ISOMETER® iso415R insulation monitoring device for AC/DC IT systems up to 400 V
The iso415R from the SmartDetect range monitors insulation resistance in unearthed AC and DC systems. Measuring range 1…10000 kΩ, RS-485 (Modbus RTU) and NFC interfaces, DIN rail mounting in an 18 mm enclosure.
- Supply voltage Us (iso415R-1)
- DC 12…48 V
- Supply voltage Us (iso415R-2)
- AC/DC 100…240 V
- Nominal system voltage Un (iso415R-1)
- 3(N)AC, AC, DC 0…400 V
- Nominal system voltage Un (iso415R-2)
- 3(N)AC, AC, DC 100…240 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The iso415R, part of the SmartDetect range, is an insulation monitoring device for unearthed AC and DC systems (IT systems). It suits large plants with many control circuits, main circuits up to 400 V in small unearthed AC and DC systems without variable-speed drives, and applications that need a communications interface.
The device adapts itself to a system leakage capacitance of up to 25 μF and responds within 10 s. Measured values are shown on LEDs and an alarm is output by LED and relay. Two separately adjustable ranges of response values, 5…1000 kΩ, are provided. The measuring range Rf is 1…10000 kΩ and the display range is 1…1000 kΩ.
Settings are made with rotary potentiometers, with the Connect app over NFC, or over Modbus RTU. The RS-485 interface carries Modbus RTU and the NFC interface is used for configuration from the app.
The iso415R-1 is supplied with DC 12…48 V and monitors 3(N)AC, AC, DC 0…400 V systems. The iso415R-2 is supplied with AC/DC 100…240 V and monitors 3(N)AC, AC, DC 100…240 V systems.
The 18 mm enclosure (48.5 x 64 x 18 mm) clips onto a DIN rail, weighs up to 100 g and has IP20 protection. Operating temperature is −25…+55 °C at altitudes up to 2000 m. Standards include IEC 61557-8, IEC 61010-1, IEC 61010-2-30, IEC 61326-2-4 and IEC 60364-4. A SMARTDETECT ISO41xR connector kit and a sealable transparent cover, SMARTDETECT 41x, are available as accessories.
Technical specifications
| Supply voltage Us (iso415R-1) | DC 12…48 V |
|---|---|
| Supply voltage Us (iso415R-2) | AC/DC 100…240 V |
| Nominal system voltage Un (iso415R-1) | 3(N)AC, AC, DC 0…400 V |
| Nominal system voltage Un (iso415R-2) | 3(N)AC, AC, DC 100…240 V |
| Measuring range Rf | 1…10000 kΩ |
| Display range Rf | 1…1000 kΩ |
| Response value Ran | 5…1000 kΩ |
| Response time tan | ≤ 10 s |
| Permissible leakage capacitance Ce | ≤ 25 μF |
| Operating altitude | ≤ 2000 m |
| Operating temperature | −25…+55 °C |
| Storage temperature | −40…+70 °C |
| Transport temperature | −40…+85 °C |
| Degree of protection | IP20 |
| Weight | ≤ 100 g |
| Dimensions | 48.5 x 64 x 18 mm |
Part numbers
Show all part numbers (2)
B71603000 (iso415R-2), B81604000 (iso415R-1)
How it compares with similar models
| Parameter | ISOMETER® iso415R insulation monitoring device for AC/DC IT systems up to 400 V | ISOMETER® iso685 insulation monitoring device for IT systems, AC up to 690 V and DC up to 1000 V | ISOMETER® iso685-…-B insulation monitoring device for IT systems, AC 0…690 V, DC 0…1000 V | ISOMETER® IR420-D4 insulation monitoring device for AC IT control circuits, 0…300 V |
|---|---|---|---|---|
| Operating temperature | −25…+55 °C | −25…+55 °C | −25…+55 °C | -25…+55 °C |
| Weight | ≤ 100 g | < 390 g | < 390 g | ≤ 150 g |
Request a price and lead time
ISOMETER® iso415R insulation monitoring device for AC/DC IT systems up to 400 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which systems can the iso415R monitor?
Unearthed AC and DC (IT) systems: 3(N)AC, AC, DC 0…400 V for the iso415R-1 and 3(N)AC, AC, DC 100…240 V for the iso415R-2.
How is the device configured?
With rotary potentiometers, with the Connect app over NFC, or over Modbus RTU via RS-485.
What leakage capacitance can it cope with?
It adapts automatically to system leakage capacitances of up to 25 μF, with a response time of no more than 10 s.