ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V

The iso1685DP, isoHV1685D and isoLR1685DP series monitors unearthed AC, AC/DC and DC IT systems. Three versions cover AC 690 V / DC 690 V, AC 1000 V / DC 1500 V and AC 2000 V / DC 3000 V.

Purpose
Insulation monitoring of unearthed IT systems
Range isoLR1685DP-325
20 Ω…100 kΩ
Range iso1685DP-425, isoHV1685D-425
200 Ω…1 MΩ
System voltage isoLR1685DP-325
AC 0…690 V / DC 0…690 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The iso1685DP, isoHV1685D and isoLR1685DP monitor insulation in unearthed AC, AC/DC and DC IT systems. They use the AMPPlus measuring method, which adapts automatically to the leakage capacitance of the system. The measuring range depends on the version.

The isoLR1685DP-325 suits low insulation levels, measuring 20 Ω…100 kΩ at AC 0…690 V / DC 0…690 V. The iso1685DP-425 measures 200 Ω…1 MΩ at AC 0…1000 V / DC 0…1500 V. The isoHV1685D-425 measures 200 Ω…1 MΩ in systems of AC 2000 V / DC 3000 V.

Response values are adjusted separately. A graphical LC display plots insulation resistance over time (isoGraph), and the history memory has a real-time clock. Digital inputs and outputs are freely programmable. For fault location the device generates locating current pulses, which permanently installed or mobile locators pick up.

Data exchange runs over RS-485 with BMS and Modbus RTU. The supply voltage is DC 18…30 V, weight is up to 1600 g and the degree of protection is IP30.

Mounting is on a DIN rail. The devices comply with IEC 61557-8, including Appendix C, and carry CE and UKCA marks.

Technical specifications

PurposeInsulation monitoring of unearthed IT systems
Range isoLR1685DP-32520 Ω…100 kΩ
Range iso1685DP-425, isoHV1685D-425200 Ω…1 MΩ
System voltage isoLR1685DP-325AC 0…690 V / DC 0…690 V
System voltage iso1685DP-425AC 0…1000 V / DC 0…1500 V
System voltage isoHV1685D-425AC 0…2000 V / DC 0…3000 V
Supply voltageDC 18…30 V
Weight≤ 1600 g
Degree of protectionIP30
Interface and protocolsRS-485, BMS, Modbus RTU
MountingDIN rail
StandardIEC 61557-8; IEC 61557-8 Appendix C

Part numbers

Show all part numbers (3)

B91065803, B91065805, B91065802

How it compares with similar models

ParameterISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 VISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 VISOMETER® isoMED527 insulation monitor for medical IT systems, AC 100…240 V, NFC and RS-485ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V
PurposeInsulation monitoring of unearthed IT systemsInsulation monitoring of unearthed IT systemsInsulation monitoring of medical IT systemsInsulation monitoring of IT systems in PV plants and BESS
Weight≤ 1600 g≤ 510 g≤ 130 g≤1600 g
Degree of protectionIP30IP30IP20IP30

Request a price and lead time

ISOMETER® iso1685DP, isoHV1685D and isoLR1685DP insulation monitors for IT systems up to AC 2000 V / DC 3000 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the iso1685DP-425, isoHV1685D-425 and isoLR1685DP-325 differ?

In system voltage and range: the iso1685DP-425 goes to AC 1000 V / DC 1500 V, the isoHV1685D-425 to AC 2000 V / DC 3000 V, and the isoLR1685DP-325 to AC 690 V / DC 690 V with a 20 Ω…100 kΩ range.

Which interfaces are provided?

RS-485 with BMS and Modbus RTU.

What is the supply voltage?

DC 18…30 V.