ISOMETER® isoRW425 insulation monitoring device for IT systems up to AC/DC 440 V, railway applications

Insulation monitoring device for unearthed AC, AC/DC and DC systems up to 3(N)AC, AC/DC 440 V. It operates in R mode (resistance) or Z mode (impedance), with response values Ran1 2…990 kΩ and Zan1 11…500 kΩ. RS-485 interface; push-wire and screw-type terminal versions.

Nominal system voltage Un
3(N)AC, AC/DC 0…440 V
Supply voltage Us
AC 100…240 V / DC 24…240 V
Frequency range Us
47…63 Hz
Frequency range of Un
DC, 15…460 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ISOMETER® isoRW425 monitors insulation in unearthed AC, AC/DC and DC systems (IT systems) up to 3(N)AC, AC/DC 440 V, and its manual describes railway applications. Typical circuits are AC control circuits in railway vehicles to EN 50155, AC control and auxiliary circuits to DIN EN 60204-1, and smaller AC IT systems such as lighting systems and mobile generators.

In R mode the device measures insulation resistance, and in Z mode it measures impedance. Four response values are adjustable: Ran1 2…990 kΩ, Ran2 1…980 kΩ, Zan1 11…500 kΩ and Zan2 10…490 kΩ. Voltage monitoring covers undervoltage U< at 10…499 V and overvoltage U> at 11…500 V. Maximum permissible system leakage capacitance Ce is 300 μF in R mode and 1 μF in Z mode. The frequency range of Un is DC and 15…460 Hz.

The response time tan is at most 10 s at RF = 0.5 x Ran and Ce = 1 μF, and at most 5 s at ZF = 0.5 x Zan. Start-up delay is 0…10 s, and response delay ton and delay on release toff are each 0…99 s. The operating mode is continuous.

Supply voltage Us is AC 100…240 V, 47…63 Hz or DC 24…240 V, with power consumption of at most 3 W and 9 VA. Rated voltage is 440 V and overvoltage category III. An RS-485 interface carries the BMS, Modbus RTU and isoData protocols. Built-in components are rated IP30 and terminals IP20, and the flammability class is UL 94V-0. The enclosure measures 93 x 90 x 70.5 mm.

B71037000W has push-wire terminals and B91037000W has screw-type terminals. The device mounts on a DIN rail or with screws; for screw mounting a mounting clip B98060008 (one piece per device) and a mounting frame XM420 (B990994) are available.

The design follows IEC 60664-1, IEC 60664-3, IEC 61557-8, EN 50155, DIN EN 60204-1, IEC 60204-1, DIN VDE 0100-725, DIN EN 60529 and UL508, and the device is CE and UKCA marked.

Technical specifications

Nominal system voltage Un3(N)AC, AC/DC 0…440 V
Supply voltage UsAC 100…240 V / DC 24…240 V
Frequency range Us47…63 Hz
Frequency range of UnDC, 15…460 Hz
Rated voltage440 V
Overvoltage categoryIII
Power consumption≤ 3 W, ≤ 9 VA
Response value Ran1 / Ran22…990 kΩ / 1…980 kΩ
Response value Zan1 / Zan211…500 kΩ / 10…490 kΩ
Undervoltage detection U<10…499 V
Overvoltage detection U>11…500 V
Response time tan (RF = 0.5 x Ran, Ce = 1 μF)≤ 10 s
Response time tan (ZF = 0.5 x Zan)≤ 5 s
Max. permissible system leakage capacitance Ce300 μF (R mode), 1 μF (Z mode)
Interface/protocolsRS-485; BMS, Modbus RTU, isoData
Degree of protection, built-in components / terminalsIP30 / IP20
Flammability classUL 94V-0
Dimensions93 x 90 x 70.5 mm

Part numbers

Show all part numbers (4)

B71037000W (push-wire), B91037000W (screw-type terminal), accessories B98060008, B990994

How it compares with similar models

ParameterISOMETER® isoRW425 insulation monitoring device for IT systems up to AC/DC 440 V, railway applicationsISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 VISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 VISOMETER® isoBAT425 with ZE420 insulation monitoring device for batteries up to DC 500 V
Nominal system voltage Un3(N)AC, AC/DC 0…440 V3(N)AC, AC 0…400 V3(N)AC, AC, DC 0…400 V—
Rated voltage440 V400 V400 V400 V
Dimensions93 x 90 x 70.5 mm93 x 90 x 70.5 mm45 x 70.5 x 93 mm—

Request a price and lead time

ISOMETER® isoRW425 insulation monitoring device for IT systems up to AC/DC 440 V, railway applications. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the difference between R mode and Z mode?

R mode measures insulation resistance and Z mode measures impedance. Permissible leakage capacitance is 300 μF in R mode and 1 μF in Z mode.

How do B71037000W and B91037000W differ?

B71037000W has push-wire terminals and B91037000W has screw-type terminals. The other data are the same.

Which systems is the isoRW425 intended for?

Unearthed IT systems up to 3(N)AC, AC/DC 440 V, including AC control circuits in railway vehicles to EN 50155 and circuits to DIN EN 60204-1.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides