ISOMETER® isoHV425 with AGH422 insulation monitoring device for IT systems up to AC/DC 1000 V
Insulation monitoring device with a coupling device for unearthed AC, AC/DC and DC systems (IT) up to 1000 V. It watches insulation resistance and system leakage capacitance up to 150 μF, with response value ranges of 10...500 kΩ. Versions with a serial interface or an analogue output.
- Nominal system voltage Un
- AC/DC 0…1000 V
- Nominal system voltage Un for UL508
- AC/DC 0…600 V
- Max. permissible system leakage capacitance Ce
- 150 μF
- Response value ranges
- 10...500 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ISOMETER® isoHV425 is paired with the AGH422 coupling device to monitor insulation resistance in unearthed AC, AC/DC and DC systems (IT systems) with a nominal voltage of AC/DC 0…1000 V. For UL508 the nominal system voltage is AC/DC 0…600 V. Typical uses are AC and DC main circuits up to 1000 V, including systems with switched-mode power supplies.
The device measures insulation resistance and system leakage capacitance, and the permissible leakage capacitance Ce is up to 150 μF. Response value ranges cover 10...500 kΩ. The measuring voltage Um is ±45 V, the measuring current Im is at most 120 μA and the internal resistance Ri, Zi is at least 390 kΩ. The frequency range of Un is DC and 1…460 Hz.
isoHV425-D4-4 with AGH422 has a serial interface, while isoHV425-D4M-4 with AGH422 has an analogue output. The W-variants are isoHV425W-D4-4 with AGH422W and isoHV425W-D4M-4 with AGH422W. Mounting is on a DIN rail or by screws; for screw mounting a mounting clip B98060008 (one piece per device) and a mounting frame XM420 (B990994) are listed.
The supply voltage Us is AC 100…240 V, 47…63 Hz or DC 24…240 V. Rated insulation voltage is 1000 V, rated impulse voltage 8 kV, overvoltage category III and pollution degree 3. Protection is IP30 for built-in components and IP20 for the terminals. Operating temperature is -40…+70 °C, transport -40…+85 °C and storage -55…+80 °C. The unit measures 93 x 70.5 x 36 mm and weighs up to 150 g.
Terminals take AWG 24…12 conductors: rigid or flexible 0.2…2.5 mm², flexible with ferrules 0.25…2.5 mm². Stripping length is 8 mm and tightening torque 0.5…0.6 Nm (5…7 lb-in).
The device is built to DIN EN 61557-8, IEC 61326-2-4, IEC 60664-1, IEC 60664-3 and DIN EN 45545-2:2016, and carries CE and UKCA marks as well as UL508.
Technical specifications
| Nominal system voltage Un | AC/DC 0…1000 V |
|---|---|
| Nominal system voltage Un for UL508 | AC/DC 0…600 V |
| Max. permissible system leakage capacitance Ce | 150 μF |
| Response value ranges | 10...500 kΩ |
| Supply voltage Us | AC 100…240 V, 47…63 Hz / DC 24…240 V |
| Measuring voltage Um | ±45 V |
| Measuring current Im | ≤ 120 μA |
| Internal resistance Ri, Zi | ≥ 390 kΩ |
| Frequency range of Un (sinus) | DC, 1…460 Hz |
| Rated insulation voltage / impulse voltage | 1000 V / 8 kV |
| Overvoltage category / pollution degree | III / 3 |
| Conductor sizes | AWG 24…12; rigid / flexible 0.2…2.5 mm²; flexible with ferrules 0.25…2.5 mm² |
| Operating temperature | -40…+70 °C |
| Degree of protection | IP30 (built-in components); IP20 (terminals) |
| Dimensions | 93 x 70.5 x 36 mm |
| Weight | ≤ 150 g |
Part numbers
Show all part numbers (9)
B71036501, B71036501W, B71036503, B71036503W, B78039032, B98039032, B78039032W, accessories B98060008 (mounting clip), B990994 (mounting frame XM420)
How it compares with similar models
| Parameter | ISOMETER® isoHV425 with AGH422 insulation monitoring device for IT systems up to AC/DC 1000 V | ISOMETER® IR423 insulation monitoring device for mobile generator IT systems AC 0…300 V | ISOMETER® isoCHA425HV with coupling device AGH420-1/AGH421-1 for CCS and CHAdeMO DC charging stations | ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V |
|---|---|---|---|---|
| Nominal system voltage Un | AC/DC 0…1000 V | AC 0…300 V | DC 0…1000 V (CCS), DC 50…1000 V (CHAdeMO) | DC 12…120 V |
| Supply voltage Us | AC 100…240 V, 47…63 Hz / DC 24…240 V | AC 16…72 V / DC 9.6…94 V; AC/DC 70…300 V | — | AC 100…240 V, 47…63 Hz / DC 24…240 V |
| Measuring voltage Um | ±45 V | ± 12 V | ±45 V | — |
| Operating temperature | -40…+70 °C | -25…+55 °C; option W -40…+70 °C | -40…+70 °C | — |
| Dimensions | 93 x 70.5 x 36 mm | 93 x 74.5 x 45 mm | — | 93 x 90 x 45 mm |
Request a price and lead time
ISOMETER® isoHV425 with AGH422 insulation monitoring device for IT systems up to AC/DC 1000 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which voltages does the isoHV425 with AGH422 cover?
IT systems of AC/DC 0…1000 V, or AC/DC 0…600 V for UL508. Permissible system leakage capacitance is up to 150 μF.
What is the difference between the D4 and D4M versions?
isoHV425-D4-4 has a serial interface and isoHV425-D4M-4 has an analogue output. The W versions come with the AGH422W.
What supply and operating conditions apply?
Supply is AC 100…240 V, 47…63 Hz or DC 24…240 V. Operating temperature is -40…+70 °C, with IP30 for built-in components and IP20 for the terminals.
Similar equipment from other manufacturers