International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 V

Insulation monitoring device for unearthed AC systems of 0…300 V supplied by mobile generators according to DIN VDE 0100-551. Two response values, Ran1 and Ran2, each 1…200 kΩ, with leakage capacitance up to 5 μF. Supply versions AC 16…72 V / DC 9.6…94 V or AC/DC 70…300 V.

Nominal system voltage Un
AC 0…300 V
Nominal frequency fn
30…460 Hz
Supply voltage Us
AC 16…72 V / DC 9.6…94 V; AC/DC 70…300 V
Rated insulation voltage
250 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The IR423 ISOMETER® monitors the insulation resistance to earth of an unearthed AC system of 0…300 V supplied by a mobile generator according to DIN VDE 0100-551. It suits AC systems with operating frequencies of 30 Hz and above as well as systems with DC components. Typical uses are mobile generators, mobile or transportable units, auxiliary power generators on pipeline sites, and construction and installation sites. A modified measuring method is used for mobile power generators.

The nominal system voltage Un is AC 0…300 V and the nominal frequency fn is 30…460 Hz. Two alarms, Ran1 (Alarm 1) and Ran2 (Alarm 2), are set separately within 1…200 kΩ. Permissible system leakage capacitance is at most 5 μF. The measuring voltage Um is ± 12 V and the measuring current Im at RF = 0 Ω is at most 200 µA. Response time tan is at most 1 s, start-up delay is 0…10 s and response delay ton is 0…99 s.

The versions differ in supply. IR423-D4-1 runs from AC 16…72 V / DC 9.6…94 V (screw terminals B91016304, push-wire B71016304), and IR423-D4-2 from AC/DC 70…300 V (B91016305 and B71016305). The D4W-1 and D4W-2 versions with option W are for high mechanical stress (B91016304W, B71016304W, B91016305W, B71016305W).

Rated insulation voltage is 250 V, rated impulse voltage 4 kV and pollution degree 3. Operating temperature is -25…+55 °C, or -40…+70 °C with option W. Internal components are rated IP30 and terminals IP20. The unit measures 93 x 74.5 x 45 mm and weighs up to 150 g. It mounts on a DIN rail or with screws, using clip B98060008 and frame XM420 (B990994) for screw mounting.

The design follows DIN VDE 0100-551, IEC 60364-5-551, IEC 61557-8, IEC 61326-2-4, IEC 60664-1, IEC 60664-3 and IEC 61010-1, and the device is CE and UKCA marked.

Technical specifications

Nominal system voltage UnAC 0…300 V
Nominal frequency fn30…460 Hz
Supply voltage UsAC 16…72 V / DC 9.6…94 V; AC/DC 70…300 V
Rated insulation voltage250 V
Rated impulse voltage / pollution degree4 kV / 3
Response value Ran1 (Alarm 1)1…200 kΩ
Response value Ran2 (Alarm 2)1…200 kΩ
Response time tan≤ 1 s
Start-up delay0…10 s
Response delay ton0…99 s
Measuring voltage Um± 12 V
Measuring current Im (at RF = 0 Ω)≤ 200 µA
Permissible system leakage capacitance≤ 5 μF
Operating temperature-25…+55 °C; option W -40…+70 °C
Degree of protection, internal components / terminalsIP30 / IP20
Weight≤ 150 g
Dimensions93 x 74.5 x 45 mm

Part numbers

Show all part numbers (10)

B71016304, B91016304, B71016304W, B91016304W, B71016305, B91016305, B71016305W, B91016305W, accessories B98060008, B990994

How it compares with similar models

ParameterISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 VISOMETER® IR425-D4 insulation monitor for AC/DC IT systems 0…300 V, response values 1…200 kΩISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 VISOMETER® isoHV425 with AGH422 insulation monitoring device for IT systems up to AC/DC 1000 V
Nominal system voltage UnAC 0…300 V0…300 VDC 12…120 VAC/DC 0…1000 V
Supply voltage UsAC 16…72 V / DC 9.6…94 V; AC/DC 70…300 V—AC 100…240 V, 47…63 Hz / DC 24…240 VAC 100…240 V, 47…63 Hz / DC 24…240 V
Operating temperature-25…+55 °C; option W -40…+70 °C-25…+55 °C—-40…+70 °C
Weight≤ 150 gapprox. 150 g—≤ 150 g
Dimensions93 x 74.5 x 45 mm93 × 74.5 × 70.5 mm93 x 90 x 45 mm93 x 70.5 x 36 mm

Request a price and lead time

ISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which systems is the IR423 intended for?

Unearthed AC systems of 0…300 V supplied by a mobile generator according to DIN VDE 0100-551. Permissible system leakage capacitance is up to 5 μF.

How do IR423-D4-1 and IR423-D4-2 differ?

IR423-D4-1 is supplied from AC 16…72 V / DC 9.6…94 V and IR423-D4-2 from AC/DC 70…300 V. Each comes with screw or push-wire terminals.

What does option W mean?

It marks the version for high mechanical stress (IR423-D4W-1, IR423-D4W-2). Its operating temperature range is -40…+70 °C.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides