ISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 V
Insulation monitoring device for unearthed 3(N)AC, AC and DC systems in generator applications according to DIN VDE 0100-551. It is supplied from DC 12…48 V, with response values Ran1 10…250 kΩ and Ran2 5…200 kΩ and leakage capacitance up to 5 μF. RS-485 interface with Modbus RTU, plus NFC.
- Supply voltage Us
- DC 12…48 V
- Nominal system voltage Un
- 3(N)AC, AC, DC 0…400 V
- Frequency range of Un
- 42…460 Hz
- Response value Ran1
- 10…250 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ISOMETER® isoGEN413R-1 monitors the insulation resistance of unearthed 3(N)AC, AC and DC systems (IT systems) in generator applications according to DIN VDE 0100-551, and it is made for mobile generators. The nominal system voltage Un is 3(N)AC, AC, DC 0…400 V and the frequency range of Un is 42…460 Hz.
Two response values are set separately: Ran1 10…250 kΩ and Ran2 5…200 kΩ. Maximum permissible mains leakage capacitance Ce is 5 μF. The supply voltage Us is DC 12…48 V, so the device can run from a vehicle battery, and the power supply is integrated.
Communication uses an RS-485 interface with the Modbus RTU protocol, and the device also has NFC. Connection is by pluggable push-in terminals. The version isoGEN413R-1 has part number B81674000. A SMARTDETECT ISO41xR connector kit for push-in terminals (B80609102) and a sealable transparent cover SMARTDETECT 41x, 49 × 18 × 3 mm (B80609199), are listed as accessories. The article list also includes B94053110, B94053111 and B94053112.
The device follows DIN VDE 0100-551, DIN EN 61557-8, IEC 60364-5-51, BGI 608 and IEC 60947-5-1, and it is CE and UKCA marked.
Technical specifications
| Supply voltage Us | DC 12…48 V |
|---|---|
| Nominal system voltage Un | 3(N)AC, AC, DC 0…400 V |
| Frequency range of Un | 42…460 Hz |
| Response value Ran1 | 10…250 kΩ |
| Response value Ran2 | 5…200 kΩ |
| Max. permissible mains leakage capacitance Ce | 5 μF |
| Protocol | Modbus RTU |
| Interfaces | RS-485, NFC |
| Connection type | Pluggable push-in terminal |
Part numbers
Show all part numbers (6)
B81674000, B94053110, B94053111, B94053112, accessories B80609102, B80609199
How it compares with similar models
| Parameter | ISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 V | ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V | ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V | ISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 V |
|---|---|---|---|---|
| Supply voltage Us | DC 12…48 V | AC 100…240 V / DC 24…240 V | AC 100…240 V, 47…63 Hz / DC 24…240 V | AC 100…240 V / DC 24…240 V |
| Nominal system voltage Un | 3(N)AC, AC, DC 0…400 V | 3(N)AC, AC, DC 0…400 V | DC 12…120 V | 3(N)AC, AC 0…400 V |
| Response value Ran1 | 10…250 kΩ | Ran2…250 kΩ | 2…100 kΩ | 2…990 kΩ |
| Response value Ran2 | 5…200 kΩ | 5 kΩ…Ran1 | 1…95 kΩ | 1…980 kΩ |
Request a price and lead time
ISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What supply voltage does the isoGEN413R-1 use?
DC 12…48 V. The power supply is integrated and suits a vehicle battery.
Which response values and leakage capacitance apply?
Ran1 is 10…250 kΩ and Ran2 is 5…200 kΩ. Maximum mains leakage capacitance is 5 μF.
Which systems and interfaces does it cover?
Unearthed 3(N)AC, AC and DC systems of 0…400 V in generator applications according to DIN VDE 0100-551. It has an RS-485 interface with Modbus RTU and NFC.