x 74.5 x 45 mm | 93 × 74.5 × 70.5 mm | 48.5 x 64 x 18 mm |
Request a price and lead time
ISOMETER® IR420-D4 insulation monitoring device for AC IT control circuits, 0…300 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What kind of system does the IR420-D4 monitor?
Unearthed AC control circuits (IT systems) with a nominal system voltage of AC 0…300 V and a frequency of 42…460 Hz.
How many response values are there and how do they act?
Two separate values of 1…200 kΩ, each with its own changeover relay. The response delay ton is set within 0…99 s and N/O or N/C operation can be selected.
What separates the IR420-D4-1 from the IR420-D4-2?
The supply voltage only: the IR420-D4-1 takes DC 9,6…94 V / AC 16…72 V and the IR420-D4-2 takes AC/DC 70…300 V.