International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DC

The LINETRAXX® RCMS460-L evaluates fault, residual and operating currents on 12 channels with Type A or Type B transformers. Up to 90 monitors on a BMS bus (RS-485) cover as many as 1080 sub-circuits.

Number of measuring channels
12
Response ranges
10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)
Frequency response
0…2000 Hz, 42…2000 Hz
Supply voltage US (L-1)
DC 16…94 V / AC 16…72 V, 42…460 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Earthed power supplies are monitored by the LINETRAXX® RCMS460-L, which detects and evaluates fault, residual and operating currents. Its tasks include personnel protection, fire protection, plant protection, monitoring of N conductors, monitoring of PE and equipotential bonding conductors, flammable atmospheres and EMC monitoring of TN-S systems.

Each device has up to 12 measuring channels, connected through current transformers of Type A or Type B. AC, pulsed DC and AC/DC sensitive measurement are supported. The frequency response is adjustable to the protection task, either 0…2000 Hz or 42…2000 Hz. Response ranges are 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz) and 100 mA…125 A (42…2000 Hz). Harmonics, DC and THD are analysed.

The history memory holds 300 data records and the data logger 300 data records per channel. Two alarm relays, each with one changeover contact, signal alarms. A BMS bus (RS-485) links up to 90 monitors for up to 1080 sub-circuits. Repeaters and interface converters COM465IP, CP907-I and CP915-I are offered for connection to other networks.

The RCMS460-L-1 runs from DC 16…94 V / AC 16…72 V, 42…460 Hz and the RCMS460-L-2 from DC 70…276 V / AC 70…276 V, 42…460 Hz. Options include transformers CTBS25, CTUB100, CTAC, WR, WS, WF and power supply units of the STEP-PS series. The device is RoHS compliant, with IEC/TR 60755 and DGUV V3 listed as standards.

Technical specifications

Number of measuring channels12
Response ranges10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)
Frequency response0…2000 Hz, 42…2000 Hz
Supply voltage US (L-1)DC 16…94 V / AC 16…72 V, 42…460 Hz
Supply voltage US (L-2)DC 70…276 V / AC 70…276 V, 42…460 Hz
Alarm relays2, one changeover contact each
History memory300 data records
Data logger300 data records per channel
Max. monitors on the bus90
Max. channels in the system1080
Interface / protocolRS-485 / BMS
Type to IEC/TR 60755Type A, Type B

Part numbers

Show all part numbers (2)

B94053003, B94053004

How it compares with similar models

ParameterLINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DCLINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DCLINETRAXX® RCMS460-D residual current monitor for earthed systems, 12 channelsLINETRAXX® RCMS490-D multi-channel residual current monitor, 12 channels
Response ranges10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz)10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz)10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz)
Alarm relays2, one changeover contact each2 changeover + one contact per channelTwo relays with one changeover contact eachTwo relays with one changeover contact each
Data logger300 data records per channel—300 data records/channel300 data records/channel

Request a price and lead time

LINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DC. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many monitors and channels does a BMS bus link?

Up to 90 monitors, giving up to 1080 channels in the system.

Which transformers can be connected?

Current transformers of Type A or Type B, including CTBS25, CTUB100, CTAC, WR, WS and WF.

How do the RCMS460-L-1 and L-2 differ?

By supply voltage: the L-1 takes DC 16…94 V / AC 16…72 V, the L-2 DC 70…276 V / AC 70…276 V.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides