ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V
Earth fault detection and insulation monitoring in unearthed DC systems up to 120 V. Nominal system voltage is DC 12…120 V, leakage capacitance up to 50 μF, with response values Ran1 2…100 kΩ and Ran2 1…95 kΩ. RS-485 interface with BMS, Modbus RTU and isoData protocols.
- Nominal system voltage Un
- DC 12…120 V
- Supply voltage Us
- AC 100…240 V, 47…63 Hz / DC 24…240 V
- System leakage capacitance Ce
- ≤ 50 μF
- Response value Ran1
- 2…100 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ISOMETER® isoUG425 detects earth faults in unearthed DC systems (IT systems) up to 120 V. Typical installations are simple battery systems, DC control voltage systems and DC lamp circuits. The device monitors asymmetrical insulation resistance.
Nominal system voltage Un is DC 12…120 V and system leakage capacitance Ce may reach 50 μF. Two response values are set: Ran1 2…100 kΩ and Ran2 1…95 kΩ. System voltage monitoring covers undervoltage at 8…143 V and overvoltage at 8,1…144 V. The response time tan is at most 1 s. Start-up delay is 0…10 s, and the response delay ton and delay on release toff are each 0…99 s. The measuring method is passive.
The supply voltage Us is AC 100…240 V, 47…63 Hz or DC 24…240 V, in the version isoUG425-D4-4 (part number B71036320). The device has an LC display, LEDs and alarm relays. The RS-485 interface carries BMS (9.6 kBit/s), Modbus RTU and isoData (115.2 kBit/s). Cable length at 9.6 kBit/s is up to 1200 m, and an internal 120 Ω (0.25 W) terminating resistor can be connected. The device address on the BMS bus and Modbus RTU is 3…90.
Push-wire terminals take AWG 24-14 conductors at a nominal current of up to 10 A: rigid 0.2…2.5 mm², flexible without ferrules 0.75…2.5 mm², flexible with ferrules 0.25…2.5 mm², and multi-conductor flexible with TWIN ferrules 0.5…1.5 mm². Stripping length is 10 mm. Built-in components are rated IP30 and terminals IP20. The enclosure is 93 x 90 x 45 mm and the operating mode is continuous.
Mounting is on a DIN rail or with screws; a mounting clip B98060008 (one piece per device) and a mounting frame XM420 (B990994) are available for screw mounting. The device follows IEC 61557-8, IEC 60664-1, IEC 60664-3 and DIN EN 60529, is CE and UKCA marked and is RoHS compliant.
Technical specifications
| Nominal system voltage Un | DC 12…120 V |
|---|---|
| Supply voltage Us | AC 100…240 V, 47…63 Hz / DC 24…240 V |
| System leakage capacitance Ce | ≤ 50 μF |
| Response value Ran1 | 2…100 kΩ |
| Response value Ran2 | 1…95 kΩ |
| Undervoltage detection UDC | 8…143 V |
| Overvoltage detection UDC | 8,1…144 V |
| Response time tan | ≤ 1 s |
| Start-up delay | 0…10 s |
| Response delay ton / delay on release toff | 0…99 s / 0…99 s |
| Interface/protocol | RS-485/BMS, Modbus RTU, isoData |
| Cable length (9.6 kBit/s) | ≤ 1200 m |
| Connection | Push-wire, AWG 24-14 |
| Nominal current | ≤ 10 A |
| Degree of protection, built-in components | IP30 |
| Degree of protection, terminals | IP20 |
| Dimensions | 93 x 90 x 45 mm |
Part numbers
Show all part numbers (3)
B71036320, accessories B98060008 (mounting clip), B990994 (mounting frame XM420)
How it compares with similar models
| Parameter | ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V | ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V | ISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 V | ISOMETER® isoBAT425 with ZE420 insulation monitoring device for batteries up to DC 500 V |
|---|---|---|---|---|
| Nominal system voltage Un | DC 12…120 V | 3(N)AC, AC, DC 0…400 V | 3(N)AC, AC 0…400 V | — |
| Supply voltage Us | AC 100…240 V, 47…63 Hz / DC 24…240 V | AC 100…240 V / DC 24…240 V | AC 100…240 V / DC 24…240 V | AC 100…240 V / DC 24…240 V |
| System leakage capacitance Ce | ≤ 50 μF | 5 μF | < 100 μF | — |
| Response value Ran1 | 2…100 kΩ | Ran2…250 kΩ | 2…990 kΩ | 11…5000 kΩ |
| Response value Ran2 | 1…95 kΩ | 5 kΩ…Ran1 | 1…980 kΩ | 10…4900 kΩ |
| Dimensions | 93 x 90 x 45 mm | 45 x 70.5 x 93 mm | 93 x 90 x 70.5 mm | — |
Request a price and lead time
ISOMETER® isoUG425 insulation monitoring device for DC IT systems up to 120 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which voltages is the isoUG425 made for?
Unearthed DC systems of DC 12…120 V. System leakage capacitance Ce may be up to 50 μF.
Which response values and delays can be set?
Ran1 within 2…100 kΩ and Ran2 within 1…95 kΩ. Start-up delay is 0…10 s, and response delay and delay on release are 0…99 s.
Which interface and cable length are specified?
RS-485 with BMS, Modbus RTU and isoData. Cable length at 9.6 kBit/s is up to 1200 m.