LINETRAXX® RCMS490-D multi-channel residual current monitor, 12 channels
Residual current monitor with 12 measuring channels for earthed power supplies. It works with Type A and Type B measuring current transformers and offers response ranges from 6 mA to 125 A. Up to 90 monitors and 1080 channels can share one BMS bus.
- Measuring channels
- 12
- Max. monitors in system
- 90
- Max. channels in system
- 1080
- Response ranges
- 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Residual, fault and operating currents in earthed power supplies are measured and evaluated by the LINETRAXX® RCMS490-D through measuring current transformers. It has 12 measuring channels and serves as an alternative to periodic insulation testing. Depending on the transformer, alternating, pulsating or AC/DC sensitive residual currents are detected, in line with Type A and Type B of IEC/TR 60755.
Harmonics, DC and THD are analysed, and the frequency response is adjustable. Response ranges are 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz) and 100 mA…125 A (42…2000 Hz). A history memory keeps 300 data records and the data logger holds 300 data records per channel.
There are two alarm relays with one changeover contact each. A backlit graphical display and alarm LEDs show the status. Over the BMS bus (RS-485 with BMS protocol), up to 90 monitors can be connected, giving up to 1080 channels in one system. The data for this series also lists an Ethernet interface and Modbus TCP and SNMP protocols.
Versions: RCMS490-D-1 and RCMS490-D4-1 with supply DC 16…94 V / AC 16…72 V, 42…460 Hz; RCMS490-D-2 and RCMS490-D4-2 with supply DC 70…276 V / AC 70…276 V, 42…460 Hz. Codes: B94053005, B94053011, B94053006, B94053012.
Matching accessories are measuring current transformers of the CTBS25, CTUB100, CTAC, WR, WS and WF series, STEP-PS power supply units, COM465IP, CP907-I and CP915-I interface devices, MK2430 alarm indicators, and the mounting frames XM460 (B990995) and XM490 (B990996).
Listed applications: measuring residual, fault and rated currents; monitoring currents regarded as fire hazards in flammable atmospheres; EMC monitoring of TN-S systems; monitoring N conductors for overload caused by harmonics; monitoring PE and equipotential bonding conductors; residual current monitoring of stationary electrical equipment; fire protection by rapid disconnection; and monitoring of digital inputs.
Technical specifications
| Measuring channels | 12 |
|---|---|
| Max. monitors in system | 90 |
| Max. channels in system | 1080 |
| Response ranges | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) |
| History memory | 300 data records |
| Data logger | 300 data records/channel |
| Alarm relays | Two relays with one changeover contact each |
| Display | Backlit graphical display and alarm LEDs |
| Interface | BMS bus (RS-485, BMS protocol) |
| Supply D-1 / D4-1 | DC 16…94 V / AC 16…72 V, 42…460 Hz |
| Supply D-2 / D4-2 | DC 70…276 V / AC 70…276 V, 42…460 Hz |
| Transformer types | IEC/TR 60755: Type A, Type B |
Part numbers
Show all part numbers (4)
B94053005, B94053011, B94053006, B94053012
How it compares with similar models
| Parameter | LINETRAXX® RCMS490-D multi-channel residual current monitor, 12 channels | LINETRAXX® RCMS460-D residual current monitor for earthed systems, 12 channels | LINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DC | LINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DC |
|---|---|---|---|---|
| Response ranges | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) | 10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz) | 10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz) |
| Data logger | 300 data records/channel | 300 data records/channel | 300 data records per channel | — |
| Alarm relays | Two relays with one changeover contact each | Two relays with one changeover contact each | 2, one changeover contact each | 2 changeover + one contact per channel |
| Interface | BMS bus (RS-485, BMS protocol) | RS-485 | — | RS-485, BMS bus |
Request a price and lead time
LINETRAXX® RCMS490-D multi-channel residual current monitor, 12 channels. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many channels does the RCMS490-D have, and how many per system?
12 measuring channels per device; up to 90 monitors can be linked on the BMS bus, which gives up to 1080 channels.
Which response ranges are available?
10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz) and 100 mA…125 A (42…2000 Hz).
Which current transformers can be connected?
Type A and Type B measuring current transformers, including the CTBS25, CTUB100, CTAC, WR, WS and WF series.
Similar equipment from other manufacturers