International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 V

Insulation monitoring device for unearthed 3(N)AC, AC and DC systems in generator applications according to DIN VDE 0100-551. It is supplied from DC 12…48 V, with response values Ran1 10…250 kΩ and Ran2 5…200 kΩ and leakage capacitance up to 5 μF. RS-485 interface with Modbus RTU, plus NFC.

Supply voltage Us
DC 12…48 V
Nominal system voltage Un
3(N)AC, AC, DC 0…400 V
Frequency range of Un
42…460 Hz
Response value Ran1
10…250 kΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ISOMETER® isoGEN413R-1 monitors the insulation resistance of unearthed 3(N)AC, AC and DC systems (IT systems) in generator applications according to DIN VDE 0100-551, and it is made for mobile generators. The nominal system voltage Un is 3(N)AC, AC, DC 0…400 V and the frequency range of Un is 42…460 Hz.

Two response values are set separately: Ran1 10…250 kΩ and Ran2 5…200 kΩ. Maximum permissible mains leakage capacitance Ce is 5 μF. The supply voltage Us is DC 12…48 V, so the device can run from a vehicle battery, and the power supply is integrated.

Communication uses an RS-485 interface with the Modbus RTU protocol, and the device also has NFC. Connection is by pluggable push-in terminals. The version isoGEN413R-1 has part number B81674000. A SMARTDETECT ISO41xR connector kit for push-in terminals (B80609102) and a sealable transparent cover SMARTDETECT 41x, 49 × 18 × 3 mm (B80609199), are listed as accessories. The article list also includes B94053110, B94053111 and B94053112.

The device follows DIN VDE 0100-551, DIN EN 61557-8, IEC 60364-5-51, BGI 608 and IEC 60947-5-1, and it is CE and UKCA marked.

Technical specifications

Supply voltage UsDC 12…48 V
Nominal system voltage Un3(N)AC, AC, DC 0…400 V
Frequency range of Un42…460 Hz
Response value Ran110…250 kΩ
Response value Ran25…200 kΩ
Max. permissible mains leakage capacitance Ce5 μF
ProtocolModbus RTU
InterfacesRS-485, NFC
Connection typePluggable push-in terminal

Part numbers

Show all part numbers (6)

B81674000, B94053110, B94053111, B94053112, accessories B80609102, B80609199

How it compares with similar models

ParameterISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 VISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 VISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 VISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 V
Supply voltage UsDC 12…48 VAC 100…240 V / DC 24…240 VAC 100…240 V, 47…63 Hz / DC 24…240 VAC 100…240 V / DC 24…240 V
Nominal system voltage Un3(N)AC, AC, DC 0…400 V3(N)AC, AC, DC 0…400 VDC 12…120 V3(N)AC, AC 0…400 V
Response value Ran110…250 kΩRan2…250 kΩ2…100 kΩ2…990 kΩ
Response value Ran25…200 kΩ5 kΩ…Ran11…95 kΩ1…980 kΩ

Request a price and lead time

ISOMETER® isoGEN413R-1 insulation monitoring device for generator IT systems, supply DC 12…48 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What supply voltage does the isoGEN413R-1 use?

DC 12…48 V. The power supply is integrated and suits a vehicle battery.

Which response values and leakage capacitance apply?

Ran1 is 10…250 kΩ and Ran2 is 5…200 kΩ. Maximum mains leakage capacitance is 5 μF.

Which systems and interfaces does it cover?

Unearthed 3(N)AC, AC and DC systems of 0…400 V in generator applications according to DIN VDE 0100-551. It has an RS-485 interface with Modbus RTU and NFC.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides