ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V
Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT) up to 400 V, made for mobile generators and protective isolation with shutdown. Response values Ran1 up to 250 kΩ and Ran2 from 5 kΩ. RS-485 interface with BMS, Modbus RTU and isoData protocols.
- Rated voltage
- 400 V
- Nominal system voltage Un
- 3(N)AC, AC, DC 0…400 V
- Supply voltage Us
- AC 100…240 V / DC 24…240 V
- Response value Ran1
- Ran2…250 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ISOMETER® isoGEN423 monitors the insulation of unearthed AC, AC/DC and DC systems (IT systems) up to 3(N)AC, AC 400 V, DC 400 V. It is built for mobile generators and for protective isolation with shutdown, and its manual states suitability for generators according to DIN VDE 0100-551. It serves AC and DC main circuits up to 400 V.
There are two response values. Ran1 is set between Ran2 and 250 kΩ, and Ran2 between 5 kΩ and Ran1. Permissible system leakage capacitance Ce is 5 μF and the minimum load current is DC 10 mA. The response time tan is at most 10 s. Rated voltage is 400 V.
The supply voltage Us is AC 100…240 V or DC 24…240 V. A galvanically isolated RS-485 interface carries BMS (9.6 kbit/s), Modbus RTU and isoData (115.2 kbit/s). Cable length is up to 1200 m. Built-in components are rated IP30 and terminals IP20.
isoGEN423-D4-4 has push-wire terminals (B71036325), and the same type with screw-type terminals has the part number B91036325. isoGEN423-D4W-4 (B71036325W) has push-wire terminals and option W for special climatic conditions. The device measures 45 x 70.5 x 93 mm.
It mounts on a DIN rail or with screws; a mounting clip B98060008 (one piece per device) and a mounting frame XM420 (B990994) are available for screw mounting.
The design follows DIN VDE 0100-551, DIN EN 61557-8, DIN IEC/TS 61439-7, IEC 60364-5-51, IEC 60664-1 and IEC 60664-3, and the device is CE and UKCA marked and RoHS compliant.
Technical specifications
| Rated voltage | 400 V |
|---|---|
| Nominal system voltage Un | 3(N)AC, AC, DC 0…400 V |
| Supply voltage Us | AC 100…240 V / DC 24…240 V |
| Response value Ran1 | Ran2…250 kΩ |
| Response value Ran2 | 5 kΩ…Ran1 |
| System leakage capacitance Ce | 5 μF |
| Minimum load current | DC 10 mA |
| Response time tan | ≤ 10 s |
| Baud rate | BMS (9.6 kbit/s), Modbus RTU (selectable), isoData (115.2 kbit/s) |
| Cable length | ≤ 1200 m |
| Degree of protection, built-in components | IP30 |
| Degree of protection, terminals | IP20 |
| Dimensions | 45 x 70.5 x 93 mm |
Part numbers
Show all part numbers (5)
B71036325, B71036325W, B91036325, accessories B98060008, B990994
How it compares with similar models
| Parameter | ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V | ISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 V | ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V | ISOMETER® isoBAT425 with ZE420 insulation monitoring device for batteries up to DC 500 V |
|---|---|---|---|---|
| Nominal system voltage Un | 3(N)AC, AC, DC 0…400 V | 3(N)AC, AC 0…400 V | DC 12…120 V | — |
| Supply voltage Us | AC 100…240 V / DC 24…240 V | AC 100…240 V / DC 24…240 V | AC 100…240 V, 47…63 Hz / DC 24…240 V | AC 100…240 V / DC 24…240 V |
| Response value Ran1 | Ran2…250 kΩ | 2…990 kΩ | 2…100 kΩ | 11…5000 kΩ |
| Response value Ran2 | 5 kΩ…Ran1 | 1…980 kΩ | 1…95 kΩ | 10…4900 kΩ |
| System leakage capacitance Ce | 5 μF | < 100 μF | ≤ 50 μF | — |
| Dimensions | 45 x 70.5 x 93 mm | 93 x 90 x 70.5 mm | 93 x 90 x 45 mm | — |
Request a price and lead time
ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the isoGEN423 intended for?
Mobile generators and protective isolation with shutdown in IT systems up to 3(N)AC, AC 400 V, DC 400 V. The manual states suitability for generators according to DIN VDE 0100-551.
Which response values and leakage capacitance apply?
Ran1 is set between Ran2 and 250 kΩ and Ran2 between 5 kΩ and Ran1. Permissible system leakage capacitance is 5 μF.
How do the D4 and D4W versions differ?
Both have push-wire terminals, and isoGEN423-D4W-4 adds option W for special climatic conditions. The screw-terminal version has part number B91036325.