ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V
The iso1685DP, isoHV1685D and isoLR1685DP series monitors unearthed AC, AC/DC and DC IT systems. Three versions cover AC 690 V / DC 690 V, AC 1000 V / DC 1500 V and AC 2000 V / DC 3000 V.
- Purpose
- Insulation monitoring of unearthed IT systems
- Range isoLR1685DP-325
- 20 Ω…100 kΩ
- Range iso1685DP-425, isoHV1685D-425
- 200 Ω…1 MΩ
- System voltage isoLR1685DP-325
- AC 0…690 V / DC 0…690 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The iso1685DP, isoHV1685D and isoLR1685DP monitor insulation in unearthed AC, AC/DC and DC IT systems. They use the AMPPlus measuring method, which adapts automatically to the leakage capacitance of the system. The measuring range depends on the version.
The isoLR1685DP-325 suits low insulation levels, measuring 20 Ω…100 kΩ at AC 0…690 V / DC 0…690 V. The iso1685DP-425 measures 200 Ω…1 MΩ at AC 0…1000 V / DC 0…1500 V. The isoHV1685D-425 measures 200 Ω…1 MΩ in systems of AC 2000 V / DC 3000 V.
Response values are adjusted separately. A graphical LC display plots insulation resistance over time (isoGraph), and the history memory has a real-time clock. Digital inputs and outputs are freely programmable. For fault location the device generates locating current pulses, which permanently installed or mobile locators pick up.
Data exchange runs over RS-485 with BMS and Modbus RTU. The supply voltage is DC 18…30 V, weight is up to 1600 g and the degree of protection is IP30.
Mounting is on a DIN rail. The devices comply with IEC 61557-8, including Appendix C, and carry CE and UKCA marks.
Technical specifications
| Purpose | Insulation monitoring of unearthed IT systems |
|---|---|
| Range isoLR1685DP-325 | 20 Ω…100 kΩ |
| Range iso1685DP-425, isoHV1685D-425 | 200 Ω…1 MΩ |
| System voltage isoLR1685DP-325 | AC 0…690 V / DC 0…690 V |
| System voltage iso1685DP-425 | AC 0…1000 V / DC 0…1500 V |
| System voltage isoHV1685D-425 | AC 0…2000 V / DC 0…3000 V |
| Supply voltage | DC 18…30 V |
| Weight | ≤ 1600 g |
| Degree of protection | IP30 |
| Interface and protocols | RS-485, BMS, Modbus RTU |
| Mounting | DIN rail |
| Standard | IEC 61557-8; IEC 61557-8 Appendix C |
Part numbers
Show all part numbers (3)
B91065803, B91065805, B91065802
How it compares with similar models
| Parameter | ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V | ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V | ISOMETER® isoMED527 insulation monitor for medical IT systems, AC 100…240 V, NFC and RS-485 | ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V |
|---|---|---|---|---|
| Purpose | Insulation monitoring of unearthed IT systems | Insulation monitoring of unearthed IT systems | Insulation monitoring of medical IT systems | Insulation monitoring of IT systems in PV plants and BESS |
| Weight | ≤ 1600 g | ≤ 510 g | ≤ 130 g | ≤1600 g |
| Degree of protection | IP30 | IP30 | IP20 | IP30 |
Request a price and lead time
ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the iso1685DP-425, isoHV1685D-425 and isoLR1685DP-325 differ?
In system voltage and range: the iso1685DP-425 goes to AC 1000 V / DC 1500 V, the isoHV1685D-425 to AC 2000 V / DC 3000 V, and the isoLR1685DP-325 to AC 690 V / DC 690 V with a 20 Ω…100 kΩ range.
Which interfaces are provided?
RS-485 with BMS and Modbus RTU.
What is the supply voltage?
DC 18…30 V.